外部接続
(External connection)
ピン配列
Pin arrangement
端子番号
Terminal
No.
信号名
Signal
name
ピン番号
Pin
No.
信号名
Signal
name
TB1 DA
1
XC
TB2 DB
2
XD
TB3 DG
3
XE
TB4 SLD
CON 4
4
XF
TB5 +24V
1
Y10
TB6
(FG)
2
Y11
TB7 24G
3
Y12
CON 5
4
Y13
ピン番号
Pin
No.
信号名
Signal
name
1
Y14
1 X0
2 Y15
2 X1
3 Y16
3 X2
CON 6
4
Y17
CON1
4 X3
1 Y18
1 X4
2 Y19
2 X5
3 Y1A
3 X6
CON 7
4 Y1B
CON 2
4 X7
1 Y1C
1 X8
2 Y1D
2 X9
3 Y1E
3 XA
CON 8
4 Y1F
1
CON2
CON1
CON3
CON4
CON5
CON6
CON7
CON8
2
3
4
上記はユニット上部
から見た場合
Above indicates a module
view from the top.
CON 3
4 XB
端子番号
Terminal
No.
信号名
Signal
name
TB8 COM+
TB9 COM-
I/O module power supply
Insulation
Constant voltage circuit
External power
supply for output
When external power supply for output
and load power supply are common.
Load power supply
I/Oユニット電源
DA
DB
DG
SLD
+24V
FG
24G
2
3
4
5
6
7
絶縁
DC/DC
1
COM+
8
COM-
9
定電圧回路
負荷電源
出力部
外部供給電源
L
COM+
8
COM-
9
1
2
3
4
CON1 to CON4
L
1
2
3
4
L
CON5 to CON8
出力部外部供給電源・負荷電源共通
とした場合
注
意
● FG端子はシーケンサ専用の第三種接地以上で必ず接地を行ってください。感
電,誤動作の恐れがあります。
● 空き端子ネジは必ず締付けトルク範囲(42~50N・㎝)で締付けてください。
圧着端子と短絡する原因になります。
● 圧着端子は適合圧着端子を使用し,規定のトルクで締付けてください。
先開形圧着端子を使用すると,端子ネジがゆるんだ場合に脱落し,故障の原
因になります。
● ユニットの配線は,製品の定格電圧および端子配列を確認した上で正しく行
ってください。
定格と異なった電源を接続したり,誤配線をすると,火災,故障の原因にな
ります。
● 端子ネジの締付けは,規定トルク範囲内で行ってください。
端子ネジの締付けがゆるいと,火災や誤動作の原因になります。
端子ネジを締め過ぎると,ネジの破損による短絡,誤動作の原因になります。
● ユニット内に,切粉や配線クズなどの異物が入らないように注意してください。
火災,故障,誤動作の原因になります。
● ユニットに接続する電線やケーブルは,必ずダクトに納める,またはクラン
プによる固定処理を行ってください。ケーブルをダクトに納めなかったり,
クランプによる固定処理をしていないと,ケーブルのブラツキや移動,不注
意の引っ張りなどによるユニットやケーブルの破損,ケーブルの接触不良に
よる誤動作の原因となります。
● 制御線と通信ケーブルは束線したり,近接したりしないでください。
ノイズにより,誤動作の原因になります。
● ユニットに接続されたケーブルを取り外すときは,ケーブル部分を手に持っ
て引っ張らないでください。
コネクタ付きのケーブルは,ユニットに接続している部分のコネクタを手で
持って取り外してください。コネクタなしのケーブルは,ユニットに接続し
ている部分のネジを緩めてから取り外してください。
ユニットに接続された状態でケーブルを引っ張ると,ユニットやケーブルの
破損,ケーブルの接続不良による誤動作の原因となります。
【立上げ・保守時の注意事項】
危
険
● 通電中に端子やコネクタに触れないでください。感電の原因になります。
● 清掃,端子ネジ,ユニット取付けネジの増し締めは,必ずシステムで使用して
いる外部供給電源を全相遮断してから行ってください。全相遮断しないと,
ユニットの故障や誤動作の原因になります。
注
意
● ユニットの分解,改造はしないでください。
故障,誤動作,ケガ,火災の原因になります。
● ユニットは落下させたり,強い衝撃を与えないでください。
ユニットの破損の原因になります。
● ユニットの盤への取付け・取外しは必ずシステムで使用している外部供給電
源を全相遮断してから行ってください。全相遮断しないと,ユニットの故障
や誤動作の原因になります。
● 端子台の着脱は,製品ご使用後,50回以内としてください。
(JIS B 3502準拠)
● ユニットに触れる前には,必ず接地された金属などに触れて,人体などに帯
電している静電気を放電してください。
静電気を放電しないと,ユニットの故障や誤動作の原因になります。
【廃棄時の注意事項】
注
意
● 製品を廃棄するときは,産業廃棄物として扱ってください。
1.
