7.2.4
DC
C
ONNECTIONS
1.
Open the front door on the cabinet and check for any noticeable problems or damage that
may have occurred during shipment.
2.
Review the attached installation drawing and schematic. Note that a cable has been left off
in the middle of the battery string for safety purposes and will be installed later.
3.
Check and re-torque internal battery connections, as shipping may have caused these
connections to come loose. Proper torque values are noted on the drawing and also on the
battery case.
4.
Connect main cables from the UPS or charger source to the battery cabinet output. The
battery cabinet output connection point will vary depending on the cabinet configuration.
The main output connection point may be directly to the circuit breaker, to the fuse block,
or to a terminal block or bus bars. Review the supplied cabinet drawing for information on
the battery cabinet output. All cables should be sized per NEC and any other local codes
pertaining to this equipment. Refer to the UPS or charger manual for wiring external
batteries. Note! Make sure any charging source is disconnected before making these
connections.
5.
Connect the cable that was left off during shipment and install as shown on the wiring
drawing. Torque connections properly.
7.2.5
S
YSTEM
O
PERATION
Please refer to the UPS system manual for system start up and operation information.
Review the attached system drawings and schematics for model specific
information on DC output connections.
Wire should be sized for a maximum voltage drop of 0.5 volt.
Battery cabinets that are not supplied with an incorporated DC output disconnect
device must have an appropriate disconnect device provided external to the cabinet.
Verify that the output breaker is in the off/open position before making any DC
connections to additional cabinets or to the UPS. Also verify that the UPS charger
is not running.
Summary of Contents for C&C Power BC29
Page 2: ...4 16 2014 2 755 00087 R03 ...
Page 4: ...4 16 2014 4 755 00087 R03 ...
Page 19: ...BC29 BATTERY CABINET 4 16 2014 19 755 00087 R03 9 REFERENCE MATERIALS ...
Page 20: ...BC29 BATTERY CABINET 4 16 2014 20 755 00087 R03 ...
Page 21: ...BC29 BATTERY CABINET 4 16 2014 21 755 00087 R03 ...
Page 23: ...C C Power Inc 395 Mission Street Carol Stream IL 60188 Phone 630 617 9022 www ccpower com ...