VII
Troubleshooting ]
- 29 -
HWE19070
GB
4. Voltage test points on the control board
1. PEFY-M20, 25, 32, 40, 50, 63, 71, 80, 100, 125, 140VMA(L)-A, PEFY-M20, 25, 32, 40, 50, 63, 71, 80, 100, 125VMA2-A
F01
Fuse (AC 250V 6.3A)
CND
Power supply voltage (220 -
240VAC)
CN2M For M-NET transmission cable
connection (24 - 30VDC)
SWE
Emergency operation
SW2
Capacity setting
SW4
Function setting
SW3
Function setting
CN32
Remote start/stop adapter
CN3A
For MA remote controller cable
connection
(10 - 13 VDC (Between 1 and 3.))
CN52
Remote display
CN51
Centralized control
CN41
JAMA standard HA terminal A
CN44
Thermistor
(liquid/gas temperature)
CN4F
Float switch
CN20
Thermistor (Inlet temperature)
CNMF Fan motor output
1 - 4: 310 - 340 VDC
5 - 4: 15 VDC
6 - 4: 0 - 6.5 VDC
7 - 4: Stop 0 or 15 VDC
Run 7.5 VDC
(0 - 15 pulse)
(*1)
V
FG
Voltage on the (-) side of PC352
and C084
(Same with the voltage between 7
(+) and 4 (-) of CNMF)
V
CC
Voltage between the C084 pins
15 VDC
(Same with the voltage between 5
(+) and 4 (-) of CNMF)
Vsp Voltage between the C351 pins
0VDC (with the fan stopped)
1 - 6.5VDC (with the fan in opera-
tion)
(Same with the voltage between 6
(+) and 4 (-) of CNMF)
CN2M
CND
F01
CN3A
CN41
CN51
CN52
CN20
C084
(-) side
PC352
(-) side
C351
CN4F
CN44
CNMF
SWE
CNP
HWE19070.book Page 29 Thursday, September 12, 2019 3:46 PM