仕様
項目
内容
入力点数
16点
絶縁方式
フォトカプラ絶縁
定格入力電圧
DC24V
定格入力電流
約5mA
使用電圧範囲
DC19.2~26.4V(リップル率5%以内)
最大同時入力点数
100%
ON電圧/ON電流
15V以上/3mA以上
OFF電圧/OFF電流
3V以下/0.5mA以下
入力抵抗
約4.7kΩ
OFF→ON
0.2ms以下(DC24V時)
応答時間
ON→OFF
0.2ms以下(DC24V時)
入力
部
入力形式
プラスコモン(シンクタイプ)
出力点数
16点
絶縁方式
フォトカプラ絶縁
定格負荷電圧
DC24V
使用負荷電圧範囲
DC19.2~26.4V(リップル率5%以内)
最大負荷電流
0.1A/1点 1.6A/1コモン
最大突入電流
1.0A 10ms以下
OFF時漏洩電流
0.25mA以下
ON時最大電圧降下
0.3V以下 (TYP.) 0.1A,
0.6V以下 (MAX.) 0.1A
出力形式
シンクタイプ
出力部
保護機能
過負荷保護機能,過電圧保護機能,過熱保護機能
CAUTION
●
Always ground the FG terminal.
There is a risk of electric shock or malfunction.
●
Be sure to tighten any unused terminal screws within a tightening torque
range (42 to 50 N
・
cm).
Failure to do so may cause a short circuit due to contact with a solderless
terminal.
●
Use applicable solderless terminals and tighten them with the specified torque.
If any solderless spade terminal is used, it may be disconnected when the
terminal screw comes loose, resulting in failure.
●
Perform correct wiring for the module according to the product's rated
voltage and terminal arrangement. Connecting to a power supply different
from rating or miss-wiring may cause fire and/or product failure.
●
Fix terminal screws securely within the regulated torque. Loose terminal
screws may cause fire and/or malfunction.
If the terminal screws are too tight, it may cause short circuit or erroneous
operation due to damage of the screws.
●
Make sure foreign objects do not get inside the module, such as dirt and
wire chips. It may cause fire, product failure or malfunction.
●
Be sure to fix the wires or cables by ducts or clamps when connecting them
to the module. Failure to do so may cause damage of the module or the
cables due to accidental pull or unintentional shifting of the cables, or
malfunctions due to poor contact of the cable.
●
Do not install the control lines together with the communication cables, or
bring them close to each other. Failure to do so may cause malfunctions
due to noise.
●
When disconnecting a cable from the module, do not pull on the cable itself.
Disconnect cables fitted with connectors by holding and pulling the cable
connector. Disconnect cables not fitted with a connector by removing the
screws from the part connected to the module.
Pulling on a cable that is connected to the module can cause damage to
the module or cable, or malfunction due to cable connection faults.
【
STARTING AND MAINTENANCE PRECAUTIONS
】
DANGER
●
Do not touch terminals or connectors when the power is on. Doing so could
cause an electric shock.
●
Switch off all phases of the externally supplied power used in the system
when cleaning the module or retightening the terminal or module mounting
screws. Not doing so could result in electric shock.
CAUTION
●
Never try to disassemble or modify module. It may cause product failure,
malfunction, fire or cause injury.
●
Do not drop or apply any strong impact to the module. Doing so may
damage the module.
●
Completely turn off the externally supplied power used in the system before
mounting or removing the module to/from the panel. Not doing so could
result in damage to the product.
●
Mounting/removing the terminal block is limited to 50 times after using a
product. (IEC61131-2-compliant)
●
Always make sure to touch the grounded metal to discharge the electricity
charged in the electricity charged in the body, etc., before touching the module.
Failure to do so may cause a failure or malfunctions of the module.
【
DISPOSAL PRECAUTIONS
】
CAUTION
●
When disposing of this product, treat it as industrial waste.
