background image

9

GB

D

F

E

I

NL

GR

RU

TR

CZ

SV

HG

PO

Store the piping to be used during installation indoors and keep both
ends of the piping sealed until just before brazing.

- If dust, dirt, or water gets into the refrigerant cycle, the oil will deteriorate and

the compressor may fail.

Use Suniso 4GS or 3GS (small amount) refrigerator oil to coat the flare
and flange connection part. (For models using R22)

Use ester oil, ether oil or alkylbenzene (small amount) as the refrigerator
oil to coat flares and flange connections. (For models using  R410A or R407C)

- The refrigerant used in the unit is highly hygroscopic and mixes with water

and will degrade the refrigerator oil.

7.2. Drain piping work

Ensure that the drain piping is downward (pitch of more than 1/100) to the
outdoor (discharge) side. Do not provide any trap or irregularity on the way.

Ensure that any cross-wise drain piping is less than 20 m [65 ft] (excluding the
difference of elevation). If the drain piping is long, provide metal braces to prevent
it from waving. Never provide any air vent pipe. Otherwise drain may be ejected.

Use a hard vinyl chloride pipe O. D. ø32 mm [1-1/4 in] for drain piping.

Ensure that collected pipes are 10 cm [3-15/16 in] lower than the unit body’s
drain port.

Do not provide any odor trap at the drain discharge port.

Put the end of the drain piping in a position where no odor is generated.

Do not put the end of the drain piping in any drain where ionic gases are generated.

[Fig. 7.2.1] (P.3)

Correct piping

Wrong piping

A

Insulation (9 mm [3/8 in] or more)

B

Downward slope (1/100 or more)

C

Support metal

K

Air bleeder

L

Raised

M

Odor trap

Grouped piping

D

O. D. ø32 mm [1-1/4 in] PVC TUBE

E

Make it as large as possible. About 10 cm [3-15/16 in].

F

Indoor unit

G

Make the piping size large for grouped piping.

H

Downward slope (1/100 or more)

I

O. D. ø38 mm [1-1/2 in] PVC TUBE for grouped piping.

(9 mm [3/8 in] or more insulation)

J

Up to 550 mm [21-11/16 in]

N

Drain hose (accessory)

O

Horizontal or slightly upgradient

1.

Insert the drain hose (accessory) into the drain port (insertion margin: 32 mm
[1-1/4 in]).
(The drain hose must not be bent more than 45° to prevent the hose from
breaking or clogging.)
(Attach the hose with glue, and fix it with the band (small, accessory).)

2.

Attach the drain pipe (O.D. ø32 mm [1-1/4 in] PVC TUBE PV-25, field supply).
(Attach the pipe with glue, and fix it with the band (small, accessory).)

3.

Perform insulation work on the drain pipe (O.D. ø32 mm [1-1/4 in] PVC TUBE
PV-25) and on the socket (including elbow).

4.

Check the drainage. (Refer to [Fig. 7.3.1])

7. Connecting refrigerant pipes and drain pipes

7.1. Refrigerant piping work

This piping work must be done in accordance with the installation manuals for both
outdoor unit and BC controller (simultaneous cooling and heating series R2).

Series R2 is designed to operate in a system that the refrigerant pipe from an
outdoor unit is received by BC controller and branches at the BC controller to
connect between indoor units.

For constraints on pipe length and allowable difference of elevation, refer to
the outdoor unit manual.

The method of pipe connection is brazing connection.

 Caution:

Install the refrigerant piping for the indoor unit in accordance with the
following.

1. Cut the tip of the indoor unit piping, remove the gas, and then remove the

brazed cap.

[Fig. 7.1.1] (P.3)

A

Cut here

B

Remove brazed cap

2. Pull out the thermal insulation on the site refrigerant piping, braze the unit

piping, and replace the insulation in its original position.
Wrap the piping with insulating tape.

Note:

When blazing the refrigerant pipes, be sure to blaze, after covering a wet
cloth to the pipes of the units in order to prevent it from burning and
shrinking by heat.

[Fig. 7.1.2] (P.3)

A

Cool by a wet cloth

Pay strict attention when wrapping the copper piping since wrapping the
piping may cause condensation instead of preventing it.

[Fig. 7.1.3] (P.3)

A

Thermal insulation

B

Pull out insulation

C

Wrap with damp cloth

D

Return to original position

E

Ensure that there is no gap here

F

Wrap with insulating tape

Cautions On Refrigerant Piping

Be sure to use non-oxidative brazing for brazing to ensure that no for-
eign matter or moisture enter into the pipe.
Be sure to apply refrigerating machine oil over the flare connection seat-
ing surface and tighten the connection using a double spanner.
Provide a metal brace to support the refrigerant pipe so that no load is
imparted to the indoor unit end pipe. This metal brace should be pro-
vided 50 cm away from the indoor unit’s flare connection.

 Warning:

When installing and moving the unit, do not charge it with refrigerant other
than the refrigerant specified on the unit.

- Mixing of a different refrigerant, air, etc. may cause the refrigerant cycle to mal-

function and result in severe damage.

 Caution:

Use refrigerant piping made of C1220 (Cu-DHP) phosphorus deoxidized
copper as specified in the JIS H3300 “Copper and copper alloy seamless
pipes and tubes”. In addition, be sure that the inner and outer surfaces
of the pipes are clean and free of hazardous sulphur, oxides, dust/dirt,
shaving particles, oils, moisture, or any other contaminant.

Never use existing refrigerant piping.

- The large amount of chlorine in conventional refrigerant and refrigerator oil

in the existing piping will cause the new refrigerant to deteriorate.

6.1. Refrigerant pipe and drain pipe specifications

6.2. Refrigerant pipe, drain pipe

[Fig. 6.2.1] (P.2)

A

Refrigerant pipe (liquid pipe)

B

Refrigerant pipe (gas pipe)

C

Drain pipe (O.D. ø32 [1-1/4 in])

D

Drain pipe (O.D. ø32 [1-1/4 in], spontaneous draining)

Model

PEFY-P·NMAU-E

Item

06·08·12·15·18

24·27·30·36·48·54

Liquid pipe

ø 6.35 [1/4]

ø 9.52 [3/8]

Gas pipe

ø 12.7 [1/2]

ø 15.88 [5/8]

Drain pipe

O.D. ø 32 [1-1/4]

Refrigerant pipe

(Brazing connection)

(Unit: mm [in])

01_KB79P491H01_GB.p65

6/23/09, 4:22 PM

9

Summary of Contents for CITY MULTI PEFY-P06NMAU-E

Page 1: ...ANUAL For safe and correct use please read this installation manual thoroughly before installing the air conditioner unit MANUEL D INSTALLATION Veuillez lire le manuel d installation en entier avant d installer ce climatiseur pour éviter tout accident et vous assurer d une utilisation correcte ...

Page 2: ...7 16 357 14 1 16 122 4 13 16 33 1 5 16 41 1 5 8 217 8 9 16 C A B D A Access door B Electrical parts box C Air inlet D Air outlet E Ceiling surface F Service space viewed from the side G Service space viewed from the direction of arrow 1 600 mm 23 5 8 in or more 2 100 mm 3 15 16 in or more 3 20 mm 13 16 in or more 4 300 mm 11 13 16 in or more Model PEFY P06 08 12NMAU E PEFY P15 18NMAU E PEFY P24 27...

Page 3: ...it as large as possible About 10 cm 3 15 16 in F Indoor unit G Make the piping size large for grouped piping H Downward slope 1 100 or more I O D ø38 1 1 2 in PVC TUBE for grouped piping 9 mm 3 8 in or more insulation J Up to 550 mm 21 11 16 in N Drain hose accessory O Horizontal or slightly upgradient 7 2 Fig 7 2 2 C B A L D D D E K M B H I Max 20m 65ft 1 5 2m 5 7ft G F F F B C D D G F E H A 32 1...

Page 4: ... B Terminal block for outdoor transmission cable C Remote controller 9 2 Fig 7 3 1 7 3 A Insert pump s end 2 to 4 cm 13 16 to 1 5 8 in B Remove the water supply port C About 2500 cc D Water E Filling port F Screw Fig 8 0 2 SWE Fig 7 3 2 Fig 8 0 3 Fig 8 0 4 Indoor controller board A B F C D E A B G F A A B C D E F G C E Duct Air inlet Access door Canvas duct Ceiling surface Air outlet Leave distanc...

Page 5: ...ound terminal C Shield wire D The earth wire from two cables are connected together to the S terminal Dead end connection E Insulation tape To keep the earth wire of the shielded cable from coming in contact with the transmis sion terminal 9 3 Fig 9 3 3 Fig 9 3 4 Fig 9 3 5 C Terminal box D Knockout hole E Remove A Screw holding cover 1pc B Cover Fig 9 3 1 Fig 9 3 2 A Non polarized B TB15 C Remote ...

Page 6: ...ins Improper handling may result in injury When handling this product always wear protective equipment EG Gloves full arm protection namely boiler suit and safety glasses Improper handling may result in injury If refrigerant gas leaks during installation work ventilate the room If the refrigerant gas comes into contact with a flame poisonous gases will be released Install the air conditioner accor...

Page 7: ...t on a structure that may cause leakage When the room humidity exceeds 80 or when the drain pipe is clogged condensation may drip from the indoor unit Perform collective drainage work together with the outdoor unit as required The indoor models should be installed the ceiling over than 2 5 m from floor 1 4 Before getting installed moved elec trical work Caution Ground the unit Do not connect the g...

