Outdoor Twinning Kit Installation Manual

CMY-Y100VBK2, Y200VBK2, Y300VBK2

• For safe and correct use, please read this installation manual thoroughly before installation.

For your safety, follow the instructions with  

 WARNING and  

 CAUTION symbols.

Safety Precautions

• Before installing the unit, make sure you read all the “Safety precautions”.
• These precautions provide very important points regarding safety. Make sure you follow them.
• The following symbols are intended to alert the presence of danger in case of miss-operation.

Ask the dealer or an authorized technician to install
the unit.

• Improper installation may result in problems such as gas

leakage.

Do not modify the unit in any way. Ask your dealer to
repair the air conditioner.

• Improper installation by the user may result in water leakage,

electric shock, or fire.

If refrigerant gas leaks during installation work,
ventilate the room.

• If the refrigerant gas comes into contact with a flame, poisonous

gases will be released.

Install the unit according to this Installation Manual.

• Select appropriate twinning types and sizes of connecting pipes.

If inappropriate types or sizes are connected, the air condition-
ing system cannot deliver the expected performance.

When installing or moving the unit, make sure that
the specified refrigerant (R410A only) is charged into
the refrigerant circuit.

• Any presence of foreign substance or even air can cause

abnormal pressure rise or explosion.

After the installation is completed, make sure that the
refrigerant gas is not leaking.

• If the refrigerant gas leaks into the room, and it is exposed to a

fan heater, space heater, kitchen range, or some other heat
source, it may generate a noxious gas.

Safely dispose of the packing materials.

• Tear up and throw away any plastic packaging bags so that

children will not play with them. If children play with a plastic
bag which has not been torn apart, they run the risk of
suffocation.

Do not touch the refrigerant pipes during and
immediately after operation.

• During and immediately after the operation, the parts of the

refrigerant circuit including the refrigerant piping or the
compressor may be hot or cold, depending on the condition of
the flowing refrigerant. To prevent the risk of frostbite or burns,
do not touch these parts with bare hands.

1. Confirming the Supplied Parts

The twinning kit box (CMY-Y100VBK2, CMY-Y200VBK2, and CMY-Y300VBK2) contains the
following twinning and accessory piping parts. Make sure that the kit contains all of these
parts.
After checking, prepare the twinning kit by connecting the twinning pipes b, c, and d to the
twinning pipe a.
*Always use the twinning pipes included in the kit when preparing the twinning kit.
Depending on the model type, the size of the field piping may be different from the pipe size
of the twinning kit. In such a case, connect the following accessory piping parts to the kit.

(1) Twinning pipes

* For general instructions on the installation of an outdoor unit, follow the Installation Manual for the outdoor unit.

CAUTION

Twinning a

Insulation cover

Twinning kit

Pipe b (Before the twinning)

Pipe c (After the twinning)

L-shape pipe d (After the twinning)

Twinning kit

L-shape pipe d (After the twinning)

Insulation cover

Twinning a

Pipe b (Before the twinning)

Pipe c (After the twinning)

Model

CMY-Y100VBK2

CMY-Y200VBK2

CMY-Y300VBK2

Section

Liquid

Gas

Liquid

Gas

Liquid

Second row

Liquid

First row

Gas

Second row

Gas

First row

Lebel

A

D

C

B

A (Red)

C (Red)

D (Red)

B (Red)

Twinning a

15.88

×

12.7

×

12.7

28.58

×

25.4

×

25.4

19.05

×

15.88

×

15.88

31.75

×

28.58

×

28.58

15.88

×

12.7

×

12.7

19.05

×

15.88

×

15.88

28.58

×

25.4

×

25.4

31.75

×

28.58

×

28.58

Pipe b (Before the twinning)

OD15.88-ID15.88

L83

OD28.58-ID28.58

L342

OD19.05-ID19.05

L85

OD31.75-ID34.93

L337

OD15.88-ID19.05

L85

OD19.05-ID19.05

L85

OD28.58-ID34.93

L337

OD31.75-ID38.1

L339

Pipe c (After the twinning)

OD12.7-ID12.7

L128

OD25.4-ID22.2

L190

OD15.88-ID15.88

L123

OD28.58-ID28.58

L192

OD12.7-ID12.7

L128

OD15.88-ID19.05

L125

OD25.4-ID28.58

L192

OD28.58-ID34.93

L187

L-shape pipe d (After the twinning)

OD12.7-ID12.7

OD25.4-ID22.2

OD15.88-ID15.88

OD28.58-ID28.58

OD12.7-ID12.7

OD15.88-ID15.88

OD25.4-ID28.58

OD28.58-ID28.58

Insulation cover

Small

Large

Small

Large

Small

Small

Large

Large

Instruction

1

(This sheet)

(2) Accessory piping parts

(3) Field supplied parts

• Field supplied parts that do not come with the twinning kit
• Heat-resistant insulation material (for field piping)
• Insulation cover fixing tape

2. Selecting the Size of the Refrigerant Pipe and How to Use the Twinning Kit

(1) PUHY-P500 – P900, EP400 – EP650

(Outdoor unit 

×

 2)

1

Prepare the pipe to be connected in the field.

2

Select the pipe size for each part from the table below. A (*)
mark after a pipe size indicates that the specified pipe size in
the following table can be obtained by connecting the acces-
sory piping to the twinning kit.

3

Cut the pipe with a pipe cutter and remove the burr. Connect
the pipe after removing any dust or foreign matter.

PUHY-P500 – P900

(2) PUHY-P950 – P1250, EP700 – EP900

(Outdoor unit 

×

 3)

1

Prepare the pipe to be connected in the field.

2

Select the pipe size for each part from the
table below. A (*) mark after a pipe size
indicates that the specified pipe size in the
following table can be obtained by connecting
the accessory piping to the twinning kit.

3

Cut the pipe with a pipe cutter and remove the
burr. Connect the pipe after removing any dust
or foreign matter.

PUHY-EP400 – EP650

Outdoor unit 2

Outdoor unit 1

Outdoor unit 3

To Indoor unit

To Indoor unit

b

a

d

c

j

i

g

h

e

f

Liquid 1 twinning pipe

Liquid 2 twinning pipe

Gas 1 twinning pipe

Gas 2 twinning pipe

Outdoor unit 3

Outdoor unit 1

Outdoor unit 2

To Indoor unit

To Indoor unit

Liquid 1 twinning

pipe

Gas 1 twinning pipe

a

b

c

d

e

f

g

h

Liquid 2 twinning pipe

Gas 2 twinning pipe

i

j

(5) The piping connection

When connecting the twinning kit to the outdoor unit, note the following:

· If the length of piping from the twinning kit to the outdoor unit is more than 2 m (6 ft), install a trap within 2 m (6 ft) from

the outdoor unit.
The height of the trap must be 200 mm (7 inch) or higher.

PUHY-P950 – P1250

(3) The angle of tilt of the twinning pipe

The angle of tilt of the twinning pipe should be within 

±

15

°

 with the

ground.
Tilting the twinning pipe more than specified will cause damage to the
unit.

(4) The length of the straight part of the pipe before the twinning

For the twinning kit, always use the accessory piping parts. The length
of the straight part of pipe connected in front of the twinning pipe must
be 500 mm (19 inch) or longer. (Connect the field piping so that the
length of the straight part of pipe connected in front of the twinning pipe
can be 500 mm (19 inch) or longer.)
If the length is less than 500 mm (19 inch), it will cause damage to the
unit.

<2 m (6 ft) or less>

<More than 2 m (6 ft)>

· When installing the twinning kit in a higher

position than the outdoor unit base, make sure
that the twinning kit is installed in a position
lower than 200 mm (7 inch) from the outdoor
unit base.

To Indoor unit

2 m (6 ft)

2 m (6 ft)

To Indoor unit

PUHY-EP700 – EP900

Less than
2 m (6 ft)

To Indoor unit

200 mm (7 inch)
or over

Less than
2 m (6 ft)

To Indoor unit

200 mm (7 inch)
or over

Reducer

±

15

°

The angle of tilt of the reducer should be within 

±

15

°

 with the ground.

