[Detailed setting]

[4]–1. CHANGE LANGUAGE setting

  The language that appears on the dot display can be selected.

•  Press the [ MENU] button 

G

 to change the language.

 

1

 English (GB), 

2

 German (D), 

3

 Spanish (E), 

4

 Russian (RU), 

5

 Italian (I), 

6

 Chinese (CH), 

7

 French (F), 

8

 Japanese (JP)

  Refer to the dot display table.

[4]–2. Function limit

(1) Operation function limit setting (operation locking function)

•  To switch the setting, press the [ ON/OFF] button 

D

.

1

 no1 : Operation lock setting is made on all buttons other than 

the [ ON/OFF] button.

2

 no2 : Operation lock setting is made on all buttons.

3

 OFF (Initial setting value): Operation lock setting is not made.

*  To make the operation lock setting valid on the normal screen, 

it is necessary to press buttons (Press and hold down the 
[FILTER] and [ ON/OFF] buttons at the same time for 2 
seconds.) on the normal screen after the above setting is made.

(2) Use of automatic mode setting
 

When the remote controller is connected to the unit that has 
automatic operation mode, the following settings can be made.
•  To switch the setting, press the [ ON/OFF] button 

D

.

ON (Initial setting value):

 

The automatic mode is displayed when the operation mode is 
selected.

2

 OFF:

 

The automatic mode is not displayed when the operation 
mode is selected.

(3) Temperature range limit setting
 

After this setting is made, the temperature can be changed within 
the set range.
•  To switch the setting, press the [ ON/OFF] button 

D

.

1

  LIMIT TEMP COOL MODE:

 

The temperature range can be changed on cool/dry mode.

2

  LIMIT TEMP HEAT MODE: 

 

The temperature range can be changed on heat mode.

3

 LIMIT TEMP AUTO MODE:

 

The temperature range can be changed on automatic mode.

4

  OFF (initial setting): The temperature range limit is not active.

*  When the setting, other than OFF, is made, the temperature 

range limit setting on cool, heat and automatic mode is made at 
the same time. However, the range cannot be limited when the 
set temperature range has not changed.

•  To increase or decrease the temperature, press the [  TEMP. 

(

) or (

)] button 

F

.

•  To switch the upper limit setting and the lower limit setting, 

press the [ 

 ] button 

H

. The selected setting will flash and the 

temperature can be set.

• Settable range

Cool/Dry mode:
  Lower limit:19°C - 30°C 

Upper limit:30°C - 19°C

Heat mode:
  Lower limit:17°C - 28°C 

Upper limit:28°C - 17°C

Automatic mode:
  Lower limit:19°C - 28°C 

Upper limit:28°C - 19°C

8. Function Selection

[4]–3. Operation mode selection setting

(1) Remote controller main/sub setting

•  To switch the setting, press the [ ON/OFF] button 

D

.

1

  Main: 

The controller will be the main controller.

2

  Sub: 

The controller will be the sub controller.

(2) Use of clock setting

•  To switch the setting, press the [ ON/OFF] button 

D

.

1

  ON: 

The clock function can be used.

2

  OFF: 

The clock function cannot be used.

(3) Timer function setting

•  To switch the setting, press the [ ON/OFF] button 

D

 (Choose 

one of the followings.).

1

  WEEKLY TIMER (initial setting value):

 

The weekly timer can be used.

2

 AUTO OFF TIMER:

 

The auto off timer can be used.

3

 SIMPLE TIMER:

 

The simple timer can be used.

4

  TIMER MODE OFF:

 

The timer mode cannot be used.

*  When the use of clock setting is OFF, the “WEEKLY TIMER” 

cannot be used.

(4) Contact number setting for error situation

•  To switch the setting, press the [ ON/OFF] button 

D

.

1

 CALL OFF:

 

The set contact numbers are not displayed in case of error.

2

  CALL **** *** ****:

 

The set contact numbers are displayed in case of error.

   CALL_:
 

The contact number can be set when the display is as shown 
on the left.

•  Setting the contact numbers

  To set the contact numbers, follow the following procedures.
  Move the flashing cursor to set numbers. Press the [   TEMP. 

(

) and (

)] button 

F

 to move the cursor to the right (left). 

Press the [ CLOCK (

) and (

)] button 

C

 to set the 

numbers.

[4]–4. Display change setting

(1) Temperature display °C/°F setting

•  To switch the setting, press the [ ON/OFF] button 

D

.

1

  °C: 

The temperature unit °C is used.

2

  °F: 

The temperature unit °F is used.

(2) Suction air temperature display setting

•  To switch the setting, press the [ ON/OFF] button 

D

.

1

  ON: 

The suction air temperature is displayed.

2

  OFF: 

The suction air temperature is not displayed.

(3) Automatic cooling/heating display setting

•  To switch the setting, press the [ ON/OFF] button 

D

.

1

 ON: 

 

One of “Automatic cooling” and “Automatic heating” is 
displayed under the automatic mode is running.

2

 OFF:

 

Only “Automatic” is displayed under the automatic mode.

Summary of Contents for city multi PLFY-P-VCM-E2

Page 1: ...ire acondicionado para garantizar un uso seguro y correcto PARA EL USUARIO Español E ISTRUZIONI DI FUNZIONAMENTO Leggere attentamente questi istruzioni di funzionamento prima di avviare l unità per un uso corretto e sicuro della stessa PER L UTENTE Italiano I EΓXEIPIΔIO OΔHΓIΩN XPHΣEΩΣ Για ασφάλεια και σωστή χρήση παρακαλείστε διαβάσετε προσεχτικά αυτό το εγχειρίδιο χρήσεως πριν θέησετε σε λειτουρ...

Page 2: ...not splash water over the unit and do not touch the unit with wet hands An electric shock may result Do not spray combustible gas close to the unit Fire may result Do not place a gas heater or any other open flame appliance where it will be exposed to the air discharged from the unit Incomplete combustion may result Do not remove the front panel or the fan guard from the outdoor unit when it is ru...

Page 3: ...ng life Long life Filter cleaning indication 100 hr 2 500 hr 2 500 hr PLFY P VCM E2 4 way Ceiling Cassette Filter Air intake Vane Air outlet This operation is available only using the remote controller that is able to set its Fan speed setting Auto PCFY P VKM E Ceiling Suspended Air outlet Louver Vane Air intake Filter Inside of Air intake Emergency operation switch Front grille Filter Air inlet A...

Page 4: ...been locked Clean the filter indicator Comes on when it is time to clean the filter Timer indicators The indicator comes on if the corresponding timer is set For purposes of this explanation all parts of the display are shown as lit During actual operation only the relevant items will be lit Note PLEASE WAIT message This message is displayed for approximately 3 minutes when power is supplied to th...

Page 5: ...ller or subject it to strong shocks In addition do not get the remote controller wet or leave it in a location with high humidity To avoid misplacing the remote controller install the holder included with the remote controller on a wall and be sure to always place the remote controller in the holder after use For explanation purposes all of the items that appear in the display are shown All items ...

Page 6: ... Day button 9 to set the day Each press advances the day shown at 3 Sun Mon Fri Sat 3 Press the appropriate Set Time button 1 as necessary to set the time As you hold the button down the time at 4 will increment first in minute intervals then in ten minute intervals and then in one hour intervals 4 After making the appropriate settings at Steps 2 and 3 press the Filter button 4 to lock in the valu...

Page 7: ...l mode In the same way if the room temperature remains 1 5 C or more below the set temperature for 3 minutes the air conditioner switches to heat mode Because the room temperature is automatically adjusted in order to maintain a fixed effective temperature cooling operation is performed a few degrees warmer and heating operation is performed a few degrees cooler than the set room temperature once ...

Page 8: ...m is waiting for the operation mode change to take effect 3 In heat mode when room temperature is higher than the temperature setting Manual To Change the Airflow s Left Right Direction The louver button 7 cannot be used Model PKFY P VKM E Stop the unit operation hold the lever of the louver and adjust to the desired direction Do not set to the inside direction when the unit is in the cooling or d...

Page 9: ...Timer Menu button 2 so that the Set Up appears on the screen at 2 Note that each press of the button toggles the display between Set Up and Monitor 3 Press the Timer On Off Set Day button 9 to set the day Each press advances the display at 3 to the next setting in the following sequence Sun Mon Tues Wed Thurs Fri Sat Sun Fri Sat Sun Mon Tues Wed Thurs Fri Sat 4 Press the or operation button 7 or 8...

Page 10: ...e only The air conditioner starts when the set time has elapsed Stop time only The air conditioner stops when the set time has elapsed Start stop times The air conditioner starts and stops at the respective elapsed times The simple timer start and stop can be set only once within a 72 hour period The time setting is made in hour increments Note 1 Weekly Timer Simple Timer Auto Off Timer cannot be ...

Page 11: ...er button 4 8 Press the Operation mode Back button 2 to return to the standard control screen 9 Press the Timer On Off button 9 to start the timer countdown When the timer is running the timer value is visible on the display Be sure that the timer value is visible and appropriate Viewing the Current Simple Timer Settings 1 Be sure that the simple timer indicator is visible on the screen at 1 2 Pre...

Page 12: ...er mode to stop the unit will cancel the timers If the current time has not been set the timer operation cannot be used 7 Other Functions C C TIME SUN FUNCTION PAR 21MAA ON OFF FILTER CHECK OPERATION CLEAR TEST TEMP MENU BACK DAY MONITOR SET CLOCK ON OFF 4 1 1 Locking function indicator 7 1 Locking the Remote Controller Buttons Operation function limit controller If you wish you can lock the remot...

Page 13: ...two remote controllers are connected to one group one controller must be set to sub 2 Use of clock setting CLOCK Setting the use or non use of clock function 3 Timer function setting WEEKLY TIMER Setting the timer type 4 Contact number setting for error situation CALL Contact number display in case of error Setting the telephone number 4 Display change DISP MODE SETTING 1 Temperature display C F s...

Page 14: ... setting is not used Initial setting value Operation lock setting is except On Off button Operation lock setting is All buttons The automatic mode is displayed when the operation mode is selected Initial setting value The automatic mode is not displayed when the operation mode is selected The temperature range limit is not active Initial setting value The temperature range can be changed on cool d...

Page 15: ...imit setting press the button H The selected setting will flash and the temperature can be set Settable range Cool Dry mode Lower limit 19 C 30 C Upper limit 30 C 19 C Heat mode Lower limit 17 C 28 C Upper limit 28 C 17 C Automatic mode Lower limit 19 C 28 C Upper limit 28 C 19 C 8 Function Selection 4 3 Operation mode selection setting 1 Remote controller main sub setting To switch the setting pr...

Page 16: ...hinese French Japanese CHANGE LANGUAGE Function selection Operation function limit setting Use of automatic mode setting Temperature range limit setting Limit temperature cool day mode Limit temperature heat mode Limit temperature auto mode Operation mode selection Remote controller setting MAIN Remote controller setting SUB Use of clock setting Setting the day of the week and time Timer set Timer...

Page 17: ...d When the filter display goes off the cumulative time is reset FILTER indicates the cleaning period when the air conditioner was used under general indoor air conditions by criteria time Since the degree of dirtiness depends on the environmental conditions clean the filter accordingly The filter cleaning period cumulative time differs with the model This indication is not available for wireless r...

Page 18: ...ution Never use gasoline benzene thinner scouring powder or any type of non neutral detergent as these substances may damage the unit s case PKFY P VKM E 1 Using both hands pull both the bottom corners of the inlet grille to open the grille then lift the filter until it clicks at the stop position 2 Hold the knobs on the filter and pull the filter up then pull it out downward Located in two places...

Page 19: ...oor unit During cool mode water may form and drip from the cool pipes and joints During heat mode water may form and drip from the heat exchanger During defrosting mode water on the heat exchanger evaporates and water vapor may be emitted The operation indicator does not appear in the remote controller display Turn on the power switch will appear in the remote controller display The air conditione...

Page 20: ...nditioner Do not attempt to repair this equipment by yourself Turn off the power switch immediately and consult your dealer Be sure to provide the dealer with the model name Warm air blows from the indoor unit intermittently when heat mode is off or during fan mode When another indoor unit is operating in heat mode the control valve opens and closes occasionally to maintain stability in the air co...

Page 21: ...oise level Low Middle High dB 28 30 31 28 31 35 28 31 37 29 33 38 30 34 39 Model PCFY P40VKM E PCFY P63VKM E PCFY P100VKM E PCFY P125VKM E Power source Voltage V Frequency Hz N 220 230 240 50 220 60 Capacity Cooling Heating kW 4 5 5 0 7 1 8 0 11 2 12 5 14 0 16 0 Dimension Height mm 230 Dimension Width mm 960 1280 1600 Dimension Depth mm 680 Net weight kg 24 32 36 38 Fan Airflow volume Low Middle2 ...

Page 22: ...e be sure to put the contact address telephone number on this manual before handing it to the customer Printed in Thailand RG79Y571H01 HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN ...

Reviews: