21
Note:
1. When the hydrobox is powered via outdoor unit, the maximum grand total current of (a)+(b) is 3.0 A.
2. Do not connect multiple water circulation pumps directly to each output (OUT1, OUT2, and OUT3). In such a case, connect them via (a) relay(s).
3. Connect an appropriate surge absorber to OUT10 (TBO.1 1-2) depending on the load at site.
Wiring specification and field supply parts
Item
Name
Model and specifications
External
output
function
Outputs
wire
Use sheathed vinyl coated cord or cable.
Max. 30 m
Wire type: CV, CVS or equivalent
Wire size: Stranded wire 0.5 mm² to 1.25 mm²
Solid wire: ø0.65 mm to ø1.2 mm
4.5.3 Outputs
Name
Terminal block Connector Item
OFF
ON
Signal/Max current
Max. total current
OUT1
TBO.1 3-4
—
Water circulation pump 1 output (Space heating & DHW)
OFF
ON
230V AC 1.0 A Max
3.0 A (a)
OUT2
TBO.1 5-6
—
Water circulation pump 2 output (Space heating for Zone1) OFF
ON
230V AC 1.0 A Max
OUT3
TBO.1 7-8
—
Water circulation pump 3 output (Space heating for Zone2) OFF
ON
230V AC 1.0 A Max
OUT4
TBO.1 9-11
—
3-way valve (2-way valve 1) output
Heating
DHW
230V AC 0.1 A Max
3.0 A (b)
OUT5
TBO.1 12-13
—
Mixing valve output
Stop
Close
230V AC 0.1 A Max
TBO.1 13-14
Stop
Open
OUT6
TBO.3 1-2
—
Booster heater 1 output
OFF
ON
230V AC 0.5 A Max (Relay)
OUT7
TBO.3 3-4
—
Booster heater 2 output
OFF
ON
230V AC 0.5 A Max (Relay)
OUT8
TBO.2 11-12
—
Booster heater 2+ output
OFF
ON
230V AC 0.5 A Max (Relay)
OUT9
TBO.2 9-10
CNIH
Immersion heater output
OFF
ON
230V AC 0.5 A Max (Relay)
OUT11 TBO.2 1-2
—
Error output
Normal
Error
230V AC 0.5 A Max
OUT12 TBO.2 3-4
—
Defrost output
Normal
Defrost
230V AC 0.5 A Max
OUT13 TBO.2 7-8
—
2-way valve 2 output
DHW
Heating
230V AC 0.1 A Max
BC
TBO.3 5-6
—
Booster heater protection output
OFF
(BHT open)
ON
(BHT short)
230V AC 0.5 A Max
OUT10 TBO.1 1-2
—
Boiler output
OFF
ON
non-voltage contact
• 220 - 240V AC (30V DC)
0.5A or less
• 10 mA 5V DC or more
—
BHT
TBO.2 13-14 CNBHT
Thermostat for booster heater
Thermostat Normal: short / High temp.: open
N
L
TBO.1
12 13 14
9 10 11
6 7 8
3 4 5
1 2
12 13 14
9 10 11
6 7 8
3 4 5
1 2
TBO.2
OUT5
OUT1 OUT2 OUT3 OUT4
N L N L N L N
L
OUT10
N L
OUT11
N L
OUT12
6
3 4 5
1 2
TBO.3
L
OUT6
L
L
OUT7 BC
BHT
N L
OUT9
N L
OUT13
N L
N
OUT8
Close Open
4. Electrical work