background image

GB

8

1 2 3 4 5 6 7 8 9 10

ON

OFF

SW1

SW5

220V

240V

CN82

CN43

SW14

SWC

. /

.

(BRANCH No.)

0 12

3

4

5

67

89

AB

C

D

EF

SW11

SW12

0 1

2

3

4

5

6

7

8

9

0 1

2

3

4

5

6

7

8

9

(10ths DIGIT)

(1s DIGIT)

Fig. 7-4

7.5. Setting addresses (Fig. 7-4)

(Be sure to operate with the main power turned OFF.)
• There are 2 types of rotary switch setting available: setting addresses 1 to 9 and 

over 10, and setting branch numbers.

1

 How to set addresses

Example: If Address is “3”, remain SW12 (for over 10) at “0”, and match
SW11 (for 1 to 9) with “3”.

2

 How to set branch numbers SW14 (Series R2 only)

   Match the indoor unit’s refrigerant pipe with the BC controller’s end connection
    number.
   Remain other than series R2 at “0”.
• The rotary switches are all set to “0” when shipped from the factory. These

switches can be used to set unit addresses and branch numbers at will.

• The determination of indoor unit addresses varies with the system at site. Set

them referring to the Data Book.

Note:
Please set the switch SW5 according to the power supply voltage.
• Set SW5 to 240 V side when the power supply is 230 and 240 volts.
• When the power supply is 220 volts, set SW5 to 220 V side.

A

 Address board

7.6. Sensing room temperature with the built-in sensor 

in a remote controller (Fig.7-4)

If you want to sense room temperature with the built-in sensor in a remote 
controller, set SW1-1 on the control board to “ON”. The setting of SW1-7 and 
SW1-8 as necessary also makes it possible to adjust the air flow at a time when 
the heating thermometer is OFF.

8.1. Before test run

 After completing installation and the wiring and piping of the indoor and 

outdoor units, check for refrigerant leakage, looseness in the power 
supply or control wiring, wrong polarity, and no disconnection of one 
phase in the supply.

  Use a 500-volt megohmmeter to check that the resistance between the 

power supply terminals and ground is at least 1.0 M

"

.

 Do not carry out this test on the control wiring (low voltage circuit) 

terminals.

 Warning:

Do not use the air conditioner if the insulation resistance is less than 1.0 M

"

.

8.2. Test run (Using wired remote controller) (Fig 8-1)

1

 Turn on the power at least 12 hours before the test run.

2

 Press the [TEST] button twice.    “TEST RUN” liquid crystal display

3

 Press the [Mode selection] button.    Make sure that wind is blown out.

4

 Press the [Mode selection] button and switch to the cooling (or heating) mode.    

 

 

Make sure that cold (or warm) wind is blown out.

5

 Press the [Fan speed] button.    Make sure that the wind speed is switched.

6

 Check operation of the outdoor unit fan.

7

 Release test run by pressing the [ON/OFF] button.    Stop

8

 Register a telephone number.

      The telephone number of the repair shop, sales office, etc., to contact if an error 

occurs can be registered in the remote controller. The telephone number will be 
displayed when an error occurs. For registration procedures, refer to the operation 
manual for the indoor unit.

Note:
• If an error code is displayed on the remote controller or if the air conditioner 

does not operate properly, refer to the outdoor unit installation manual or 
other technical materials.

• The OFF timer is set for the test run to automatically stop after 2 hours.
• During the test run, the time remaining is shown in the time display.
• During the test run, the temperature of the indoor unit refrigerant pipes is 

shown in the room temperature display of the remote controller.

• When the VANE or LOUVER button is pressed, the message “NOT 

AVAILABLE” may appear on the remote controller display depending on the 
indoor unit model, but this is not a malfunction.

• For the PFFY-P•VKM series, the airflow direction displayed on the remote 

controller is different from the actual airflow direction. Refer to the 
following table.

ON/OFF button

Test run display

Indoor liquid pipe
temperature display

ON/OFF lamp

Power display

Error code display
Test run remaining time
display

Set temperature button

Mode selection button

Fan speed button

Air direction button

 

TEST button

SIMPLE

PAR-21MAA

ON/OFF

FILTER

CHECK

OPERATION

CLEAR

TEST

TEMP.

