7. Connections of Operation Panel I/O Unit
7.9 Connecting with Machine Operation Panel
90
Input conditions
The input signals must be used within the following condition ranges.
Sink type
Source type
1 Input voltage at external contact ON
6V or less
18V or more, 25.2V or less
2 Input current at external contact ON
9mA or more
3 Input voltage at external contact OFF
20V or more, 25.2V or less
4V or less
4 Input current at external contact OFF
2mA or less
5 Tolerable chattering time
3ms or less (Refer to T1 below)
6 Input signal holding time
40ms or more (Refer to T2 below)
7 Input circuit operation delay time
3ms
≤
T3
T4
≤
16ms
8 Machine side contact capacity
30V or more, 16mA or more
(Note)
Input signal holding time: 40ms or more as a guideline. The input signal can only be confirmed if held
longer than the ladder process cycle time.
T1 T1
T1
T1
T2
T2
T4 T4
T3
T3