Page 8: ...1 2 P 2 C Nuts field supply D Washers field supply E M10 hanging bolt field supply 5 2 Confirming the unit s position and fix ing hanging bolts Use the gage supplied with the panel to confirm that the unit body and hanging bolts are positioned in place If they are not positioned in place it may result in dew drops due to wind leak Be sure to check the positional relationship Use a level to check t...

Page 9: ... is designed to operate in a system that the refrigerant pipe from an outdoor unit is received by BC controller and branches at the BC controller to connect between indoor units For constraints on pipe length and allowable difference of elevation refer to the outdoor unit manual The method of pipe connection is brazing connection Caution Install the refrigerant piping for the indoor unit in accord...

Page 10: ...e and outlet duct to prevent condensa tion Be sure to change the position of air filter to the position where it can be serv iced Fig 8 0 1 P 4 A In case of rear inlet B In case of bottom inlet A Duct B Air inlet C Access door D Canvas duct E Ceiling surface F Air outlet G Leave distance enough to prevent short cycle Procedure for changing the rear inlet to the bottom inlet Fig 8 0 2 P 4 A Filter ...

Page 11: ...pe water pipe lightening rod or telephone earth cable Incomplete grounding may cause a risk of electric shock Types of control cables 1 Wiring transmission cables Types of transmission cables Design wiring in accordance with the following table Table 1 Cable diameter More than 1 25 mm2 AWG16 Precautions on electrical wiring Warning Electrical work should be done by qualified electrical engineers i...

Page 12: ... box cover with that shown on the rating name plate 1 Remove the screw 1pc holding the cover to dismount the cover Fig 9 3 1 P 5 A Screw holding cover 1pc B Cover 2 Open knockout holes Recommend to use a screwdriver or the like for this work Fig 9 3 2 P 5 C Terminal box D Knockout hole E Remove 3 Fix power source wiring to terminal box by using buffer bushing for tensile force PG connection or the...

Page 13: ... de protection pour manipuler ce produit Par ex gants protection intégrale des bras par combinaison et lunettes de sécurité Vous risqueriez de vous blesser En cas de fuite de gaz durant l installation aérez la pièce Si le gaz réfrigérant entre en contact avec une flamme il y aura émission de gaz toxiques Installez le climatiseur en respectant les instructions du manuel d installa tion En cas d ins...

Page 14: ...èles intérieurs doivent être installés à un plafond situé à plus de 2 5 m du sol 1 4 Avant de procéder à l installation déplacement installation électrique Précaution Mettez l appareil à la terre NNe branchez pas le fil de mise à la terre à un tuyau de gaz ou d eau un para tonnerre ou câble téléphonique de terre Une mauvaise mise à la terre peut pro voquer des risques d électrocution Installez le ...

Page 15: ... 1 Fixation des boulons de suspension Fig 4 1 1 P 2 Fournir une structure résistante à l endroit de suspension de l appareil Cadre de suspension Plafond La structure du plafond varie d un édifice à un autre Pour plus d informa tions veuillez prendre contact avec la société de construction de l immeuble Si nécessaire renforcez les boulons de suspension avec des supports antisismi ques comme mesure ...

Page 16: ... tuyaux de réfrigérant Toujours utiliser des soudures non oxydantes afin qu aucun corps étranger ni aucune humidité ne pénètre à l intérieur du tuyau Revêtir le siège du goujon d huile pour machine réfrigérante et le serrer fermement à l aide de deux clés Placer une entretoise métallique pour soutenir les tuyaux de réfrigérant de telle sorte qu aucune charge ne s applique à la sortie des tuyaux de...

Page 17: ...s de fonctionner sans télécommande Veiller au bon écou lement en utilisant un tube transparent 4 Après confirmation annuler le mode d essai et couper l alimentation principale Si le connecteur est relié au côté ON de SWE le débrancher et le rebrancher au côté OFF puis fixer capot du port d alimentation en eau dans sa position initiale Fig 7 3 1 P 4 Fig 7 3 2 P 4 8 Raccords des conduites Lors du ra...

Page 18: ... Ne pas raccorder le câble de terre à une conduite de gaz à une conduite d eau à un paratonnerre ou à un câble de terre téléphonique Une mauvaise mise à la terre peut consti tuer un danger d électrocution Types de câbles de commandes 1 Mise en place des câbles de transmission Types de câbles de transmission Concevoir le câblage conformément aux indications reprises dans le tableau sui vant Table1 ...

Page 19: ...sance électrique entre les éléments accessibles et le circuit de con trôle doit être de 2 750 V minimum 9 5 Sélection de la pression statique extérieure Le réglage d usine admet une pression statique extérieure de 0 20 in WG 50 Pa par conséquent aucun commutateur n est nécessaire pour une utilisation en deçà des conditions standard Fig 9 5 1 P 5 9 6 Configuration des adresses Toujours effectuer ce...

Page 20: ...ress telephone number on this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN ...

Reviews: