4
Note :
Unit converter
kcal/h = kW × 860
Btu/h = kW × 3,412
cfm =
m
3
/min × 35.31
lb =
kg/0.4536
*Above specification data is
subject to rounding variation.
Model
Power source
Cooling capacity
(Nominal)
Heating capacity
(Nominal )
External finish
External dimension H × W × D
Net weight
Heat exchanger
Fan
Noise level (Low-High)
(measured in anechoic room)
Insulation material
Air filter
Protection device
Refrigerant control device
Connectable outdoor unit
Diameter of
refrigerant pipe
Field drain pipe size
Standard
attachment
Optional parts
Remarks
Power input
Current input
Power input
Current input
Type × Quantity
External
static press.
Motor type
Motor output
Driving mechanism
Airflow rate
(Low-High)
Liquid
Gas
Document
Accessory
External heater adapter
Installation
kW
Btu/h
kW
A
kW
Btu/h
kW
A
mm
in.
kg (lb)
Pa
mmH
2
O
kW
m
3
/min
L/s
cfm
dB <A>
mm (in.)
mm (in.)
mm (in.)
*1
*1
*2
*2
(R410A)
(R22)
(R410A)
(R22)
Installation Manual, Instruction Book
PAC-YU25HT
1-phase 208-230V 60Hz
Cross fin (Aluminum fin and copper tube)
DC motor
Direct-drive
Polyethylene sheet
PP honeycomb
Fuse
LEV
R410A, R22 CITY MULTI
PKFY-P24NKMU-E
Plastic, MUNSELL (1.0Y 9.2/0.2)
7.0
24,000
0.04
0.29
7.9
27,000
0.04
0.29
365 × 1170 × 295
14-3/8" × 46-1/16" × 11-5/8"
21 (46)
Line flow fan × 1
0
0
0.056
20 - 24
333 - 400
710 - 850
43 - 49
I.D. 16mm (5/8")
ø9.52 (ø3/8")
ø9.52 (ø3/8")
ø15.88 (ø5/8")
ø15.88 (ø5/8")
Flare
Flare
Flare
Flare
PKFY-P30NKMU-E
8.8
30,000
0.06
0.43
10.0
34,000
0.06
0.43
16 - 20
267 - 333
570 - 710
39 - 45
Flare
Flare
Flare
Flare
*1 Nominal cooling conditions
Indoor :
Outdoor :
Pipe length :
Level difference :
80°FDB/67°FWB (26.7°CDB/19.4°CWB)
95°FDB (35°CDB)
25 ft. (7.6 m)
0 ft (0 m)
*2 Nominal heating conditions
70°FDB(21°CDB)
47°FDB/43°FWB (8.3°CDB/6.1°CWB)
25 ft. (7.6 m)
0 ft (0 m)
* Due to continuing improvement, above specification may be subject to change without notice.
ø9.52 (ø3/8")
ø9.52 (ø3/8")
ø15.88 (ø5/8")
ø15.88 (ø5/8")
Details on foundation work, insulation work, electrical wiring, power source switch, and other items shall be referred to
the Installation Manual.
2
SPECIFICATION
2-1. Speci
fi
cations