8-4. TEST POINT DIAGRAM
Indoor controller board
LED1
Main power supply
(Indoor unit : 220-240V)
CND
Power supply for
indoor controller board
Between
1
to
3
220-240V AC
CNP
Drain pump output (DP)
Between
1
to
3
220-240V AC
F1
6.3A 250V
CNMF
Fan motor output (MF)
CN2M
Connect to the terminal block (TB5)
(M-NET transmission connecting wire)
24-30V DC (non-polar)
CN3A
Connect to the terminal block
(TB15)
(MA-Remote controller con-
necting wire)
Between
1
to
3
8.7-13V DC
(Pin
1
(+))
CN29
Pipe temperature
detection/Gas (TH23)
SW4
Model selection
SW3
Function setting
SW2
Capacity setting
CN52
Remote indicator
1
-
2
: Status lamp 12VDC (
1
: +)
Fan motor output (SW1-5 OFF)
Thermostat ON (SW1-5 ON)
1
-
3
: Cooling/Dry status lamp
12VDC (
1
: +)
1
-
4
: Heating status lamp
12VDC (
1
: +)
When only demand input is used
1
-
5
: Demand input
ON/OFF input (
1
: +)
CN6V
Vane motor output (MV)
CN32
Connector
(Remote switch)
CN25
Connecter
(Humidifier)
CN27
Connector (Damper)
12VDC
(
1
: +)
SW14
Branch No.
CN90
Connect to the wireless
junction cable
SW1
Model selection
Jumper wire J41, J42
Pair No. setting for
wireless remote controller
CN51
Centrally control
1
-
2
: Control signal
12VDC pulse input (
1
: +)
3
-
4
: Operation indicator
12VDC (
3
: +)
3
-
5
: Malfunction indicator
12VDC (
3
: +)
Note:
The voltage range of DC12V in this page is between DC11.5 V to DC13.7 V.
CNC
Dew prevention
heater (H2)
(220~240V AC)
PLFY-P15VCM-E3.TH
PLFY-P20VCM-E3.TH
PLFY-P25VCM-E3.TH
PLFY-P32VCM-E3.TH PLFY-P40VCM-E3.TH
CN60
Linear expansion valve
output (LEV)
CN20
Room temperature
detection (TH21)
CN21
Pipe temperature
detection/Liquid (TH22)
CN31
Drain sensor (DS)
SW12
Address setting 10ths DIGIT
SW11
Address setting 1s DIGIT
LED2
Power supply for
MA-Remote controller
OCH569