8-4. TEST POINT DIAGRAM
8-4-1. Indoor controller board
PMFY-P20VBM-E PMFY-P25VBM-E PMFY-P32VBM-E PMFY-P40VBM-E
PMFY-P20VBM-E
1
PMFY-P25VBM-E
1
PMFY-P32VBM-E
1
PMFY-P40VBM-E
1
LED1
Main power supply
(Indoor unit : 220-240V)
CND
Power supply for
indoor controller board
Between
1
to
3
220-240V AC
CNP
Drain pump
output (DP)
Between
1
to
3
220-240V AC
FUSE
6.3A 250V
FAN
Fan motor output (MF)
CN2M
Connect to the terminal block (TB5)
(M-NET transmission connecting wire)
24-30V DC (non-polar)
CN3A
Connect to the terminal block (TB15)
(MA-Remote controller connecting wire)
Between
1
to
3
8.7-13V DC (Pin
1
(+))
CN29
Pipe temperature
thermistor/Gas (TH23)
CN21
Pipe temperature
thermistor/Liquid (TH22)
LED2
Power supply for
MA-Remote controller
CN60
Linear expansion valve
output (LEV)
CN31
Drain sensor (DS)
CN20
Room temperature
thermistor (TH21)
CN41
Connector
(HA terminal-A)
CN6V
Vane motor output
(MV)
CN32
Connector
(Remote switch)
SW4
Model selection
SW3
Mode selection
SW2
Capacity setting
CN25
Humidifier
CN27
Damper
CN51
Centrally control
1
-
2
: Control signal
12VDC pulse input (
1
: +)
3
-
4
: Operation indicator
12VDC (
3
: +)
3
-
5
: Malfunction indicator
12VDC (
3
: +)
CN52
Remote indicator
1
-
2
: Status lamp 12VDC (
1
: +)
Fan motor output (SW1-5 OFF)
Thermostat ON (SW1-5 ON)
1
-
3
: Cooling/Dry status lamp
12VDC (
1
: +)
1
-
4
: Heating status lamp
12VDC (
1
: +)
OC307E