background image

GB

6

5.  Drainage piping work

• Insert the drain hose all the way to the base of the drain pan. (Fig. 5-4) Make sure 

that the drain hose is securely caught on the projection in the hole in the drain 
pan.

Fig. 5-4

Fig. 5-5

• Route the drain hose diagonally below the connecting pipes. (Fig. 5-5)
   

A

 Piping tape

   

B

 Refrigerant piping

   

C

 Drain hose

• Make sure that the drain hose is not routed upward and that there are no waves 

in the hose.

• Do not pull the drain hose, and then wrap tape around it.
• Route the piping so that it does not project past the rear of the indoor unit. (Refer 

to the figure to the left.)

   

D

 Piping bent outward

   

E

 Push

6.  Embedding the indoor unit in a wall

6.1. Embedding the indoor unit in a wall (Fig. 6-1)

• On the indoor unit and right and left space (100 mm or more) are the service 

space.

• On a right side of the indoor unit, there is a hole for the room temperature sensor, 

and do not close it, please.

• When installing a grating, use a grating with narrow upper and lower horizontal 

bars so that the airflow from the upper and lower air outlets does not contact the 
bars. If the horizontal bars will block the lower air outlet, use a stand, etc., to ad-
just the height of the indoor unit. If the upper or lower air outlet is blocked, the air 
conditioner will not be able to cool or warm the room well.

• Use a grating with vertical bars, etc., that has at least 75% open area. If the grat-

ing has horizontal bars or if the open area is less than 75%, performance could 
be reduced.

• When the indoor unit is embedded in a wall (built-in), the time it takes for the room 

temperature to reach the set temperature will increase.

   

A

 100 mm or more

   

B

 Upper air outlet

   

C

 Lower air outlet

   

D

 Grating

   

E

 100 mm or more

   

F

 Indoor unit

   

G

 35 mm or more

6.2. Embedded indoor unit setting (must be performed)
  

(Fig. 6-2)

• When embedding the indoor unit in a wall, restrict the movement of the horizontal 

vane for the upper air outlet so that it only operates horizontally.

• If this setting is not performed, heat will build up in the wall and the room will not 

be cooled or warmed properly.

• Remove the electrical part cover and pull out the control board.
• Set DIP switches 3-5 and 3-6 on the control board to ON.
• After setting the switches, reinstall the control board in its original position and 

install the electrical part cover.

 Caution:

To avoid damage to the control board due to static electricity, be sure to dis-
charge the static buildup before handling it.

Fig. 6-1

65

52

475

Fig. 6-2

ON

SW3

1 2 3 4 5 6 7 8 9 10

Summary of Contents for CITY MULTI PFFY-P-VKM-E

Page 1: ...DE INSTALACIÓN Para un uso seguro y correcto lea detalladamente este manual de instalación antes de montar la unidad de aire acondicionado MANUAL DE INSTALAÇÃO Para uma utilização segura e correcta leia atentamente este manual e o manual de instalação da unidade exte rior antes de instalar o aparelho de ar condicionado PARA O INSTALADOR PER L INSTALLATORE PARA EL INSTALADOR VOOR DE INSTALLATEUR PO...

Page 2: ...rant should leak The cut face punched parts may cause injury by cut etc The installers are requested to wear protective equipment such as gloves etc When installing or relocating or servicing the outdoor unit use only the specified refrigerant R410A to charge the refrigerant lines Do not mix it with any other refrigerant and do not allow air to remain in the lines If air is mixed with the refriger...

Page 3: ...1 14 1 3 3 Indoor unit installation Fig 3 5 Hook the top of the indoor unit on the indoor unit mounting bracket Use the included wood screws and washer and fasten the indoor unit at 2 loca tions each at the top and the middle of the unit Note Install the indoor unit securely to the wall making sure that there is no gap between the unit and the wall 3 4 Making holes in the wall and floor 3 4 1 Maki...

Page 4: ...o insulate indoor unit connections Insulate carefully Warning When installing the unit securely connect the refrigerant pipes before start ing the compressor Copper pipe O D mm Flare dimensions øA dimensions mm ø6 35 8 7 9 1 ø9 52 12 8 13 2 ø12 7 16 2 16 6 ø15 88 19 3 19 7 ø19 05 23 6 24 0 A Flare cutting dimensions B C D 90 0 5 øA R 0 4 R 0 8 A 45 2 Fig 4 1 B Refrigerant pipe sizes Flare nut tigh...

Page 5: ...ghtly downward 1 100 or more so that the drain water flows easily Do not route the drain piping as shown in the examples mark with an X in the figure Fig 5 1 If the drain hose is too short refer to Fig 5 2 to extend the length of the hose If the indoor unit is installed in a high location such as a high rise apartment strong winds may cause the drain water to flow back through the drain hose and l...

Page 6: ...d etc to ad just the height of the indoor unit If the upper or lower air outlet is blocked the air conditioner will not be able to cool or warm the room well Use a grating with vertical bars etc that has at least 75 open area If the grat ing has horizontal bars or if the open area is less than 75 performance could be reduced When the indoor unit is embedded in a wall built in the time it takes for...

Page 7: ...bles refer to the outdoor unit installation manual Install a remote controller following the manual supplied with the remote control ler Connect the remote controller s transmission cable within 10 m using a 0 75 mm2 core cable If the distance is more than 10 m use a 1 25 mm2 junction cable 1 MA Remote controller Connect the connector for MA remote controller Non polarized 2 wire DC 9 to 13 V betw...

Page 8: ...arning Do not use the air conditioner if the insulation resistance is less than 1 0 M 8 2 Test run Using wired remote controller Fig 8 1 1 Turn on the power at least 12 hours before the test run 2 Press the TEST button twice TEST RUN liquid crystal display 3 Press the Mode selection button Make sure that wind is blown out 4 Press the Mode selection button and switch to the cooling or heating mode ...

Page 9: ...dress board SWC SWC Note Be sure to operate with the main power turned off Description of operation Operation Upper and lower air flow Room temperature and set temperature are dif ferent Upper air flow Room temperature is close to set temperature or thermo off Upper air flow only Upper and lower air flow Normal condition in heating Upper air flow During defrosting op eration start of opera tion th...

Page 10: ...ct at hand is based on the following EU regulations Low Voltage Directive 2006 95 EC Electromagnetic Compatibility Directive 2004 108 EC Machinery Directive 2006 42 EC Energy related Products Directive 2009 125 EC HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Authorized representative in EU MITSUBISHI EUROPE B V HARMAN HOUSE 1 GEORGE STREET UXBRIDE MIDDLE SEX UB8 1QQ U K ...

Reviews: