6. Troubleshooting

Before you ask for repair service, check the following points:

State of Machine

Remote Controller

Cause

Troubleshooting

It does not run.

“ ” display is not lit up.

No display appears 

even when the [ON/

O F F ]   b u t t o n   i s 

pressed.

Power failure

Press the [ON/OFF] button after power restoration.

The power supply is turned OFF.

Turn the power supply ON.

The fuse in the power supply is gone.

Replace fuse.

The earth leakage breaker is gone.

Put in the earth leakage breaker.

Air flows out but it 

does not cool enough 

or heat enough.

The liquid crystal dis-

play shows that it is in 

the state of operation.

Improper temperature adjustment

After checking the set temperature and inlet temperature 

on the liquid crystal display, refer to [Room temperature 

adjustment], and operate the adjustment button.

The filter is filled with dust and dirt.

Clean up the filter.

(Refer to [Caring for the machine].)

There are som obstacles at the air inlet and outlet of 

the indoor and outdoor units.

Remove.

Windows and doors are open.

Close

Cool air or warm air 

does not come out.

The liquid crystal dis-

play shows that it is in 

operation.

The restart-preventing circuit is in operation for 3 

minutes.

Wait for a while.

(To protect the compressor, a 3-minute restart-preventing 

circuit is built into the indoor unit. Therefore, there are oc-

casions sometimes when the compressor does not start 

running immediately. There are cases when it does not run 

for as long as 3 minutes.)

Indoor unit operation was restarted during the heat-

ing and defrosting operation.

Wait for a while.

(Heating operation starts after ending defrosting opera-

tion.)

It runs briefly, but soon 

stops.

T h e  “ C H E C K ”  a n d 

check code flashes on 

the liquid crystal dis-

play.

There are some obstacles at the air inlet and outlet 

of the indoor and outdoor units.

Rerun after removal

The filter is filled with dust and dirt.

Rerun after cleaning the filter. (Refer to [Caring for the ma

-

chine].)

The sound of the ex-

haust and rotation of 

the motor can still be 

heard after stop of run-

ning.

All lights are out ex-

cept the powered dis-

play of “ ”.

When other indoor units are engaged in cooling op-

eration, the machine stops after running a drain-up 

mechanism for 3 minutes when air-cooling operation 

is stopped.

Wait for 3 minutes.

The sound of the ex-

haust and the rotation 

of the motor can be 

heard intermittently 

after stop of running.

All lights are out ex-

cept the powered dis-

play of “ ”.

When other indoor units are engaged in cooling 

operation, drained water is brought in. If the drain 

water is collected, the drain-up mechanism initiates a 

draining operation.

It soon stops. (If the noise occurs more than 2-3 times in 

an hour, ask for repair service.)

Warm air comes out 

intermittently when the 

thermostat is OFF or 

during fan operation.

The liquid crystal dis-

play shows that it is in 

the state of operation.

When other indoor units are engaged in heating 

operation, the control valves are opened and closed 

from time to time to maintain the stability of the sys-

tem.

It soon stops. (If the room temperature rises uncomfortably 

high in a small room, stop operation.)

• 

If operation stops due to a power failure, the [restart-preventing circuit at power failure] operates and disables unit operation even after power restoration. In this case, 

press the [ON/OFF] button again and start operation.

If malfunctions persist after you have checked the above, turn the power supply OFF and contact your dealer with information about the product name, the nature of the 

malfunction, etc. If the display of “[CHECK]” and (4 digit) check code flashes, tell the dealer contents of the display (check code). Never attempt to repair by yourself.

The following symptoms are not air conditioner failures:

• 

The air blown out from the air conditioner can sometimes give off odors. This is due to cigarette smoke contained in the air of the room, the smell of cosmetics, the 

walls, furniture, etc., absorbed in the air conditioner.

•  A hissing noise can be heard immediately after the air conditioner is started or stopped. This is the sound of the refrigeration flowing inside the air conditioner. This is 

normal.

• 

The air conditioner sometimes snaps or clicks at the beginning or end of cooling/heating operation. This is the sound of friction on the front panel and other sections 

due to expansion and contraction caused by temperature change. This is normal.

• 

The fan speed changes in spite of not changing the setting. Not to blow out cold air at the beginning of heating operation, the air conditioner automatically adjusts the 

fan speed gradually from lower to the set speed. It also adjust its fan speed to protect the fan motor when return air temperature or fan speed excessively rises.

Summary of Contents for City Multi PEFY-P-NMHSU-E

Page 1: ...operating the air conditioner unit MANUEL D UTILISATION Pour une utilisation correcte sans risques veuillez lire le manuel d utilisation en entier avant de vous servir du climatiseur Air Conditioners INDOOR UNIT PEFY P NMHU E 2 PEFY P NMHU E F PLFY P NLMU E PFFY P NEMU E PFFY P NRMU E PEFY P NMHSU E ...

Page 2: ...e Filter b Touche ON OFF Touche c Position du capteur de température de la pièce intégré d Touche de réglage de l heure Ne jamais laisser la commande à distance en plein soleil sinon les données de température ambiante risquent d être erronées Ne jamais placer d obstacle devant la partie inférieure droite de la com mande à distance sinon la lecture des températures ne sera pas correcte ON OFF ERRO...

Page 3: ...3 Fig A PLFY P NLMU E A PEFY P NMHU E 2 PEFY P NMHU E F A A PEFY P NMHSU E PFFY P NEMU E NRMU E A A A Filter Air Flow Filtre Flux d air ...

Page 4: ...y precautions 1 Outdoor unit Warning The outdoor unit must be installed on a stable level surface in a place where there is no accumulation of snow leaves or rubbish Do not stand on or place any items on the unit You may fall down or the item may fall causing injury Caution The outdoor unit should be installed in a location where air and noise emit ted by the unit will not disturb the neighbours 2...

Page 5: ...nit Warning When you need to dispose of the unit consult your dealer If pipes are re moved incorrectly refrigerant fluorocarbon gas may blow out and come into contact with your skin causing injury Releasing refrigerant into the atmosphere also damages the environment 2 Names and functions of various parts Attachment and detachment of filter Fig A P 3 Caution In removing the filter precautions must...

Page 6: ...etc The fan speed comes to low or high Except PEFY P NMHU E F 3 3 Room temperature adjustment To change room temperature Press the 1 Set Temperature Button and set the room temperature of your choice Pressing or once changes the setting by 1 C 1 F If the pressing is continued the setting continues to change by 1 C 2 F Indoor temperature can be set within the following range Cooling dry 19 C 67 F 3...

Page 7: ... you start cleaning stop operation and turn OFF the power sup ply Remember that the fan is rotating inside at high speed posing a serious risk of injury Indoor units are equipped with filters to remove the dust of sucked in air Clean the filters using the methods shown in the following sketch es The standard filter should normally be cleaned once a week and the long life filter at the beginning of...

Page 8: ...ped Wait for 3 minutes The sound of the ex haust and the rotation of the motor can be heard intermittently after stop of running All lights are out ex cept the powered dis play of When other indoor units are engaged in cooling operation drained water is brought in If the drain water is collected the drain up mechanism initiates a draining operation It soon stops If the noise occurs more than 2 3 t...

Page 9: ...ferring the instal lation Caution When moving or reinstalling the air conditioner consult with your dealer Defective installation can result in electric shock fire etc Regarding noise In installing work choose a place that can fully bear the weight of the air con ditioner and where noise and vibration can be reduced Choose a place where cool or warm air and noise from the outdoor air outlet of the...

Page 10: ...ating kW 11 7 15 8 17 6 23 4 31 7 BTU h 40000 54000 60000 80000 108000 Dimension Height mm 380 470 in 15 18 9 16 Width mm 1195 1250 in 47 1 4 49 1 4 Depth mm 900 1120 in 35 7 16 44 1 8 Net weight kg 69 71 100 lb 153 157 221 FAN Airflow rate Low High m3 min 26 5 38 0 26 5 38 0 28 0 40 0 58 0 72 0 cfm 936 1342 936 1342 989 1412 2048 2541 External static pres sure 3 Pa 208V 100 250 100 250 100 250 70...

Page 11: ...r the factory setting is below PEFY P NMHU E F series PEFY P30NMHU E F PEFY P54NMHU E F PEFY P72NMHU E F PEFY P96NMHU E F 208V 230V 208V 230V 208V 230V 208V 230V 85 130 85 130 180 260 180 260 PEFY P NMHSU E Model Item PEFY P72NMHSU E PEFY P96NMHSU E Power source 208 230V 60Hz Capacity 1 Cooling kW 21 1 28 1 BTU h 72000 96000 Heating kW 23 4 31 7 BTU h 80000 108000 Dimension Height mm 470 in 18 9 1...

Page 12: ...MU E PFFY P12NRMU E PFFY P15NRMU E PFFY P18NRMU E PFFY P24NRMU E Power source 208 230V 60Hz Capacity 1 Cooling kW 1 8 2 3 3 5 4 4 5 3 7 0 BTU h 6000 8000 12000 15000 18000 24000 Heating kW 2 0 2 6 4 0 5 0 5 9 7 9 BTU h 6700 9000 13500 17000 20000 27000 Dimension Height mm 630 in 25 3 16 Width mm 886 1006 1246 in 34 15 16 39 5 8 49 1 16 Depth mm 220 in 8 11 16 Net weight kg 19 19 20 21 25 27 lb 41 ...

Page 13: ...e le moteur et le LEV restent secs en utilisant une couverture étanche Note 2 N évacuez jamais l eau de lavage pour la cuvette d écoulement et l échangeur thermique avec la pompe de drainage Evacuez la séparément Ne pas permettre l usage de cet appareil à des enfants en bas âge ou à des handicapés sans supervision Toujours prendre toutes les précautions nécessaires pour éviter que des enfants en b...

Page 14: ...e certaine période Si le climatiseur ne doit pas être utilisé pendant une certaine période à cause d un changement de climat etc le faire fonctionner pendant 4 5 heures avec la soufflerie d air jusqu à ce que l intérieur soit complète ment sec Sinon de la moisissure non hygiénique et insalubre risque de se développer à des endroits divers Lorsqu il ne doit pas être utilisé pendant un certain temps...

Page 15: ...é par le climatiseur sinon sa combustion sera irrégulière Le micro ordinateur fonctionne dans les cas suivants L air ne souffle pas lorsque le chauffage démarre Pour éviter le souffle d air froid le ventilateur interne est progressivement allumé par étapes entre un très léger souffle un léger souffle la soufflerie programmée en fonction de l augmentation de la température de l air propulsé Il faut...

Page 16: ... durée doivent l être au début de chaque saison d utilisation La durée de vie du filtre dépend du lieu d installation de l appareil et de son fonctionnement Comment nettoyer les filtres Brosser doucement la poussière ou nettoyer le filtre avec l aspirateur En cas de taches persistantes laver le filtre dans de l eau tiède avec un détergent non abrasif ou dans de l eau pure puis rincer convenablemen...

Page 17: ...e la rotation du moteur est toujours audible par intermit tence après l arrêt du climatiseur Tous les témoins sont éteints sauf le témoin de mise sous tension Lorsque d autres appareils intérieurs sont program més pour le refroidissement l eau d écoulement est amenée à l intérieur Lorsque l eau d écoulement est rassemblée le mécanisme d écoulement entame l opération de drainage Le bruit s arrête r...

Page 18: ...ur une estimation du coût des travaux requis pour le démé nagement de l installation Précaution Lors du déménagement et de la réinstallation du climatiseur veuillez prendre contact avec votre revendeur car une installation défectueuse peut être la cause d électrocution d incendie etc Faire également attention au bruit Lors des travaux d installation choisir un endroit capable de supporter entiè re...

Page 19: ...000 54000 60000 80000 108000 Dimensions Hauteur mm 380 470 in 15 18 9 16 Largeur mm 1195 1250 in 47 1 4 49 1 4 Profondeur mm 900 1120 in 35 7 16 44 1 8 Poids net kg 69 71 100 lb 153 157 221 VENTILA TEUR Débit de l air Faible Haut m3 min 26 5 38 0 26 5 38 0 28 0 40 0 58 0 72 0 cfm 936 1342 936 1342 989 1412 2048 2541 Pression statique externe 3 Pa 208V 100 250 100 250 100 250 70 160 70 160 230V 150...

Page 20: ...ages d usine Séries PEFY P NMHU E F PEFY P30NMHU E F PEFY P54NMHU E F PEFY P72NMHU E F PEFY P96NMHU E F 208V 230V 208V 230V 208V 230V 208V 230V 85 130 85 130 180 260 180 260 PEFY P NMHSU E Modèle Élément PEFY P72NMHSU E PEFY P96NMHSU E Source d alimentation 208 230V 60Hz Capacité 1 Refroidissement kW 21 1 28 1 BTU h 72000 96000 Chauffage kW 23 4 31 7 BTU h 80000 108000 Dimensions Hauteur mm 470 in...

Page 21: ... P24NRMU E Source d alimentation 208 230V 60Hz Capacité 1 Refroidissement kW 1 8 2 3 3 5 4 4 5 3 7 0 BTU h 6000 8000 12000 15000 18000 24000 Chauffage kW 2 0 2 6 4 0 5 0 5 9 7 9 BTU h 6700 9000 13500 17000 20000 27000 Dimensions Hauteur mm 630 in 25 3 16 Largeur mm 886 1006 1246 in 34 15 16 39 5 8 49 1 16 Profondeur mm 220 in 8 11 16 Poids net kg 19 19 20 21 25 27 lb 41 41 45 47 56 60 VENTILA TEUR...

Page 22: ......

Page 23: ......

Page 24: ...ne number on this manual before handing it to the customer HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN WT06893X01 This product is designed and intended for use in the residential commercial and light industrial environment ...

Reviews: