30
OPERATING PROCEDURE
PHOTOS&ILLUSTRATIONS
7. Removing the pipe temperature detection/liquid (TH22)
and pipe temperature detection/gas (TH23)
(1) Remove the panel. (Refer to
3
)
(2) Remove the drain pan. (Refer to
6
)
(3) Disconnect the liquid or gas from the holder.
(4) Remove the 3 screws fixed to the piping cover, and remove
the piping cover. (See Photo 9)
(5) Remove the 2 screws fixed to the control box cover, and
remove the control box cover.
Pipe temperature detection/liquid (TH22)
(6) Remove the connector (CN21) from the indoor controller
board, and disconnect the pipe temperature detection/Liquid.
Pipe temperature detection/gas (TH23)
(6) Remove the connector (CN29) from the indoor controller
board, and disconnect the pipe temperature detection/Gas
with its holder.
8. Removing the fan motor (MF)
(1) Remove the panel. (Refer to
3
)
(2) Remove the drain pan. (Refer to
6
)
(3) Remove the nut and the washer from the turbo fan, and
remove the turbo fan.
(4) Remove the 2 screws fixed to the control box cover, and
remove the control box cover.
(5) Disconnect the connectors of the (FAN) from the indoor
controller board.
(6) Remove the 3 screws fixed to the piping cover, and remove
the piping cover. (See photo 9)
(7) Remove the 6 screws fixed to the flat plate, and remove
the flat plate.
(8) Disconnect the lead wires to the direction of the fan motor,
and remove 3 nuts of the fan motor.
Photo 5
6. Removing the drain pan
(1) Remove the panel. (Refer to
3
)
(2) Remove the room temperature detection and the 2 lead
wires held with fastener; wireless controller board relay
connector (9P red) and panel relay connector (10P white).
(3) Remove the 4 screws fixed to the drain pan, and remove
the drain pan.
(4) Remove the fan guard. (Refer to
2
)
Photo 4
Control box
Thermistor
(Pipe temperature
detection/ Liquid)
(TH22)
Screw
Screw
Screw
Screw
Room
temperature
detection
(TH21)
Drain pan
Control box
Photo 6
Fan
motor
(MF)
Nuts
Flat plate
Screws
Lead
wires
Nut
Screws
Screws
5. Removing the room temperature detection (TH21)
(1) Remove the panel. (Refer to
3
)
(2) Pull out the room temperature detection from the drain pan.
(3) Remove the 2 screws fixed to the control box cover, and
remove the control box cover.
(4) Remove the connector (CN20) from the indoor controller
board, and disconnect the room temperature detection.
Fan guard
Drain plug
Connectors
Thermistor
(Pipe temperature
detection/ Gas)
(TH23)
LEV