Air Handling Unit Interface
AHU-KIT-SP
MORIKAWA
SPECIFICATION
PSZ000Z308
2/38
MODEL NAME
MODEL TYPE
ISSUE
CLASSIFICATION
DWG NO.
REV.MARK PAGE
21.09.17
1. Specifications
AHU-KIT-SP (AHU interface) is the controller dedicated to making the AHU system by using a split type outdoor unit.
AHU interface equips 0–10V and 4–20mA analog input as a basic capacity control method of the connected outdoor unit.
As an alternative control method, the setting temperature control can be used from the remote controller as well.
In addition, AHU interface can communicate over the Modbus protocol and it enables the capacity control (0–100%) or setting temperature control according to requirements.
For more details, please see the relevant sections.
Model
AHU-KIT-SP
Outdoor unit compatibility
See below (*1)
Usage environment
Temperature
:
-20
~
60
℃
Relative humidity
:
less than 85% RH (without condensation)
Storage environment
Temperature
:
-20
~
70
℃
Relative humidity
:
40%
~
90% RH (without condensation)
Power supply
Single phase 220–240V
+10%
,
-15%
50Hz
Single phase 220V
+10%
,
-15%
60Hz
Power consumption
5W
Product dimensions
(height×width×depth)
109.5 mm × 290 mm × 57 mm
Weight
0.55 kg
Installation
DIN rail TS 35 mm × 7.5 mm (separate DIN rail required)
Cascade connection
Max 16 outdoor units can be combined by cascade control
(16 interfaces are required)
Power blackout compensation
This interface does not have a battery circuit for power blackout recovery.
Operation can continue
:
The power blackout duration is 30 msec or less.
Heat exchanger sensor (Thi-R1
,
Thi-R2
,
Thi-R3)×1
Return air sensor (Thi-A)×1
Reserve sensor×1
Spring leaf for heat exchanger sensor ×3
Ferrite core for functional ground wire ×1
Installation manual
Caution label
Accessories
(* 1) Connectable outdoor unit
R410A
R32
40/50/60
SRC40/50/60ZSX-S, SA
SRC40/50/60ZSX-W1, W2, WA
71
FDC71VNX
FDC71VNX-W
FDC100/125/140VN(S)A
FDC100/125/140VN(S)A-W
FDC100/125/140VN(S)X
FDC100/125/140VN(S)X-W
200/250
FDC200/250VSA
FDC200/250VSA-W
280
FDC280VSA-W
Model
capacity
Outdoor unit
100/125/140