Air Handling Unit Interface
AHU-KIT-SP
MORIKAWA
SPECIFICATION
PSZ000Z308
30/38
MODEL NAME
MODEL TYPE
ISSUE
CLASSIFICATION
DWG NO.
REV.MARK PAGE
21.09.17
●
Holding register
・
The holding registers (readable, changeable, 2-byte data) are as follows.
Data address
Item
Initial
Range
Units
Notes
0: stop
1: run
0: cooling
1: heating
40003
Set temperature command
46
(23
℃
)
36
~
60
0.5
℃
/count
36=18
℃
60=30
℃
0
:
emergency stop release
1
:
emergency stop
40006
CPU
reset command
0
0
~
1
-
0: NOP
1: reset
Compressor accumulated
time
all reset command
0–100%
40005
0
0
~
1
-
40007
0
0
~
1
-
40001
Emergency stop
command
Capacity Control
command
Run/stop
command
0
0
~
1
-
40002
Operation mode command
0
0
~
1
-
0: NOP
1: reset
40008
0
0
~
10000 0.01 /count
If data outside the range is received, the data is not accepted and an error is returned.