Air Handling Unit Interface
AHU-KIT-SP
MORIKAWA
SPECIFICATION
PSZ000Z308
5/38
MODEL NAME
MODEL TYPE
ISSUE
CLASSIFICATION
DWG NO.
REV.MARK PAGE
21.09.17
●
Heat exchanger, minimum airflow and recommended circuits
・
Be sure to select and set the capacity of the heat exchanger connected to each outdoor unit and the minimum air volume according to the following table.
・
The table below is for both R 32 and R 410 A refrigerants.
・
The range of use for air conditions conforms to the specifications of the outdoor unit.
Refer to the technical manual for the outdoor unit.
Min
Max
m
3
/h
m
3
/min
SRC40
0.3
0.8
420
7
SRC50
0.3
0.9
420
7
SRC60
0.5
1.1
480
8
FDC71
0.7
1.6
600
10
FDC100
0.7
2.1
840
14
FDC125
1.0
2.2
960
16
FDC140
1.0
2.8
1080
18
FDC200
1.2
4.2
1680
28
FDC250
2.0
4.4
1920
32
FDC280
2.0
4.4
2160
36
Outdoor unit
model capacity
Allowable heat exchanger
volume
L
Minimum air volume
・
Recommended circuit number for D9.52 tube
Outdoor unit model capacity
40 50 60 71 100 125 140 200 250 280
Recommended circuit
2
〜
4
4
〜
6
6
〜
10