10
4. LOADING AND INSTALLATION
4.1 Handling Precautions
This section describes precautions for handling the AJ65SBT2B-64AD.
(1) Tighten screws (such as a module fixing screw) within the
tightening torque range specified in the table below.
(2) When using a DIN rail, pay attention to the following:
(a) Applicable DIN rail (compliant with IEC 60715)
TH35-7.5Fe
TH35-7.5Al
(b) Installation screw intervals
Tighten the screws at intervals of 200mm or less.
(3) When mounting the AJ65SBT2B-64AD to a DIN rail, push in the
DIN rail hook until it clicks.
Figure 4.1 Mounting a module to a DIN rail
(4) For names, specifications, and manufacturers of applicable cables,
refer to the user’s manual for the master module used.
Table 4.1 Tightening torque range
Screw
Tightening torque range
Module mounting screw (M4)
0.78 to 1.08N•m
Terminal block terminal screw (M3)
Vis de borne sur plaque à bornes(vis M3)
0.59 to 0.88N•m
0,59 à 0,88 N•m
Terminal block mounting screw (M3.5)
0.68 to 0.98N•m
DIN rail
DIN rail hook