MENU

BACK

DAY

MONITOR/SET

CLOCK

ON/OFF

TEST RUN
COOL, HEAT

 

 

˚C

˚C

Fig. 8-1

8. Test run

7. Electrical work

Summary of Contents for CITY MULTI PFFY-P-VKM-E

Page 1: ...DE INSTALACIÓN Para un uso seguro y correcto lea detalladamente este manual de instalación antes de montar la unidad de aire acondicionado MANUAL DE INSTALAÇÃO Para uma utilização segura e correcta leia atentamente este manual e o manual de instalação da unidade exte rior antes de instalar o aparelho de ar condicionado PARA O INSTALADOR PER L INSTALLATORE PARA EL INSTALADOR VOOR DE INSTALLATEUR PO...

Page 2: ...rant should leak The cut face punched parts may cause injury by cut etc The installers are requested to wear protective equipment such as gloves etc When installing or relocating or servicing the outdoor unit use only the specified refrigerant R410A to charge the refrigerant lines Do not mix it with any other refrigerant and do not allow air to remain in the lines If air is mixed with the refriger...

Page 3: ...1 14 1 3 3 Indoor unit installation Fig 3 5 Hook the top of the indoor unit on the indoor unit mounting bracket Use the included wood screws and washer and fasten the indoor unit at 2 loca tions each at the top and the middle of the unit Note Install the indoor unit securely to the wall making sure that there is no gap between the unit and the wall 3 4 Making holes in the wall and floor 3 4 1 Maki...

Page 4: ...o insulate indoor unit connections Insulate carefully Warning When installing the unit securely connect the refrigerant pipes before start ing the compressor Copper pipe O D mm Flare dimensions øA dimensions mm ø6 35 8 7 9 1 ø9 52 12 8 13 2 ø12 7 16 2 16 6 ø15 88 19 3 19 7 ø19 05 23 6 24 0 A Flare cutting dimensions B C D 90 0 5 øA R 0 4 R 0 8 A 45 2 Fig 4 1 B Refrigerant pipe sizes Flare nut tigh...

Page 5: ...ghtly downward 1 100 or more so that the drain water flows easily Do not route the drain piping as shown in the examples mark with an X in the figure Fig 5 1 If the drain hose is too short refer to Fig 5 2 to extend the length of the hose If the indoor unit is installed in a high location such as a high rise apartment strong winds may cause the drain water to flow back through the drain hose and l...

Page 6: ...d etc to ad just the height of the indoor unit If the upper or lower air outlet is blocked the air conditioner will not be able to cool or warm the room well Use a grating with vertical bars etc that has at least 75 open area If the grat ing has horizontal bars or if the open area is less than 75 performance could be reduced When the indoor unit is embedded in a wall built in the time it takes for...

Page 7: ...bles refer to the outdoor unit installation manual Install a remote controller following the manual supplied with the remote control ler Connect the remote controller s transmission cable within 10 m using a 0 75 mm2 core cable If the distance is more than 10 m use a 1 25 mm2 junction cable 1 MA Remote controller Connect the connector for MA remote controller Non polarized 2 wire DC 9 to 13 V betw...

Page 8: ...arning Do not use the air conditioner if the insulation resistance is less than 1 0 M 8 2 Test run Using wired remote controller Fig 8 1 1 Turn on the power at least 12 hours before the test run 2 Press the TEST button twice TEST RUN liquid crystal display 3 Press the Mode selection button Make sure that wind is blown out 4 Press the Mode selection button and switch to the cooling or heating mode ...

Page 9: ...dress board SWC SWC Note Be sure to operate with the main power turned off Description of operation Operation Upper and lower air flow Room temperature and set temperature are dif ferent Upper air flow Room temperature is close to set temperature or thermo off Upper air flow only Upper and lower air flow Normal condition in heating Upper air flow During defrosting op eration start of opera tion th...

Page 10: ...ct at hand is based on the following EU regulations Low Voltage Directive 2006 95 EC Electromagnetic Compatibility Directive 2004 108 EC Machinery Directive 2006 42 EC Energy related Products Directive 2009 125 EC HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Authorized representative in EU MITSUBISHI EUROPE B V HARMAN HOUSE 1 GEORGE STREET UXBRIDE MIDDLE SEX UB8 1QQ U K ...

Reviews: