M800/M80/E80/C80 Series Alarm/Parameter Manual
10 User PLC Alarms (U)
116
IB-1501279-H
Details
Caution; Ladder program writing during RUN is disabled (common pointer is used in high-speed processing)
With RUN write is ON, high-speed program with common pointer is running. RUN write is not available with this
condition.
Remedy
RUN write is not available when high-speed processing with common pointer is running. Change the high-
speed processing program to the one without common pointer.
Details
Caution; Ladder program writing during RUN is disabled (high-speed processing size is exceeding)
With RUN write ON, the execution size of high-speed processing program has exceeded 4000 steps. RUN
write is not available with this condition.
Remedy
RUN write is not available when execution size of high-speed processing program exceeds 4000 steps. Edit
the high-speed processing program to reduce the execution size to 4000 steps or less.
(When multi-project is valid, edit the program to reduce the execution size to 4000 steps or less in total of all
the project.)
Details
Caution; Ladder program writing during RUN is disabled (number of labels in high-speed processing is beyond
the capacity)
With RUN write ON, the number of local labels in high-speed processing program has exceeded 256. RUN
write is not available with this condition.
Remedy
RUN write is not available when the number of local labels in high-speed processing program exceeds 256.
Edit the high-speed program to reduce the number of local labels to less than 256.
(When multi-project is valid, edit the program to reduce the number of local labels to less than 256 per project.)
Details
Software exceptional interruption (BCD instruction error) has occurred.
With BCD and DBCD instructions, BIN value outside its input range was attempted to be converted into BCD.
Remedy
Check the usage of BCD, DBCD instructions existing in the steps occurred.
Details
Software exceptional interruption (BIN instruction error) has occurred.
With BIN and DBIN instructions, BCD value outside its input range was attempted to be converted into BIN.
Remedy
Check the usage of BIN, DBIN instructions existing in the steps occurred.
Details
Software exceptional interruption (Bus error) has occurred.
Remedy
Contact Mitsubishi.
U10
Illegal PLC
0x71xx.yy
Number of steps
U10
Illegal PLC
0x720*
-
U10
Illegal PLC
0x730*.yy
-
U10
Illegal PLC
0x80xx.yy
Number of steps
U10
Illegal PLC
0x81xx.yy
Number of steps
U10
Illegal PLC
0x82xx.yy
Number of steps
Summary of Contents for C80 Series
Page 1: ......
Page 7: ......
Page 11: ......
Page 13: ......
Page 15: ......
Page 18: ...1 IB 1501279 H Alarm ...
Page 19: ...M800 M80 E80 C80 Series Alarm Parameter Manual 2 IB 1501279 H ...
Page 20: ...1 3 IB 1501279 H Operation Errors M ...
Page 54: ...2 37 IB 1501279 H Stop Codes T ...
Page 62: ...3 45 IB 1501279 H Servo Spindle Alarms S ...
Page 81: ...M800 M80 E80 C80 Series Alarm Parameter Manual 3 Servo Spindle Alarms S 64 IB 1501279 H ...
Page 82: ...4 65 IB 1501279 H MCP Alarms Y ...
Page 98: ...5 81 IB 1501279 H System Alarms Z ...
Page 111: ...M800 M80 E80 C80 Series Alarm Parameter Manual 5 System Alarms Z 94 IB 1501279 H ...
Page 112: ...6 95 IB 1501279 H Absolute Position Detection System Alarms Z7 ...
Page 118: ...7 101 IB 1501279 H Distance coded Reference Scale Errors Z8 ...
Page 120: ...8 103 IB 1501279 H Emergency Stop Alarms EMG ...
Page 124: ...9 107 IB 1501279 H Computer Link Errors L ...
Page 126: ...10 109 IB 1501279 H User PLC Alarms U ...
Page 136: ...11 119 IB 1501279 H Network Service Errors N ...
Page 139: ...M800 M80 E80 C80 Series Alarm Parameter Manual 11 Network Service Errors N 122 IB 1501279 H ...
Page 140: ...12 123 IB 1501279 H Program Errors P ...
Page 178: ...13 161 IB 1501279 H Smart Safety Observation Alarm V ...
Page 192: ...14 175 IB 1501279 H Multi CPU Errors A C80 ...
Page 215: ...M800 M80 E80 C80 Series Alarm Parameter Manual 14 Multi CPU Errors A C80 198 IB 1501279 H ...
Page 216: ...199 IB 1501279 H Parameter ...
Page 217: ...M800 M80 E80 C80 Series Alarm Parameter Manual 200 IB 1501279 H ...
Page 218: ...15 201 IB 1501279 H User Parameters ...
Page 359: ...M800 M80 E80 C80 Series Alarm Parameter Manual 15 User Parameters 342 IB 1501279 H ...
Page 360: ...16 343 IB 1501279 H Machine Parameters ...
Page 748: ......