Air Handling Unit Interface
AHU-KIT-SP
MORIKAWA
SPECIFICATION
PSZ000Z308
23/38
MODEL NAME
MODEL TYPE
ISSUE
CLASSIFICATION
DWG NO.
REV.MARK PAGE
21.09.17
Data address
Item
Range
Units
Notes
30010
Analogue input voltage [V]
0
~
65535
0.1 V/count
0
~
10V
30011
Analogue input current [mA]
0
~
65535
0.1 mA/count 0
~
20mA
30012
Digital input X2-1
0
~
65535
-
0
:
OFF 1
:
ON
30013
Digital input X2-2
0
~
65535
-
0
:
OFF 1
:
ON
30014
Digital input X2-3
0
~
65535
-
0
:
OFF 1
:
ON
30015
Digital input X2-4
0
~
65535
-
0
:
OFF 1
:
ON
30016
Digital output X4a
0
~
65535
-
0
:
OFF 1
:
ON
30017
Digital output X4b
0
~
65535
-
0
:
OFF 1
:
ON
30018
Digital output X4c
0
~
65535
-
0
:
OFF 1
:
ON
30019
Digital output X4d
0
~
65535
-
0
:
OFF 1
:
ON
0
:
0
~
10V
1
:
4
~
20mA
0
:
19200bps
1
:
9600bps
0
:
Even parity
+1Stop bit
1
:
Non parity
+2Stop bit
0
:
Capacity control
1
:
Temperature control
30024
SW8-1 Setting display
0
~
65535
-
0
:
Run/Stop
1
:
Cooling/Heating
30025
SW8-2 Setting display
0
~
65535
-
0
30026
SW8-3 Setting display
0
~
65535
-
0
30027
Reserve
0
~
65535
-
Reserve
30028
SW7-1 Reading value
0
~
65535
-
0
:
OFF 1
:
ON
30029
SW7-2 Reading value
0
~
65535
-
0
:
OFF 1
:
ON
30030
SW7-3 Reading value
0
~
65535
-
0
:
OFF 1
:
ON
30031
SW7-4 Reading value
0
~
65535
-
0
:
OFF 1
:
ON
30032
SW8-1 Reading value
0
~
65535
-
0
:
OFF 1
:
ON
30033
SW8-2 Reading value
0
~
65535
-
0
:
OFF 1
:
ON
30034
SW8-3 Reading value
0
~
65535
-
0
:
OFF 1
:
ON
30035
SW8-4 Reading value
0
~
65535
-
0
:
OFF 1
:
ON
30036
Modbus capacity control command display
0
~
65535
-
0
:
No command 1
:
Command
30037
Modbus capacity control value display
0
~
65535
0.01% count
0-100%
30020
Analogue input switching
0
~
65535
-
30023
Compressor control
0
~
65535
-
30021
Modbus baudrate setting
0
~
65535
-
30022
Modbus
Parity/Stop bit setting
0
~
65535
-