11. Modbus communication
・
X5 is Modbus communication connector.
・
Modbus communication specifications are as follows.
Item
Specification
Note
Transmission mode
RTU (remote terminal unit)
(1) 9600bps
DipSW7-2
ON
(2) 19200bps
DipSW7-2
OFF
Data bit
8
(1) Non 2 stop bits
DipSW7-3
ON
(2) Even 1 stop bit
DipSW7-3
OFF
Node number
RotarySW5: ones place
(slave address)
RotarySW6: tens place
X5-1: A polar
X5-2: B polar
X5-3: GND
Modbus master:
External controller : 1pcs
Modbus slave:
AHU interface :1pcs
01
~
99 (initial
:
01)
Combinations
Transmission speed
Parity/stop bit
Connection
RS-485 communication
・
Modbus can monitor the status of the AHU interface and outdoor units.
Modbus can also change some settings.
●
Modbus function
・
The function codes are as follows:
Function name
Remarks
3 (0x03)
Read holding register
Read the contents of the holding register
4 (0x04)
Read input register
Read the contents of the input register
6 (0x06)
Preset single register
Change the contents of the holding register
16 (0x10)
Preset multiple registers
Change the contents of multiple consecutive holding registers
Function code
●
Modbus data information
・
Modbus data type, data length and address allocation range are as follows.
Target register
Data length
Type of access
Register address range
Input register
2 byte
Monitoring only
30001
~
39999
Holding register
2 byte
Monitoring / control
40001
~
49999