Air Handling Unit Interface
AHU-KIT-SP
MORIKAWA
SPECIFICATION
PSZ000Z308
18/38
MODEL NAME
MODEL TYPE
ISSUE
CLASSIFICATION
DWG NO.
REV.MARK PAGE
21.09.17
9.
Rotation control
・
In cascade control, rotation control is automatically enabled.
・
This control averages the compressor accumulated time of all outdoor units.
・
When the outdoor unit starts operating, the outdoor unit with the lowest compressor accumulated time is preferentially operated.
・
When 12 hours have elapsed since the outdoor unit started operating, the outdoor unit will be switched.
*Operation switching time: 12 hours is fixed.
・
This is an example of rotation control.
Rotation control example