20
→
Control modes
Control details
2. Fan
Remarks
2-3. Thermo OFF mode
When the thermoregulating function changes to OFF, the indoor fan operates in
[Extra
low].
2-4. Heat defrosting mode
The indoor fan stops.
No drain pump operation
However, when the control changes from COOL or DRY operation, the drain pump
operates for 3 minutes.
(1) Initial setting : OFF
→
HEAT···[last setting]
When changing the mode from exception of HEAT to HEAT operation
···[Downward
C]
(2) Vane position :
Horizontal
→
Downward A
→
Downward B
→
Downward C
→
Swing
(3) Restriction of vane position
The vane is horizontally fixed for the following modes.
(The setting by the remote controller is temporarily invalidated and vane control is
set by the unit controller.)
•
Thermo
OFF
• Hot adjust [Extra low] mode
• Heat defrost mode
3. Drain pump
4. Vane control
(Up/down vane
change)
From the preceding page