3. Piping diagram for 2-zone temperature control
The following component parts are required for piping for 2-zone control opera-
tion.
Arrange the following component parts.
Mixing tank (field supply)
Motorized mixing valve (field supply)
Water circulation pump (× 2) (field supply)
Flow switch (× 2) (field supply)
Thermistor (× 4) *2 sets of (PAC-TH011-E) thersmistors are required.
Wire the component parts to the water circuit referring to the figure below.
For more details on wiring, refer to “4.7 Wiring for 2-zone temperature controls”.
Note: Do not install the thermistors on the mixing tank. This could affect
correct monitoring of flow and return temperatures through each
zone.
Install the Zone2 flow temp. thermistor (THW8) near the mixing valve.
•
•
•
•
•
Thermistor (THW6): Zone1 flow temp.
Thermistor (THW7): Zone1 return temp.
Thermistor (THW8): Zone2 flow temp.
Thermistor (THW9): Zone2 return temp.
THW6
THW7
THW8
THW9
Mixing tank
Motorized
mixing valve
Water circulation pump 2
(Zone1)
Flow switch 2 (Zone1)
Water circulation pump 3
(Zone2)
Flow switch 3 (Zone2)
Heat emitters (Zone1)
Heat emitters (Zone2)
1-zone temperature control
2-zone temperature control
1-zone temperature control with boiler
2-zone temperature control with boiler
1.
Zone1 heat emitters (e.g. radiator, fan coil unit) (field supply)
2.
Mixing tank (field supply)
3.
Zone1 flow water temp. thermistor (THW6) (option)
4. Zone1 return water temp. thermistor (THW7) (option)
5.
Zone1 water circulation pump (field supply)
6.
Zone1 flow switch (field supply)
7.
Motorized mixing valve (field supply)
8.
Zone2 flow water temp. thermistor (THW8) (option)
3.5 Local system
Zone1
Zone1
Zone1
Zone2
Zone1
Zone1
Zone2
Note: Cooling mode cannot run under 2-zone temperature control but can run both in Zone1 and Zone2 under 1-zone temperature control.
3. System
9. Zone2 return water temp. thermistor (THW9) (option)
10.
Zone2 water circulation pump (field supply)
11.
Zone2 flow switch (field supply)
12.
Zone2 heat emitters (e.g. underfloor heating) (field supply)
13.
Boiler flow water temp. thermistor (THWB1) (option)
14. Boiler return water temp. thermistor (THWB2) (option)
15. Boiler