background image

GB

3

3.  Installing the indoor unit

3.1. Indoor unit mounting bracket installation

• Install the bracket firmly to the wall structure (stud, etc.). (Fig. 3-1)
• Use a level to install the mounting bracket horizontally.
• Install the indoor unit 150 mm or below from the floor.
 

A

 Indoor unit mounting bracket

Note:
To prevent the indoor unit mounting bracket from vibrating slightly, be sure 
to fasten the bracket at the holes indicated by  . In addition, fasten the 
bracket at the holes indicated by   if possible. (Fig. 3-2)

3.2. Indoor unit preparation

1

 Press the 2 positions indicated by the arrows   and open the front grille.

   (Fig. 3-3)

2

 Open the front grille and remove the 2 screws.

3

 Open the horizontal vane for the upper air outlet, push the top of the front panel 

   in 3 locations, and then pull the top of the grille away from the indoor unit.
 

B

 Screws

4

 Lift up the front grille to remove it. (Fig. 3-4)

(mm)

Fig. 3-1

Fig. 3-3

(700)

200

131

131

14

586 (600)

Fig. 3-2

Fig. 3-4

Fig. 3-7

Fig. 3-5

Fig. 3-6

674

333

210

363

496

97

23

78

599

288

80

700

600

131

131

14

1)

3.3. Indoor unit installation (Fig. 3-5)

• Hook the top of the indoor unit on the indoor unit mounting bracket.
• Use the included wood screws and washer, and fasten the indoor unit at 2 loca-

tions ( ) each at the top and the middle of the unit.

Note:
Install the indoor unit securely to the wall, making sure that there is no gap
between the unit and the wall.

3.4. Making holes in the wall and floor

3.4.1. Making holes (Fig. 3-6)

1

 Make ø65 mm or ø75 mm holes that are approximately 5–7 mm deep and an-

gled slightly downward outward from the room.

2

 Insert the wall hole sleeves into the holes.

 

A

 

Wall hole

 

B

 65 mm or 75 mm dia.

 

C

 Indoor side

 

D

 Wall hole cross section

 

E

 Wall thickness

 

F

 One scale

 

G

 Cut with 1 extra scale length.

 

H

 Wall hole sleeve

 Caution:

Be sure to use the wall hole sleeves. Otherwise, the indoor/outdoor unit con-
necting wires may contact a metal object in the wall or, in the case of hollow
walls, small rodents may gnaw on the wires, resulting in a very dangerous 
situation.

3.4.2. Determining hole positions

The areas where the piping can be routed are indicated with oblique lines in the
figure.

1) For rear or left-rear piping (Fig. 3-7)

 

(The following figure is a front view of the indoor unit installation location.)

Summary of Contents for CITY MULTI PFFY-P-VKM-E

Page 1: ...DE INSTALACIÓN Para un uso seguro y correcto lea detalladamente este manual de instalación antes de montar la unidad de aire acondicionado MANUAL DE INSTALAÇÃO Para uma utilização segura e correcta leia atentamente este manual e o manual de instalação da unidade exte rior antes de instalar o aparelho de ar condicionado PARA O INSTALADOR PER L INSTALLATORE PARA EL INSTALADOR VOOR DE INSTALLATEUR PO...

Page 2: ...rant should leak The cut face punched parts may cause injury by cut etc The installers are requested to wear protective equipment such as gloves etc When installing or relocating or servicing the outdoor unit use only the specified refrigerant R410A to charge the refrigerant lines Do not mix it with any other refrigerant and do not allow air to remain in the lines If air is mixed with the refriger...

Page 3: ...1 14 1 3 3 Indoor unit installation Fig 3 5 Hook the top of the indoor unit on the indoor unit mounting bracket Use the included wood screws and washer and fasten the indoor unit at 2 loca tions each at the top and the middle of the unit Note Install the indoor unit securely to the wall making sure that there is no gap between the unit and the wall 3 4 Making holes in the wall and floor 3 4 1 Maki...

Page 4: ...o insulate indoor unit connections Insulate carefully Warning When installing the unit securely connect the refrigerant pipes before start ing the compressor Copper pipe O D mm Flare dimensions øA dimensions mm ø6 35 8 7 9 1 ø9 52 12 8 13 2 ø12 7 16 2 16 6 ø15 88 19 3 19 7 ø19 05 23 6 24 0 A Flare cutting dimensions B C D 90 0 5 øA R 0 4 R 0 8 A 45 2 Fig 4 1 B Refrigerant pipe sizes Flare nut tigh...

Page 5: ...ghtly downward 1 100 or more so that the drain water flows easily Do not route the drain piping as shown in the examples mark with an X in the figure Fig 5 1 If the drain hose is too short refer to Fig 5 2 to extend the length of the hose If the indoor unit is installed in a high location such as a high rise apartment strong winds may cause the drain water to flow back through the drain hose and l...

Page 6: ...d etc to ad just the height of the indoor unit If the upper or lower air outlet is blocked the air conditioner will not be able to cool or warm the room well Use a grating with vertical bars etc that has at least 75 open area If the grat ing has horizontal bars or if the open area is less than 75 performance could be reduced When the indoor unit is embedded in a wall built in the time it takes for...

Page 7: ...bles refer to the outdoor unit installation manual Install a remote controller following the manual supplied with the remote control ler Connect the remote controller s transmission cable within 10 m using a 0 75 mm2 core cable If the distance is more than 10 m use a 1 25 mm2 junction cable 1 MA Remote controller Connect the connector for MA remote controller Non polarized 2 wire DC 9 to 13 V betw...

Page 8: ...arning Do not use the air conditioner if the insulation resistance is less than 1 0 M 8 2 Test run Using wired remote controller Fig 8 1 1 Turn on the power at least 12 hours before the test run 2 Press the TEST button twice TEST RUN liquid crystal display 3 Press the Mode selection button Make sure that wind is blown out 4 Press the Mode selection button and switch to the cooling or heating mode ...

Page 9: ...dress board SWC SWC Note Be sure to operate with the main power turned off Description of operation Operation Upper and lower air flow Room temperature and set temperature are dif ferent Upper air flow Room temperature is close to set temperature or thermo off Upper air flow only Upper and lower air flow Normal condition in heating Upper air flow During defrosting op eration start of opera tion th...

Page 10: ...ct at hand is based on the following EU regulations Low Voltage Directive 2006 95 EC Electromagnetic Compatibility Directive 2004 108 EC Machinery Directive 2006 42 EC Energy related Products Directive 2009 125 EC HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Authorized representative in EU MITSUBISHI EUROPE B V HARMAN HOUSE 1 GEORGE STREET UXBRIDE MIDDLE SEX UB8 1QQ U K ...

Reviews: