13
REFRIGERANT SYSTEM DIAGRAM
6
Strainer (#100mesh)
Strainer (#100mesh)
Heat exchanger
Room temperature thermistor TH21
Gas pipe thermistor TH23
Liquid pipe thermistor TH22
Linear expansion valve
Gas pipe
Flared joints(Type 40~140)
Brazed joints(Type 200·250)
Gas pipe
PEFY-P40VMH-E
PEFY-P50VMH-E
Liquid pipe
Capacity
Item
ø
12.7 <1/2F> (R410A)
ø
12.7 <1/2F>
ø
6.35 <1/4F>
ø
15.88 <5/8F>
ø
9.52 <3/8F>
ø
15.88 <5/8F> (R22,R407C)
ø
6.35 <1/4F> (R410A)
ø
9.52 <3/8F> (R22,R407C)
PEFY-P63,71,80VMH-E
Gas pipe
PEFY-P100,125,140VMH-E
PEFY-P200VMH-E
Liquid pipe
Capacity
Item
ø
19.05 <3/4> (R410A)
ø
9.52 <3/8F>
ø
25.4 <1> (R22,R407C)
ø
15.88 <5/8F> (R410A)
ø
19.05 <3/4F> (R22,R407C)
ø
9.52 <3/8> (R410A)
ø
12.7 <1/2> (R22,R407C)
ø
22.2 <7/8> (R410A)
ø
28.58 <1-1/8> (R22,R407C)
ø
9.52 <3/8> (R410A)
ø
12.7 <1/2> (R22,R407C)
PEFY-P250VMH-E