- 7 -
[
IV
Outlines and Dimensions ]
GB
HWE1209A
Unit : mm
Min.300mm
Access door 1
(450×450)
Access door 3
Electric box
Intake air
Access door 1
(450×450)
Ceiling beam
Access door 2 (450×450)
Electric box
Supply air
Supply air
Intake air
Maintenance access space
Maintenance access space
Maintenance access space
Electric box
Access door 4
(V
iewed from the direction
of the arrow B)
Access door 3
Electric box
Bottom of
indoor unit
(V
iewed from the direction of the arrow B)
B
Ceiling beam
Ceiling
(V
iewed from the direction of the arrow
A)
Access door 2
(450×450)
Ceiling
A
Bottom of indoor unit
100~200
100~200
Electric box
Min.10mm
450
450
450
50~150
P
700
700
Min.300mm
N
50
50
R
777
777
50
Q
50
475
N
450
Min.20mm
Min.300mm
N
450
475
700
450
Min.300mm
Min.10mm
Fig.3
Fig.4
Fig.5
Fig.2
Fig.1
Bottom of
indoor unit
[Maintenance access space]
Secure enough access space to allow for the maintenance, inspection, and replacement of the motor, fan, drain pump, heat exchan
ger,
and electric box in one of the following ways.
Select an installation site for the indoor unit so that its maintenance access space will not be obstructed by beams or other o
bjects.
(1) When a space of 300mm or more is available below the unit between the unit and the ceiling. (Fig.1)
·Create access door 1 and 2 (450x450mm each) as shown in Fig.2.
(Access door 2 is not required if enough space is available below the unit for a maintenance worker to work in.)
(2) When a space of less than 300mm is available below the unit between the unit and the ceiling.
(At least 20mm of space should be left below the unit as shown in Fig.3.)
·Create access door 1 diagonally below the electric box and access door 3 below the unit as shown in Fig.4.
or
PEFY
-WP15VMS1-E
PEFY
-WP10VMS1-E
PEFY
-WP20VMS1-E
PEFY
-WP25VMS1-E
PEFY
-WP32VMS1-E
PEFY
-WP40VMS1-E
PEFY
-WP50VMS1-E
700
N
Model
1100
900
150~250
250~350
P
50~150
800
Q
1200
1000
R
1700
1500
1300
·Create access door 4 below the electric box and the unit as shown in Fig.5.
HWE1209A.book 7 ページ 2017年3月9日 木曜日 午後5時37分