Note: See the following drawing for the fitting position 

of the twinning pipe.

Note: See the following drawing for the fitting position

of the twinning pipe.

The angle of tilt of the reducer should be within

±

15

°

 with the ground.

Reducer

±

15

°

3. Example of a Pipe Connection

See the following drawing for connecting the pipes between the outdoor units.

<For 2 outdoor units>

<For 3 outdoor units>

4. Installing the Insulation Cover

After brazing the pipes and the twinning kit, insulate the twinning kit with the insulation cover.
Add insulation materials on all the refrigerant piping, including the field piping. Make sure to insulate the pipes for liquid and gas
separately. When using commercially available insulation material, make sure to use heat-resistant insulation material with heat-
resistant temperature of 120 

°

C or higher.

Align the edges of the insulation cover and the heat-resistant insulation material so that there will be no gap. Seal also the periphery
and centre of the twinning part with a tape (field supply).

Tape (field supply)

Lapped space of taping

Insulation cover

Insulation material
(field supply)

As the insulation cover 
contracts slightly, conduct 
taping in the field securely by 
providing lapped parts as 
shown in the left, so that no gap 
will exist on the insulation cover 
and field supply insulation 
material.

Tape (field supply)

Insulation cover

Insulation material
(field supply)

Lapped space of taping

The insulation cover
shrinks slightly, so wrap the
insulation cover and the
field-installed insulation
material securely with tape
by overlapping the tape as
shown left.

Field piping

Field piping

Insulation material (field supply)

Insulation material 
(field supply)

Field piping

Twinning kit

Insulation cover

Tape (field supply)

Tape (field supply)

Twinning kit

Field piping

Insulation material (field supply)

Field piping

Insulation cover

Field piping

Insulation material
(field supply)

Tape (field supply)

Tape (field supply)

Field piping

Field piping

Twinning kit

The length of the straight pipe must 
be 500 mm (19 inch) or longer. 

Field piping

Twinning kit

The length of the straight pipe must be
500 mm (19 inch) or longer.

Field piping

Field piping

Field piping

Twinning kit

Field piping

Twinning kit

The length of the straight pipe must 
be 500 mm (19 inch) or longer. 

The length of the straight pipe must 
be 500 mm (19 inch) or longer. 

Field piping

Twinning kit

The length of the straight pipe must
be 500 mm (19 inch) or longer.

Field piping

Twinning kit

Field piping

The length of the straight pipe must
be 500 mm (19 inch) or longer.

Outoor unit 2

Outoor unit 1

Outoor unit 3

Twinning 1

Less than
200 mm
(7 inch)

Twinning 2

To Indoor unit

To Indoor
unit

Less than
200 mm (7 inch)

Twinning 1

Twinning 2

Outdoor unit 1

Outdoor unit 2

Outdoor unit 3

WT05134X01

Model

CMY-Y100VBK2

CMY-Y200VBK2

CMY-Y300VBK2

Section

Liquid

Gas

Liquid

Gas

Liquid

Gas

OD12.7-ID9.52 (2)

OD22.2-ID28.58

OD15.88-ID12.7 (2)

OD34.93-ID41.28

OD12.7-ID9.52

OD28.58-ID22.2 (3)

OD15.88-ID12.7

OD22.2-ID19.05 (2)

OD12.7-ID15.88 (2)

OD38.1-ID41.28 (1)

OD15.88-ID9.52

OD28.58-ID19.05 (2)

OD15.88-ID12.7

OD38.1-ID34.93

Supplied pipe

Outdoor unit 2

Outdoor unit 1

To Indoor unit

f

e

d

c

b

a

Liquid twinning pipe 

Gas twinning pipe

To Indoor unit

Outdoor unit 1

Outdoor unit 2

To Indoor unit

To Indoor unit

Liquid twinning pipe

Gas twinning pipe

a

b

c

d

e

f

This symbol indicates that failure to follow the instructions exactly as stated poses the risk of serious injury or death.

This symbol indicates that failure to follow the instructions exactly as stated poses the risk of injury or damage to the
unit and other property.

WARNING

CAUTION

Set Unit

Liquid

Gas

a

b

Indoor – Twinning

Twinning Type

Set model

Unit 1

Unit 2

PUHY-P500

PUHY-P250

PUHY-P250

PUHY-P550

PUHY-P300

PUHY-P250

PUHY-P600

PUHY-P350

PUHY-P250

PUHY-P650

PUHY-P350

PUHY-P300

PUHY-P700

PUHY-P350

PUHY-P350

PUHY-P750

PUHY-P400

PUHY-P350

PUHY-P800

PUHY-P450

PUHY-P350

PUHY-P850

PUHY-P450

PUHY-P400

PUHY-P900

PUHY-P450

PUHY-P450

CMY-Y100VBK2

ø15.88

ø28.58

CMY-Y200VBK2

ø19.05

ø41.28 (*)

ø34.93

Set Unit

Liquid

Gas

a

b

Indoor unit -

Twinning pipe

Outdoor Twinning Kit (optional parts)

Set model

Outdoor unit 1

Outdoor unit 2

PUHY-EP400

PUHY-EP200

PUHY-EP200

PUHY-EP450

PUHY-P250

PUHY-EP200

PUHY-EP500

PUHY-EP300

PUHY-EP200

PUHY-EP550

PUHY-EP300

PUHY-P250

PUHY-EP650

PUHY-P350

PUHY-EP300

CMY-Y100VBK2

PUHY-EP600

PUHY-EP300

PUHY-EP300

ø15.88

ø28.58

Set Unit

Liquid

Gas

Liquid

Gas

a

b

c

d

Indoor – Twinning 2

Twinning 1 – Twinning 2

Twinning Type

Set model

Unit 1

Unit 2

Unit 3

CMY-Y300VBK2

ø19.05

ø41.28 (*)

ø19.05

ø34.93

PUHY-P950

PUHY-P400

PUHY-P300

PUHY-P250

PUHY-P1000

PUHY-P400

PUHY-P300

PUHY-P300

PUHY-P1050

PUHY-P400

PUHY-P350

PUHY-P300

PUHY-P1100

PUHY-P400

PUHY-P350

PUHY-P350

PUHY-P1150

PUHY-P450

PUHY-P350

PUHY-P350

PUHY-P1200

PUHY-P450

PUHY-P400

PUHY-P350

PUHY-P1250

PUHY-P450

PUHY-P450

PUHY-P350

Unit model

P250

P300

P350

P400

P450

EP200

EP300

Liquid

c or e

ø9.52 (*)

ø12.7

ø12.7 (*)

ø15.88

ø15.88

ø9.52

ø12.7

Gas

d or f

ø22.2

ø22.2

ø28.58

ø28.58

ø28.58

ø19.05

ø22.2

Twinning pipe - Outdoor unit

Set Unit

Outdoor Twinning Kit (optional parts)

Set model

Unit 1

Unit 2

Unit 3

ø19.05

ø34.93

Liquid

Gas

Liquid

Gas

a

b

c

d

CMY-Y300VBK2

PUHY-EP700

PUHY-EP300

PUHY-EP200

PUHY-EP200

PUHY-EP750

PUHY-EP300

PUHY-P250

PUHY-EP200

PUHY-EP800

PUHY-EP300

PUHY-EP300

PUHY-EP200

PUHY-EP850

PUHY-EP300

PUHY-EP300

PUHY-P250

PUHY-EP900

PUHY-EP300

PUHY-EP300

PUHY-EP300

ø41.28

ø34.93

ø19.05

Indoor unit -

Twinning pipe 2

Twinning pipe 1 –

Twinning pipe 2

Unit model

P250

P300

P350

P400

P450

EP200

EP300

Liquid

e or g or i

ø9.52 (*)

ø12.7

ø12.7 (*)

ø15.88

ø15.88

ø9.52

ø12.7

Gas

f or h or j

ø22.2

ø22.2

ø28.58

ø28.58

ø28.58

ø19.05

ø22.2

Twinning pipe - Outdoor unit