GB-36
WT08432X01
(1) Units "m" and "kg" (In an R2 system)
<Formula>
・
When the piping length from the outdoor unit to the farthest indoor unit is 30.5 m (100 ft) or shorter
Amount of
additional
charge (kg)
=
High-pressure pipe
ø34.93 total length
× 0.58 (kg/m)
+
High-pressure pipe
ø28.58 total length
× 0.36 (kg/m)
+
High-pressure pipe
ø22.2 total length
× 0.23 (kg/m)
+
High-pressure pipe
ø19.05 total length
× 0.16 (kg/m)
+
High-pressure pipe
ø15.88 total length
× 0.11 (kg/m)
+
Liquid pipe ø19.05
total length
× 0.29 (kg/m)
+
Liquid pipe ø15.88
total length
× 0.2 (kg/m)
+
Liquid pipe ø12.7
total length
× 0.12 (kg/m)
+
Liquid pipe ø9.52
total length
× 0.06 (kg/m)
+
Liquid pipe ø6.35
total length
× 0.024 (kg/m)
+
Main or sub BC
controller
Amount (kg/unit)
+
Total capacity of connected
indoor units
Amount (kg)
(to be added for
indoor unit)
J-type
1.5
80 or below
2.0
JA-type
3.0
81 to 160
2.5
KA-type
4.7
161 to 330
3.0
KB-type
0.4
331 to 390
3.5
391 to 480
4.5
481 to 630
5.0
631 to 710
6.0
711 to 800
8.0
801 to 890
9.0
891 to 1070
10.0
1071 to 1250
12.0
1251 or above
14.0
* When connecting PEFY-P50VMHS2-E, add 2.81 kg of refrigerant per indoor unit.
* When connecting PEFY-P63VMHS2-E, add 3.27 kg of refrigerant per indoor unit.
* When connecting PEFY-P71VMHS2-E, add 2.50 kg of refrigerant per indoor unit.
* When connecting PEFY-P80VMHS2-E, add 2.50 kg of refrigerant per indoor unit.
* When connecting PEFY-P100VMHS2-E, add 2.50 kg of refrigerant per indoor unit.
* Contact your dealer for the amount of refrigerant to be added when connecting CMB-P**-V-G1, CMB-P**-V-GA1, CMB-P**-V-HA1, CMB-P**-
V-GB1, or CMB-P**-V-HB1.
* When connecting LEV kit (PAC-LV11M-J), additional refrigerant charge may be required. Contact your dealer for details.
・
When the piping length from the outdoor unit to the farthest indoor unit is longer than 30.5 m (100 ft)
Amount of
additional
charge (kg)
=
High-pressure pipe
ø34.93 total length
× 0.52 (kg/m)
+
High-pressure pipe
ø28.58 total length
× 0.33 (kg/m)
+
High-pressure pipe
ø22.2 total length
× 0.21 (kg/m)
+
High-pressure pipe
ø19.05 total length
× 0.14 (kg/m)
+
High-pressure pipe
ø15.88 total length
× 0.1 (kg/m)
+
Liquid pipe ø19.05
total length
× 0.26 (kg/m)
+
Liquid pipe ø15.88
total length
× 0.18 (kg/m)
+
Liquid pipe ø12.7
total length
× 0.11 (kg/m)
+
Liquid pipe ø9.52
total length
× 0.054 (kg/m)
+
Liquid pipe ø6.35
total length
× 0.021 (kg/m)
+
Main or sub BC
controller
Amount (kg/unit)
+
Total capacity of connected
indoor units
Amount (kg)
(to be added for
indoor unit)
J-type
1.5
80 or below
2.0
JA-type
3.0
81 to 160
2.5
KA-type
4.7
161 to 330
3.0
KB-type
0.4
331 to 390
3.5
391 to 480
4.5
481 to 630
5.0
631 to 710
6.0
711 to 800
8.0
801 to 890
9.0
891 to 1070
10.0
1071 to 1250
12.0
1251 or above
14.0
* When connecting PEFY-P50VMHS2-E, add 2.81 kg of refrigerant per indoor unit.
* When connecting PEFY-P63VMHS2-E, add 3.27 kg of refrigerant per indoor unit.
* When connecting PEFY-P71VMHS2-E, add 2.50 kg of refrigerant per indoor unit.
* When connecting PEFY-P80VMHS2-E, add 2.50 kg of refrigerant per indoor unit.
* When connecting PEFY-P100VMHS2-E, add 2.50 kg of refrigerant per indoor unit.
* Contact your dealer for the amount of refrigerant to be added when connecting CMB-P**-V-G1, CMB-P**-V-GA1, CMB-P**-V-HA1, CMB-P**-
V-GB1, or CMB-P**-V-HB1.
* When connecting LEV kit (PAC-LV11M-J), additional refrigerant charge may be required. Contact your dealer for details.