M800/M80/E80/C80 Series Alarm/Parameter Manual
13 Smart Safety Observation Alarm (V)
174
IB-1501279-H
Details
Output signal of the safety I/O unit has been kept ON for 24 hours or longer.
The screen displays the unit No., RIO system and signal BIT that are subject to the warning.
[M8]
bit28-31: None
bit24-27: Unit No.
bit18-23: None
bit16-17: Detected system
bit0-15: Signal BIT
[C80]
bit0-31: Signal BIT
Remedy
Turn OFF the output signal concerned through the user safety sequence, or use the output OFF check
function to make sure that the output signal turns OFF.
Details
Smart safety observation target axis (the parameters "#51101 SF_Disable" = 0 / "#51301 SF_SDisable" =
0) is defined as a hypothetical axis (the parameter "#51015 safe_drv_test" = 1). In this case some alarms
fail to occur, thus avoid this setting while a drive unit is being connected.
NC system is set to a simulation mode (the parameter "#1168 test" = 1 ). During this mode some alarms
fail to occur, thus do not use this mode while a safety I/O unit is connected.
Remedy
Connect MDS-E Series drive to all the axes subject to safety observation, set the parameter ("#51015
safe_drv_test" = 0) and then turn OFF and ON the power.
Connect a safety I/O unit, set the parameter ("#1168 test" = 0) and then turn OFF and ON the power.
V53
Warning on 24Hr continuous ON
0001
Unit info
V54
Simple test mode is active
0001
Summary of Contents for C80 Series
Page 1: ......
Page 7: ......
Page 11: ......
Page 13: ......
Page 15: ......
Page 18: ...1 IB 1501279 H Alarm ...
Page 19: ...M800 M80 E80 C80 Series Alarm Parameter Manual 2 IB 1501279 H ...
Page 20: ...1 3 IB 1501279 H Operation Errors M ...
Page 54: ...2 37 IB 1501279 H Stop Codes T ...
Page 62: ...3 45 IB 1501279 H Servo Spindle Alarms S ...
Page 81: ...M800 M80 E80 C80 Series Alarm Parameter Manual 3 Servo Spindle Alarms S 64 IB 1501279 H ...
Page 82: ...4 65 IB 1501279 H MCP Alarms Y ...
Page 98: ...5 81 IB 1501279 H System Alarms Z ...
Page 111: ...M800 M80 E80 C80 Series Alarm Parameter Manual 5 System Alarms Z 94 IB 1501279 H ...
Page 112: ...6 95 IB 1501279 H Absolute Position Detection System Alarms Z7 ...
Page 118: ...7 101 IB 1501279 H Distance coded Reference Scale Errors Z8 ...
Page 120: ...8 103 IB 1501279 H Emergency Stop Alarms EMG ...
Page 124: ...9 107 IB 1501279 H Computer Link Errors L ...
Page 126: ...10 109 IB 1501279 H User PLC Alarms U ...
Page 136: ...11 119 IB 1501279 H Network Service Errors N ...
Page 139: ...M800 M80 E80 C80 Series Alarm Parameter Manual 11 Network Service Errors N 122 IB 1501279 H ...
Page 140: ...12 123 IB 1501279 H Program Errors P ...
Page 178: ...13 161 IB 1501279 H Smart Safety Observation Alarm V ...
Page 192: ...14 175 IB 1501279 H Multi CPU Errors A C80 ...
Page 215: ...M800 M80 E80 C80 Series Alarm Parameter Manual 14 Multi CPU Errors A C80 198 IB 1501279 H ...
Page 216: ...199 IB 1501279 H Parameter ...
Page 217: ...M800 M80 E80 C80 Series Alarm Parameter Manual 200 IB 1501279 H ...
Page 218: ...15 201 IB 1501279 H User Parameters ...
Page 359: ...M800 M80 E80 C80 Series Alarm Parameter Manual 15 User Parameters 342 IB 1501279 H ...
Page 360: ...16 343 IB 1501279 H Machine Parameters ...
Page 748: ......