GCH15010
78
Notes on replacing the parts
When installing the parts that are not listed above, observe the tightening torques in accordance with Table 11-1.
Always use a new O-ring or gasket.
Table 11-1
Size
[inch]
Recommended tightening torque
[Nm]
Gasket
30 ± 2
42 ± 2
11 ± 2
17 ± 2
18 ± 3
G1 1/2
G1
G1/2
G1/4
O-ring
Air vent (Automatic)
Drain cock
Air vent (manual)
0.25 ± 0.05
0.25 ± 0.05
After the procedure is complete, ensure that no water leaks.