8
Station
number
setting
switch
With the STATION NO. "10", "20", and "40" switches, the tens place of the
station number is set.
With the STATION NO. "1", "2", "4", and "8" switches, the ones place of the
station number is set.
These switches are all set to off at default.
A station number must be set within 1 to 64.
Setting any number other than that will result in an error, and the L ERR.
LED will turn on.
The same station number cannot be set to several stations.
(Example) To specify "32" for a station number, set the switches as shown
below.
Use
prohibited
All switches must be set to off.
Terminal
block for
transmission
and module
power supply
lines
A terminal block for transmission and module power supply lines
Table 3.1 Part names
No.
Name
Description
4
Station
number
Tens place
Ones place
40
20
10
8
4
2
1
1
OFF
OFF
OFF
OFF
OFF
OFF
ON
2
OFF
OFF
OFF
OFF
OFF
ON
OFF
3
OFF
OFF
OFF
OFF
OFF
ON
ON
4
OFF
OFF
OFF
OFF
ON
OFF
OFF
10
OFF
OFF
ON
OFF
OFF
OFF
OFF
11
OFF
OFF
ON
OFF
OFF
OFF
ON
64
ON
ON
OFF
OFF
ON
OFF
OFF
Station
number
Tens place
Ones place
40
20
10
8
4
2
1
1
OFF
ON
ON
OFF
OFF
ON
OFF
5
6
Terminal
Description
DA
Terminals for connecting CC-Link dedicated
cables
DB
DG
SLD
FG
A terminal for grounding to the protective ground
conductor
+24V
Terminals for connecting an external power supply
24G