background image

11

GB

 Caution:

Cut the tip of the indoor unit piping, remove the gas, and then remove the 
brazed cap.

[Fig. 5.3.1]

B

A

A

 Cut 

here 

B

  Remove brazed cap

5.4.  Insulating refrigerant pipes

Be sure to wind heat-resisting polyethylene form of more than 20 mm [13/16 
in] in thickness onto both liquid and gas pipes and also put it onto the joints 
between indoor unit and insulating material so that there will be no gaps. Incom-
plete insulation may cause excess condensation or heat losses. Pay careful at-
tention, particularly when insulating above the ceiling.

[Fig. 5.4.1] 

F

E

C

B

A

D

A

  Locally procured insulating material for pipes

B

  Bind here using band or tape. 

C

  Do not leave any opening.

D

  Lap margin: more than 40 mm [1-19/32 in] 

E

 ,QVXODWLQJPDWHULDO¿HOGVXSSOLHG

F

  Unit side insulating material

5.5.  Drain piping work

1.  Drain piping work

‡ (QVXUH WKDW WKH GUDLQ SLSLQJ LV GRZQZDUG SLWFK RI PRUH WKDQ  WR WKH

outdoor (discharge) side. If it is impossible to take any downward pitch, use 
an optionally available drain-up mechanism to obtain a downward pitch of 
more than 1/100. 

‡ (QVXUHWKDWDQ\FURVVZLVHGUDLQSLSLQJLVOHVVWKDQP>IW@,IWKHGUDLQ

piping is long, support it with metal brackets to prevent it from bending, warp-
ing, or vibrating.

‡ &RQQHFWWKHVXSSOLHGGUDLQKRVHWRWKHGLVFKDUJHSRUWRQWKHXQLWERG\8VH

hard vinyl chloride pipes VP-25 (ø32 mm [1-1/4 in]) for drain piping (

2

). 

Tighten the supplied drain hose onto the discharge port using the supplied 
hose band. (For this, do not use any adhesive because the drain hose will 
need to be removed for servicing at a later date.)

‡ 'RQRWXVHDQ\RGRUWUDSDURXQGWKHGLVFKDUJHSRUW
‡ 0DNHVXUHWRXVHWKHVXSSOLHGKRVHEDQG

G

WR¿[WKHGUDLQKRVHLQSODFH

Using a commercially available hose band may cause damage to the natural 
drain discharge port when tightend too much, resulting in water leakage.

[Fig. 5.5.1] 

(Unit: mm [in])

A

1

A

B

C

B

 

VP-25

D

E

G

F

2

A:   250  [9-27/32]

B:   1500-2000  [59-1/16-78-3/4]

A

  Downward pitch of more than 1/100  

B

 Insulating 

material

C

 Supporting 

bracket 

D

  Drain discharge port

E

  Drain hose (200 [7-7/8] long, accessory) 

F

  Tie band (accessory)

G

  Hose band (accessory)

‡ $VVKRZQLQ

3

, install a collecting pipe about 100 mm [3-15/16 in] below the 

drain ports and give it a downward pitch of more than 1/100. This collecting 
pipe should be of VP-30. 

‡ 6HWWKHHQGRIGUDLQSLSLQJLQDSODFHZLWKRXWDQ\ULVNRIRGRUJHQHUDWLRQ
‡ 'RQRWSXWWKHHQGRIGUDLQSLSLQJLQWRDQ\GUDLQZKHUHLRQLFJDVHVDUHJHQ

-

erated.

‡ 'UDLQ SLSLQJ PD\ EH LQVWDOOHG LQ DQ\ GLURZHYHU SOHDVH EH VXUH WR

observe the above instructions.

‡ :KHQXVLQJDQRSWLRQDOO\DYDLODEOHGUDLQXSPHFKDQLVPIROORZLWVLQVWUXFWLRQ

manual regarding its installation and use.

[Fig. 5.5.2]

B

B

A

D

C

VP-30

3

A

 BC 

controller 

B

 Indoor 

unit

C

 Collecting 

pipe 

D

  Please ensure this length is at least 100 mm [3-15/16 in].

