Four levels of external static pressure settings
While the conventional models only had three levels of external static pressure, the latest models offer four levels of external static
pressure. The additional external static pressure capacity provides flexibility for duct extension, branching and air outlet configuration.
Drain pumps (sold separately)
with a DC motor are now also available.
P40
PEFY-P VMH(S)
PEFY-P VMHS
P50
P63
P71
AC motor
DC motor
DC motor
P80 P100 P125 P140 P200 P250
0
10
20
30
40
50
60
70
80
P40
P50
P63
P71
P80 P100 P125 P140
42
42
43
57
57
66
66
68
35
35
35
45
45
51
51
53
VMHS (kg)
• Weight comparison
Conventional model (kg)
Three fan speeds (Low/Mid/High) to choose from
External static pressure (Pa)
P40
220 V
230, 240 V
220-240 V
PEFY-P VMH
PEFY-P VMHS
P50 P63 P71
<50>-100-<200>
<100>-150-<200>
50-<100>-<150>-<200>
P80 P100 P125 P140
Four levels of
external pressure
settings
Reduced weight
By downsizing the motor, the unit weight has been reduced,
offering easier installation.
The use of a high-efficiency DC motor for the drain pump motor in
the latest models reduces power consumption by 90%, in
comparison to conventional models. The pump head height of
550 mm provides for greater piping design flexibility.
The use of a DC motor
In the past, the only models featuring a DC motor were the P200 (8 HP) and P250 (10 HP). Now, the P140 (6 HP) and smaller models
feature a DC motor that consumes less power compared to AC motors. In the P80 models, power consumption is reduced by 59%*.
*Comparison made at 50 Hz, 220 V, 100 Pa low fan speed
The conventional models had two levels of fan speed, but the latest models offer three levels (Low/Mid/High). Combined with a wider
selection of external static pressure levels, the latest models offer optimal operation settings to suit the air-conditioning load of the
installation space.
The factory setting of external static pressure is shown without brackets (< >).
Refer to "Fan characteristics curves" according to the external static pressure, in the DATA BOOK for
the usable range of airflow rate.
P
1
40 (6 HP) and
smaller models with a DC motor
140
Summary of Contents for City Multi R2 Series
Page 1: ...CM20AN E NZ VRF City Multi Product Catalogue ...
Page 101: ...BC Controllers 101 ...
Page 112: ...Indoor Units VRF 112 ...
Page 114: ...Ceiling Cassette Type 4 Way Airflow Type 114 ...
Page 122: ...Ceiling Cassette Type 2 Way Airflow Type 122 ...
Page 128: ...Ceiling Concealed Type 128 ...
Page 150: ...Wall Mounted Type 150 ...
Page 154: ...Floor Standing Type 154 ...
Page 181: ...Ventilation Systems 181 ...
Page 190: ...Remote Controllers 190 ...