1. Specification
Item Description
Number of input points
16 points
Isolation method
Photocoupler
Rated input voltage
24 V DC
Rated input current
Approx. 5 mA
Operating voltage range
19.2 to 26.4 V DC (ripple ratio: within 5 %)
Max. simultaneous ON input points 100 %
ON voltage/ON current
15 V or higher/3 mA or higher
OFF voltage/OFF current
3 V or lower/0.5 mA or lower
Input resistance
Approx. 4.7 k
Ω
OFF
→
ON
0.2 ms or lower (when 24 V DC)
Response time
ON
→
OFF
0.2 ms or lower (when 24 V DC)
Input
Input form
Positive common (sink type)
Number of output points
16 points
Isolation method
Photocoupler
Rated load voltage
24 V DC
Operating load voltage range
19.2 to 26.4 V DC (ripple ratio: within 5 %)
Max. load current
0.1 A/point 1.6 A/common
Max. inrush current
1.0 A 10ms or lower
Leakage current at OFF
0.25 mA or lower
MAX. voltage drop at ON
0.3 VDC or lower (TYP.) 0.1 A,
0.6 VDC or lower (MAX.) 0.1 A
Output form
Sink type
Ou
tp
ut
Protection function
Overload protection function, overvoltage protection
function and overheat protection function
項目
内容
OFF→ON
0.5ms以下
応答時間
ON→OFF
1.5ms以下(抵抗負荷)
電圧
DC19.2~26.4V(リップル率5%以内)
出力部
外部供給電源
電流
17mA以下(DC24V,全点ON時)
外部負荷電流は含まず
出
力
部
サージキラー
ツェナーダイオード
コモン方式
32点1コモン
(ワンタッチコネクタ形1線式)
占有局数
1局 32点割付け(32点使用)
電圧
DC20.4~26.4V(リップル率5%以内)
I/Oユニット電源
電波
50mA以下(DC24V,全点ON時)
ノイズ耐量
DCタイプのノイズ電圧500Vp-p,ノイズ幅1µs,
ノイズ周波数25~60Hzのノイズシミュレータによる
耐電圧
DC外部端子一括-アース間AC500V 1分間
絶縁抵抗
DC外部端子一括-アース間DC500V
絶縁抵抗計にて10MΩ以上
保護等級
IP2X
質量
0.16kg
通信部,
I/Oユニット電源部
7点2ピース端子台
[伝送回路,I/Oユニット電
源,FG]
入出力電源部
2点直付け端子台
[入出力部外部供給電源]
M3×5.2 締付けトルク
範囲:59~88N・㎝
適合圧着端子の挿入枚
数は2枚以内
外部
接続
方式
入出力部
専用ワンタッチコネクタ
[I/O信号]
(4ピン・圧接タイプ,コネクタ用プラグは別売)
ユニット取付けネジ
平座金みがき丸付M4ネジ
(締付けトルク範囲:79~108N・cm)
DINレールでの取付け可,6方向取付け可
適用DINレール
TH35-7.5Fe, TH35-7.5Al(JIS C 2812に準拠)
通信部,
I/Oユニット
電源部
入出力
電源部
適合圧着
端子
・RAV1.25-3(JIS C 2805に準拠)
[適合電線サイズ:0.3~1.25mm
2
]
・V2-MS3(日本圧着端子製造(株)),
RAP2-3SL(日本端子(株)),
TGV2-3N((株)ニチフ)
[適合電線サイズ:1.25~2.0mm
2
]
適合
電線
サイズ
入出力部
仕上がり外形:
φ1.0~1.4 (A6CON-P214),
φ1.4~2.0 (A6CON-P220)
[適合電線サイズ:0.14~0.2mm
2
]
仕上がり外形:
φ1.0~1.4 (A6CON-P514),
φ1.4~2.0 (A6CON-P520)
[適合電線サイズ:0.3~0.5mm
2
]
Item Description
OFF
→
ON 0.5 ms or lower
Response time
ON
→
OFF 1.5 ms or lower (resistive load)
Voltage
19.2 to 26.4 V DC (ripple ratio: within 5 %)
External Power
supply for
output part
Current
17 mA or lower (when 24 V DC, all points ON)
Not including external load current
Ou
tp
ut
Surge suppression
Zener diode
Wiring method for common
32 points/common
(one-touch connector plug 1-wire type)
Number of stations occupied
1 station 32 points assignment (use 32 points)
Voltage
20.4 to 26.4 V DC (ripple ratio: within 5 %)
I/O module power
supply
Current
50 mA or lower (when 24 V DC, all points ON)
Noise durability
DC type noise voltage 500 Vp-p, noise width 1 µs,
noise frequency 25 to 60 Hz (noise simulator condition)
Withstand voltage
500 V AC for 1 minute between all DC external
terminals and ground
Insulation resistance
10 M
Ω
or higher, measured with a 500 V DC insulation
resistance tester between all DC external terminals and
ground
Protection of degree
IP2X
Weight 0.16
kg
Communication part, I/O
module power supply part
7-point terminal block (two-piece)
[Transmission circuit, I/O module
power supply, FG]
I/O power supply part
2-point direct-mount terminal
block [External power supply for
I/O]
M3
×
5.2 Tightening
torque range: 59 to
88 N
・
cm
Applicable
solderless terminals:
2 max.
Ext
ern
al
w
iri
ng
syst
em
I/O part
Dedicated one-touch connector [I/O signal] (4-pin
pressure-displacement type, connector plug sold
separately.)
Module installation screw
M4 screw with plain washer finished round (tightening
torque range: 79 to 108 N
・
cm) Module can be mounted
using DIN rail and can be mounted in 6 directions
Applicable DIN rail
TH35-7.5Fe, TH35-7.5Al (conforming to IEC 60715)
Communication
part, I/O module
power supply part
I/O power supply
part
Appli-
cable
solder-
less
terminal
・
RAV1.25-3 (conforming to JIS C 2805)
[Applicable wire size: 0.3 to 1.25 mm
2
]
・
V2-MS3, RAP2-3SL, TGV2-3N
[Applicable wire size: 1.25 to 2.0 mm
2
]
A
pplic
able wir
e s
iz
e
I/O part
Finished dimensions:
φ
1.0 to 1.4 (A6CON-P214),
φ
1.4 to 2.0 (A6CON-P220)
[Applicable wire size: 0.14 to 0.2 mm
2
]
Finished dimensions:
φ
1.0 to 1.4 (A6CON-P514),
φ
1.4 to2.0 (A6CON-P520)
[Applicable wire size: 0.3 to 0.5 mm
2
]