22
23
8-2. HOW TO CHECK THE PARTS
Parts name
Check points
Disconnect the connector then measure the resistance with a tester.
(At the ambient temperature 10 to 30
:
)
Disconnect the connector then measure the valve resistance with a tester.
Measure the resistance between the terminals with a tester.
(At the ambient temperature 20 to 30
:
)
Measure the resistance between the terminals with a tester.
(At the ambient temperature 20 to 30
:
)
Measure the resistance after 3 minutes have passed since the power supply was intercepted.
(At the ambient temperature 0
to 60
:
)
Vane motor (MV)
Linear expansion
valve (LEV)
Drain pump (DP)
Drain sensor (DS)
Refer to the next page for the details.
Refer to Thermistor characteristic graph.
Thermistor (TH21)
(Room temperature
detection)
Thermistor (TH22)
(Pipe temperature
detection/ Liqid)
Thermistor (TH23)
(Pipe temperature
detection/ Gas)
1
3
Yellow
Relay
connector
Yellow
1
2
3
Normal
4.3 to 9.6 k
"
Abnormal
Open or short
Abnormal
Open or short
Normal
0.6 to 6.0k
"
Abnormal
Open or short
Normal
200
"
i
10%
White-Red Yellow-Brown Orange-Red Blue-Brown
Normal
Connector
Abnormal
300
"
Open or short
Normal
Abnormal
290
"
Open or short
Orange
Red
White
Blue
Brown
Yellow
M
Orange
Red
White
Red — Yellow
Red — Blue
Red — Orange
Red — White
Blue
Yellow
M
Refer to the next
page for the details.
PLFY-P15VCM-E3.TH
PLFY-P20VCM-E3.TH
PLFY-P25VCM-E3.TH
PLFY-P32VCM-E3.TH PLFY-P40VCM-E3.TH
OCH569