PAC-AH-M-J
The Air Handling Unit Controller is an interface to allow
connection to third party manufacturers equipment.
Mitsubishi Electric City Multi outdoor units are used with
this interface box, creating an ideal solution when a
unique air handling unit is required. The Air Handling Unit
Controllers are supplied with LEV expansion device(s).
•
Discharge or return air temperature control
•
Temperature set point by control 0-10VDC
•
Auto mode available for ease of application
•
Error input
•
IP2x rated (only for internal use)
PAC-AH-M-J - AHU Controller
MODEL REFERENCE
PAC-AH125M-J PAC-AH125M-J PAC-AH140M-J PAC-AH250M-J PAC-AH250M-J PAC-AH500M-J PAC-AH500M-J
AIR HANDLING UNIT SIZE
P100
P125
P140
P200
P250
P400*
2
P500*
2
ALLOWED HEAT EXCHANGER CAPACITY
(KW) - HEATING (MIN/MAX)
10.0 - 12.5
12.5 - 16.0
16.0 - 18.0
18.0 - 25.0
25.0 - 31.5
40.0 - 50.0
50.0 - 63.0
ALLOWED HEAT EXCHANGER CAPACITY
(KW) - COOLING (MIN/MAX)
9.0 - 11.2
11.2 - 14.0
14.0 - 16.0
16.0 - 22.4
22.4 - 28.0
36.0 - 45.0
45.0 - 56.0
ALLOWED HEAT EXCHANGER VOLUME
(CM
3
)
1500 - 2850 1900 - 3550 2150 - 4050 3000 - 5700 3750 - 7100 6000 - 11400 7500 - 14200
REFERENCE AIR FLOW RATE (M3/H)*
3
2000
2500
3000
4000
5000
8000
10000
STANDARD EVAPORATOR
PATH NUMBER*
1
4 - 5
4 - 5
5 - 6
6 - 10
8 - 10
16 - 20
16 - 20
DIMENSIONS (MM)
( ) = INC MOUNTINGS
WIDTH
DEPTH
HEIGHT
328
104 (122)
378 (420)
328
104 (122)
378 (420)
328
104 (122)
378 (420)
328
104 (122)
378 (420)
328
104 (122)
378 (420)
328
104 (122)
378 (420)
328
104 (122)
378 (420)
WEIGHT (KG)
5
5
5
5
5
5
5
PIPE SIZE (MM)
GAS
LIQUID
15.88
9.52
15.88
9.52
15.88
9.52
19.05
9.52
22.22
9.52
28.58
12.7
28.58
15.88
Note: One air handling unit controller is required per air handling unit. Saturated refrigerant temperature at exit of evaporator
= 8.5ºC, SH = 5K, liquid temperature = 25ºC, air = 27ºCDB/19ºCWB.
*1 When the diameter of the heat exchanger tube is ø9.52.
*2 P400 and P500 are not compatible with PURY and PQRY.
*3 If using in combination with standard indoor units, then these figures do not apply.
APPLICABLE OUTDOOR UNITS
PUHY-P Y(S)NW-A
PUHY-EP Y(S)NW-A
PUHY-HP Y(S)HM-A
PQHY-P Y(S)LM-A
PURY-P Y(S)NW-A
PURY-EP Y(S)NW-A
PQRY-P Y(S)LM-A
Mitsubishi Electric
Air Handling Unit Controller
Mitsubishi Electric
Outdoor Unit
Air Handling Unit
(Field supplied)
Controller (Field supplied)
Example:
220-240v, 50Hz
Power supply
M-Net wiring
Thermistor wiring
Piping
Summary of Contents for City Multi R2 Series
Page 1: ...CM20AN E NZ VRF City Multi Product Catalogue ...
Page 101: ...BC Controllers 101 ...
Page 112: ...Indoor Units VRF 112 ...
Page 114: ...Ceiling Cassette Type 4 Way Airflow Type 114 ...
Page 122: ...Ceiling Cassette Type 2 Way Airflow Type 122 ...
Page 128: ...Ceiling Concealed Type 128 ...
Page 150: ...Wall Mounted Type 150 ...
Page 154: ...Floor Standing Type 154 ...
Page 181: ...Ventilation Systems 181 ...
Page 190: ...Remote Controllers 190 ...