2. Discharge 

test

After completing drain piping work, open the BC controller panel, and test drain 
discharge using a small amount of water. Also, check to see that there is no wa-
ter leakage from the connections.

3.  Insulating drain pipes

3URYLGHVXI¿FLHQWLQVXODWLRQWRWKHGUDLQSLSHVMXVWDVIRUUHIULJHUDQWSLSHV

 Caution:

Be sure to provide drain piping with heat inslation in order to prevent 
excess condensation. Without drain piping, water may leak from the unit 
causing damage to your property.

X

 

Consult all related regulations and power companies beforehand.

 Warning:

(OHFWULFDO ZRUN VKRXOG EH KDQGOHG E\ TXDOL¿HG HOHFWULFDO HQJLQHHUV LQ DF

-

cordance with all related regulations and attached instruction manuals. 
Special circuits should also be used. If there is a lack of power capacity or 

DGH¿FLHQF\LQHOHFWULFDOZRUNLWPD\FDXVHDULVNRIHOHFWULFVKRFNRU¿UH

X

 

Connect all wires securely.

‡ )L[ SRZHU VRXUFH ZLULQJ WR FRQWURO ER[ E\ XVLQJ EXIIHU EXVKLQJ IRU WHQVLOH

force (PG connection or the like).

[Fig. 6.0.1] 

B

A

C

D

A

 Control 

box 

B

  Power source wiring

C

  ø21 mm [27/32 in] hole (closed rubber bushing)

D

 Transmission 

wiring

X

  Never connect the power cable to the terminal board for control cables. 

(Otherwise it may be broken.)

X

  Be sure to wire between the control wire terminal boards for indoor 

unit, outdoor unit and BC controller.

Use non-polarized 2-wire as transmission cables.
Use 2-core shielding cables (CVVS, CPEVS) of more than 1.25 mm

2

 [AWG16] in 

diameter as transmission cables.
The switch capacity of the main power to BC controllers and the wire size are as 
follows:

Switch (A)

Molded case 

circuit breaker

Earth leakage 

breaker

Wire size

Capacity

Fuse

15

15

20 A

20 A 30 mA  

0.1 s or less

1.5 mm

[AWG15] 

‡ )RURWKHUGHWDLOHGLQIRUPDWLRQUHIHUWRWKHRXWGRRUXQLWLQVWDOODWLRQPDQXDO
‡ 3RZHUVXSSO\FRUGVRIDSSOLDQFHVVKDOOQRWEHOLJKWHUWKDQGHVLJQ,(&

or 227 IEC 53.

‡ $VZLWFKZLWKDWOHDVWPP>LQ@FRQWDFWVHSDUDWLRQLQHDFKSROHVKDOOEH

provided by the Air conditioner installation.

 Caution:

Do not use anything other than the correct capacity fuse and breaker. Us-
ing fuse, conductor or copper wire with too large capacity may cause a 

ULVNRIPDOIXQFWLRQRU¿UH

Ensure that the outdoor units are put to the ground. Do not connect the 
earth cable to any gas pipe, water pipe, lightening rod or telephone earth 
cable. Incomplete grounding may cause a risk of electric shock.

6. Electrical work

Summary of Contents for CITY MULTI CMB-P-NU-G1

Page 1: ...STALLATION Veuillez lire le manuel d installation en entier avant d installer ce climatiseur pour éviter tout accident et vous assurer d une utilisation correcte Air Conditioners For Building Application INDOOR UNIT CMB P NU G1 CMB P NU GA1 MAIN BC CONTROLLER CMB P NU GB1 SUB BC CONTROLLER CMB P NU HA1 MAIN BC CONTROLLER CMB P NU HB1 SUB BC CONTROLLER ...

Page 2: ...he unit If a different refrigerant or air is mixed with the original refrigerant the re frigerant cycle may malfunction and the unit may be damaged If the air conditioner is installed in a small room measures must be tak en to prevent the refrigerant concentration from exceeding the safety limit if the refrigerant should leak Consult the dealer regarding the appropriate measures to prevent the saf...

