15
8
Accessories
14
Connections
7
Horizontal (HT)
Vertical (VT)
Front (FT)
Fixed type
(FIX)
Drawout type
(DR)
Connections
Type
Connections
• Connection image: AED630-CV to AED1600-CV, 3-pole type
FIX-HT
FIX-VT
FIX-FT
DR-HT
DR-VT
DR-FT
Overview (AED630-CV to AED1600-CV)
Type
LINE (upper) side/LOAD (lower) side
Abbreviation
AED630-CV/AED1000-CV/AED1250-CV/AED1600-CV
Fixed type
(FIX)
Horizontal/Horizontal
FIX-HT
Available
Vertical/Vertical
FIX-VT
Front/Front
FIX-FT
Horizontal/Vertical
FIX (HV)
Horizontal/Front
FIX (HF)
Vertical/Horizontal
FIX (VH)
Vertical/Front
FIX (VF)
Front/Horizontal
FIX (FH)
Front/Vertical
FIX (FV)
Drawout type
(DR)
Horizontal/Horizontal
DR-HT
Vertical/Vertical
DR-VT
Front/Front
DR-FT
Horizontal/Vertical
DR (HV)
Horizontal/Front
DR (HF)
Vertical/Horizontal
DR (VH)
Vertical/Front
DR (VF)
Front/Horizontal
DR (FH)
Front/Vertical
DR (FV)
Available connections
The shunt trip device is a device to open the breaker by remote control.
Shunt trip device (SHT)
1
Note 1) While the voltage is applied to the input terminals (C1 and C2), the SHT keeps the
breaker in the open state and the closing operation is cancelled. Therefore, the SHT can
be used as an interlock for locking the breaker in the open state.
Note 2) In case of double rating of rated voltage, it is the value for the lower rating. (Example) In
case of 24-30 V DC, it is operating time for 24 V DC.
Diode rectifier is not used for control source 24-30 V DC and
48-60 V DC.
Accessories
2
3
1
4
6
5
SHT
Breaker
Control
supply
Coil
C1
C2
Circuit for
locking the
breaker
OFF position
SHT circuit diagram
Option
Under voltage trip device
OCR alarm
Shunt trip device
Auxiliary switch
Standard/Low capacity type
Counter
Cylinder lock
For breaker unit
Rated voltage
(Applicable
voltage)
Frequency
(AC)
Steady power
consumption
(Note 1)
Operating
time
(Note 2)
Operating
voltage
24-30 V DC
(16.8-33 V)
–
24 V
4 A 100 W
20 VA
0.05 s
max.
30 V
5 A 150 W
48-60 V DC
(33.6-66 V)
48 V
2.5 A 120 W
60 V
3 A 180 W
100-125 V AC/DC
(70-137.5 V)
50/60 Hz
100 V 1 A 100 VA
125 V 1.2 A 150 VA
200-250 V AC/DC
(140-275 V)
200 V 1 A 200 VA
250 V 1.1 A 280 VA
Inrush current and
power consumption