GCH15010
26
Note
Request codes 103 to 105 indicate error histories of both indoor and outdoor units.
As only four digits can be displayed at one time the software version number is displayed in two halves.
For example software version No. 5.01 A000, when code 190 is entered 0501 is displayed, when code 191 is entered A000 is displayed.
<Table 9-4-1>
Request
code
Request content
Range
Unit
154
Water circulation pump 1 - Accumulated operating time (after reset)
0 - 9999
10 hours
158
Water circulation pump A - Accumulated operating time (after reset)
0 - 9999
10 hours
162
Indoor unit - DIP SW1 setting information
Refer to detail contents described hereinafter.
—
163
Indoor unit - DIP SW2 setting information
Refer to detail contents described hereinafter.
—
164
Indoor unit - DIP SW3 setting information
Refer to detail contents described hereinafter.
—
165
Indoor unit - DIP SW4 setting information
Refer to detail contents described hereinafter.
—
166
Indoor unit - DIP SW5 setting information
Refer to detail contents described hereinafter.
—
175
Indoor unit - Output signal information
Refer to detail contents described hereinafter.
—
176
Indoor unit - Input signal information
Refer to detail contents described hereinafter.
—
190
Indoor unit - Software version 1st 4 digits
Refer to Note below.
—
191
Indoor unit - Software version last 4 digits
Refer to Note below.
—
340
Water circulation pump 1 - Accumulated operating time reset
—
—
344
Water circulation pump A - Accumulated operating time reset
—
—
504
Indoor unit - Zone 1 room temp. (TH1A)
–39 - 88
°C
506
Indoor unit - Return water temp. (THW2)
–39 - 110
°C
507
Indoor unit - Zone 2 room temp. (TH1B)
–39 - 88
°C
508
Indoor unit - Stored water temp. (lower)(THW5B)
–39 - 110
°C
510
Indoor unit - Outside air temp. (TH7)
–39 - 88
°C
511
Indoor unit - Flow water temp. (THW1)
–39 - 110
°C
540
Flow rate for space heating (Flow sensor 1)
0 - 255
0.1L/min.
541
Flow rate of the secondary (Potable) circuit (Flow sensor A)
0 - 255
0.1L/min.
578
Flow rate of the secondary (Potable) circuit (Flow sensor A) at time of error
0 - 255
0.1L/min.
542
Flow rate of the primary circuit (Flow sensor B)
0 - 255
0.1L/min.
579
Flow rate of the primary circuit (Flow sensor B) at time of error
0 - 255
0.1L/min.
533
Indoor unit - Flow water temp. (THW3)
–39 - 110
°C
534
Indoor unit - DHW supply temp. (THW4)
–39 - 110
°C
573
Indoor unit - DHW supply temp. (THW4) at time of error
–39 - 110
°C
535
Indoor unit - Stored water temp. (upper)(THW5A)
–39 - 110
°C
574
Indoor unit - Stored water temp. (upper)(THW5A) at time of error
–39 - 110
°C
550
Indoor unit - Error postponement history 1 (latest)
Displays postponement code.
("– –" is displays if no postponement code is present.)
—
551
Indoor unit - Operation control at time of error
0 Standard, 1 Heater
—
552
Indoor unit - Operation mode at time of error
0 OFF, 1 DHW, 2 Heating
5 Freeze protection, 6 Operation stop, 7 Defrost
—
553
Indoor unit - Output signal information at time of error
Refer to detail contents described hereinafter
—
554
Indoor unit - Input signal information at time of error
Refer to detail contents described hereinafter
—
555
Indoor unit - Zone 1 room temp. (TH1A) at time of error
–39 - 88
°C
556
Indoor unit - Zone 2 room temp. (TH1B) at time of error
–39 - 88
°C
558
Indoor unit - Flow water temp. (THW1) at time of error
–39 - 110
°C
559
Indoor unit - Return water temp. (THW2) at time of error
–39 - 110
°C
560
Indoor unit - Stored water temp.(lower) (THW5) at time of error
–39 - 110
°C
567
Indoor unit - Failure (P1/L5) thermistor
0 Failure thermistor is none, 1 TH1A, 2 TH2, 3 THW1, 4 THW2,
5 THWB1, 6 THW5B, 7 THWB2, 8 TH1B, 9 THW3, A THW6,
B THW7, C THW8, D THW9, E THW4, F THW5A
—
575
Indoor unit - Failure (LF) folw sensor
0 Failure flow sensor is none,
1 Flow sensor 1,
2 Flow sensor A,
3 Flow sensor B
—
576
Indoor unit - Failure (LU) pump
0 Failure pump is none,
1 Water circulation pump 1,
2 Water circulation pump A
—
569
Operated Flow switch / Flow sensor at time of failure (L7)
0 No operated flow switch, 1 Flow switch 1, 2 Flow switch 2,
3 Flow switch 3, 4 Flow sensor 1, 5 Flow sensor B
—
571
Flow rate for space heating at time of error (Flow sensor 1)
0 - 255
0.1L/min.
572
Indoor unit - Flow water temp. (THW3) at time of error
–39 - 110
°C
Enter code 190 to see the first four digits and code 191 to see the last four digits.