Page 3: ...pplied to the cable 7HQVLRQ PD FDXVH WKH FDEOH WR EUHDN DQG JHQHUDWH KHDW DQG FDXVH D UH Install a leak circuit breaker as required If a leak circuit breaker is not installed electric shock may result 8VH SRZHU OLQH FDEOHV RI VXI FLHQW FXUUHQW FDUU LQJ FDSDFLW DQG UDWLQJ DEOHV WKDW DUH WRR VPDOO PD OHDN JHQHUDWH KHDW DQG FDXVH D UH 8VH RQO D FLUFXLW EUHDNHU DQG IXVH RI WKH VSHFL HG FDSDFLW A fuse ...

Page 4: ...HG WR WKH JHQHUDWLRQ LQÀRZ DFFXPXODWLRQ RU OHDNDJH RI ÀDPPDEOH DQG VXOIXULF JDVHV QVXUH D GRZQZDUG JUDGLHQW RI DW OHDVW IRU GUDLQ SLSLQJ 3URSHUO LQVWDOO WKH XQLW RQ D VWDEOH ORDG EHDULQJ VXUIDFH 6RPH FRPELQDWLRQ RI FRQWUROOHU DQG RXWGRRU XQLW FDQQRW EH XVHG Refer to the table below for details Combination of BC controller and outdoor unit Outdoor unit BC controller G type GA type GB type HA type H...

Page 5: ...t 6 Indoor units that are connected to the same branch joint cannot be si multaneously operated in different operation modes 7 When connecting multiple indoor units to one branch port those in door units must be installed in the same room Distance between BC controller and farthest indoor unit Height difference between BC controller and farthest indoor unit m ft 15 49 10 32 5 16 20 65 10 32 0 0 Di...

Page 6: ... model and 30 hp P288 model The G type BC controller cannot be connected to the models between 15 hp P144 model and 30 hp P288 model 8 For Sub BC controller GB type the connectable indoor unit capaci ties may sum to equal that of a P120 unit or less However if two sub controllers are used the TOTAL sum of connectable units connected to BOTH sub controllers must also not exceed that of a P120 unit ...

Page 7: ...196 70 229 80 262 90 295 100 328 110 360 B 300 984 200 656 400 1312 500 1640 600 1968 700 2296 800 2624 900 2952 1000 3280 10 32 20 65 30 98 40 131 50 164 60 196 70 229 80 262 90 295 100 328 110 360 B 300 984 200 656 400 1312 500 1640 600 1968 700 2296 800 2624 900 2952 1000 3280 10 32 20 65 30 98 40 131 50 164 60 196 70 229 80 262 90 295 100 328 110 360 B 300 984 200 656 A 400 1312 500 1640 600 1...

Page 8: ...K KHQ UH EUD LQJ WKH FRQQHFWLRQV XVH WKH VDPH EUD LQJ PDWHULDO 3DLQW WKH EUD HG VHFWLRQV DIWHU EUD LQJ 8VH WKH SURSHU ÀX EDVHG RQ WKH EDVH PDWHULDO W SH VKDSH EUD LQJ W SH DQG EUD LQJ PHWKRG Procedures 1 UD H WKH SLSHV DV VKRZQ LQ WKH JXUH EHORZ DW WKH WHPSHUDWXUH DSSURSULDWH IRU WKH EUD LQJ PDWHULDO IWHU EUD LQJ NHHS VXSSO LQJ D ÀRZ RI QLWURJHQ JDV XQWLO WKH SLSHV EHFRPH FRRO HQRXJK WR EH WRXFKHG...

Page 9: ...ing the piping Check that there is no crack at the pipe expansion part Fig 5 2 1 B C D E F A A F A A Indoor unit connecting port B Cutting point ø9 52 Liquid side or ø15 88 Gas side Indoor unit model bigger than P18 C Cutting point ø6 35 Liquid side or ø12 7 Gas side Indoor unit model P18 or smaller D Cut the piping at the cutting point E Have pipe expansion of indoor unit connecting port F Field ...

