Restriction on installing the 2-Branch Joint Pipe CMY-R101/102S-G on the low-pressure piping
- Regarding the 2-Branch Joint Pipe on the low-pressure piping, A and B must be installed horizontally, and C must
be installed upward higher than the horizontal plane of A and B.
・
Restriction on installing the 2-Branch Joint Pipe CMY-R201/202/203/204/205S-G on the high-pressure piping, low-
pressure piping, and liquid piping.
- Regarding the 2-Branch Joint Pipe on the high-pressure/low-pressure/liquid piping, A and B must be installed
horizontally, and C must be installed upward higher than the horizontal plane of A and B.
・
If the length of the pipe between the branching point and the outdoor unit exceeds 2 m (6 ft), provide a trap within 2
m (6 ft) from the branching point.
The trap must be at least 200 mm (7-7/8 in) in height. (gas pipe only) If there is no trap, oil can accumulate inside
the pipe, causing a shortage of oil and may damage the compressor.
* Small dots in the figures indicate branching points.
Ⓐ
Ⓒ
Ⓑ
Ⓐ
Ⓐ
To indoor units
Ⓑ
Trap (high-pressure pipe only)
Ⓒ
High-pressure pipe
To outdoor unit
To main BC controller
A
B
C
To sub BC controller
To main BC controller
To sub BC controller
A
B
C
To sub BC controller
2 m (6 ft)