Page 10: ...To connect a unit with a capacity of higher than 31 After combining two branches using an optionally available piping kit CMY R160 J1 connect indoor units 3 Connection of plural indoor units with one connection or joint pipe 7RWDO FDSDFLW RI FRQQHFWDEOH LQGRRU XQLWV HVV WKDQ HVV WKDQ ZLWK joint pipe 1XPEHU RI FRQQHFWDEOH LQGRRU XQLWV 0D LPXP 6HWV 7ZLQQLQJ SLSH 8VH WKH WZLQQLQJ SLSH IRU 7 08 7 6HUL...

Page 11: ...HU SOHDVH EH VXUH WR observe the above instructions KHQ XVLQJ DQ RSWLRQDOO DYDLODEOH GUDLQ XS PHFKDQLVP IROORZ LWV LQVWUXFWLRQ manual regarding its installation and use Fig 5 5 2 B B A D C VP 30 3 A BC controller B Indoor unit C Collecting pipe D Please ensure this length is at least 100 mm 3 15 16 in 2 Discharge test After completing drain piping work open the BC controller panel and test drain d...

Page 12: ...erated After completion of installation work check the item shown in the table below If any abnormality is noticed identify the problem and correct it Leaving the problem unattended may cause mechanical failure or malfunctions and raise safety risks No Item to be checked 1 Check for refrigerant gas leakage Before commencing a test run please check the following X After installing piping and wiring...

Page 13: ...D SRXVVLqUH RX GH O HDX risque de pénétrer dans l appareil extérieur et de provoquer un incendie ou une électrocution En installant et en déplaçant le climatiseur vers un autre site ne le FKDUJH SDV DYHF XQ IULJRULJqQH GLIIpUHQW GH FHOXL TXL HVW VSpFL p VXU l unité Si un autre frigorigène ou de l air est mélangé au frigorigène original le F FOH IULJRUL TXH SHXW PDO IRQFWLRQQHU HW O XQLWp SHXW rWUH...

Page 14: ...structure qui peut provoquer une fuite Lorsque l humidité de la pièce dépasse 80 ou que le tuyau d écoulement est bouché il se peut que des gouttes d eau tombent de l appareil intérieur ou du contrôleur BC Exécutez un travail de drainage collectif avec l unité extérieure selon besoins 1 4 Avant l installation déménagement travaux électriques Attention Mettez l unité à la terre 1H FRQQHFWH SDV OH O...

Page 15: ...p rieurs n est pas possible Reportez vous au tableau suivant pour le détail Combinaison d un contrôleur BC et d un appareil extérieur L appareil extérieur Le contrôleur BC type G type GA type GB type HA type HB P72 à P126 A A A A A P127 à P240 N A A A A A P241 à P288 N A N A A A A A disponible N A Non disponible 1 Pour la suspension au plafond Fig 3 2 1 IIHFWXH XQ WURX G LQVSHFWLRQ GH PP LQ FDUUp ...

Page 16: ...ur le plus éloigné dépasse 40 m 131 ft appareil inté rieur du modèle P96 non concerné 3 Les valeurs entre parenthèses indiquent la longueur de tuyauterie maximum à respecter lorsque la capacité de connexion de l appareil intérieur est d au moins 72 4 Dans le système auquel les appareils intérieurs du modèle P72 ou su périeur sont branchés vous ne pouvez pas utiliser de joint ni de tête de dérivati...

Page 17: ... utiliser de joint ni de tête de dérivation 5 Lors du branchement de deux contrôleurs BC secondaires la longueur de tuyauterie totale doit être égale ou inférieure à longueur maximum comme indiqué sur le dessus 6 Lors du branchement de deux contrôleurs BC secondaires installez les en parallèle 7 Lorsque l appareil extérieur est de 15 hp modèle P264 ou plus utilisez le contrôleur BC principal de ty...

Page 18: ...29 80 262 90 295 100 328 110 360 B 300 984 200 656 400 1312 500 1640 600 1968 700 2296 800 2624 900 2952 1000 3280 10 32 20 65 30 98 40 131 50 164 60 196 70 229 80 262 90 295 100 328 110 360 B 300 984 200 656 400 1312 500 1640 600 1968 700 2296 800 2624 900 2952 1000 3280 10 32 20 65 30 98 40 131 50 164 60 196 70 229 80 262 90 295 100 328 110 360 B 300 984 200 656 A 400 1312 500 1640 600 1968 700 ...

Page 19: ... SDV DVVH SXLVVDQW Q FDV GH UH EUDVDJH GHV UDFFRUGHPHQWV XWLOLVH OH PrPH PDWpULHO GH EUDVDJH 3HLJQH OHV VHFWLRQV EUDVpHV DSUqV OH EUDVDJH 8WLOLVH XQ ÀX DSSURSULp VHORQ OH W SH GH PDWpULDX GH OD EDVH OD IRUPH OH W SH GH EUDVDJH HW OD PpWKRGH GH EUDVDJH Procédures 1 UDVH OHV WX DX HQ VXLYDQW OHV LQGLFDWLRQV GH OD JXUH FL GHVVRXV j OD ERQQH WHPSpUDWXUH SRXU OH PDWpULHO GH EUDVDJH SUqV OH EUDVDJH FRQW...

Page 20: ...VHPHQW GX WX DX QH SUpVHQWH SDV GH VVXUHV Fig 5 2 1 B C D E F A A F A A Port de connexion de l appareil intérieur B Point de découpe ø9 52 côté liquide ou ø15 88 côté gaz Modèle d appareil intérieur plus grand que le P18 C Point de découpe ø6 35 côté liquide ou ø12 7 côté gaz Modèle d appareil intérieur P18 ou plus petit D Découper le tuyau au niveau du point de découpe E Effectuez l élargissement...

Page 21: ...avec le contrôleur BC 2 Pour raccorder un appareil avec une capacité est supérieure à 31 Raccorder les appareils intérieurs après avoir réuni deux branchements à l aide du kit de tuyautage disponible en option CMY R160 J1 3 Connexion d appareils intérieurs multiples avec une connexion ou manchon d assemblage DSDFLWp WRWDOH GHV DSSDUHLOV LQWpUHXUV SRXYDQW rWUH FRQQHFWpV PRLQV GH moins de 96 avec un...

Page 22: ...RXOHPHQW SHXW rWUH RULHQWp GDQV Q LPSRUWH TXHOOH GLUHFWLRQ 9HLO lez cependant à respecter les instructions ci dessus RUVTXH YRXV XWLOLVH XQ PpFDQLVPH G pFRXOHPHQW HQ RSWLRQ VXLYH VRQ PD nuel d instructions pour l installation et l utilisation Fig 5 5 2 B B A D C VP 30 3 A Contrôleur BC B Appareil intérieur C Tuyau de récupération D 9pUL H TXH FHWWH ORQJXHXU HVW G DX PRLQV PP LQ 2 Test d évacuation...

Page 23: ...ur 8QH IRLV O LQVWDOODWLRQ WHUPLQpH YpUL H OHV pOpPHQWV LQGLTXpV GDQV OH WDEOHDX FL GHVVRXV 6L YRXV GpWHFWH XQH DQRPDOLH LGHQWL H OH SUREOqPH HW FRUULJH OH 1H SDV corriger le problème immédiatement risque d entrainer une panne mécanique et des risques pour la sécurité N eOpPHQWV j YpUL HU 1 9pUL H O DEVHQFH GH IXLWH GH JD UpIULJpUDQW YDQW O HVVDL GH IRQFWLRQQHPHQW YpUL H OHV pOpPHQWV VXLYDQWV X RU...

Page 24: ...ne number on this manual before handing it to the customer HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN WT07612X01 This product is designed and intended for use in the residential commercial and light industrial environment ...

Reviews: