Mitsubishi General-Purpose Programmable Controller
Renewal Tool

Conversion Adapter

Model

ERNT-ASLT62DA

User’s Manual

50CM-D180172-A(1404)

HEAD OFFICE:Hulic KUDAN BLDG.1-13-5

KUDANKITA CHIYODA-KU

TOKYO 102-0073

JAPAN

NAGOYA ENGINEERING OFFICE:139 SHIMOYASHIKICHO-SHIMOYASHIKI

KASUGAI

AICHI 486-0906

JAPAN

SAFETY PRECAUTIONS

(Always read these precautions prior to use.)

Before using this product, please read this manual carefully and pay full attention to safety to ensure that
the product is used correctly.
The precautions presented in this manual are concerned with this product only. For Programmable
Controller system safety precautions, refer to the user’s manual of the MELSEC-L series CPU module to
be used.
In this manual, the safety precautions are ranked as “WARNING” and “CAUTION.”

Indicates that incorrect handling may cause hazardous conditions,
resulting in death or severe injury.

WARNING

Indicates that incorrect handling may cause hazardous conditions,
resulting in medium or minor injury and/or property damage.

CAUTION

Note that failure to observe the

CAUTION level instructions may lead to a serious consequence

according to the circumstances. Always follow the precautions of both levels because they are important
to personal safety.
Please keep this manual in an easy-to-access location for future reference, and be sure to provide the
manual to the end user.

[Precautions before using]

CAUTION

When making a switch from the MELSEC-AnS Series to the MELSEC-L Series, be sure to
consult user's manual supplied with individual module under the MELSEC-L Series to confirm
differences in various aspects including performance, function, CPU input/output signals and
buffer memory addresses between the two series.

[Installation Precautions]

CAUTION

Use the Conversion Adapter in the environmental conditions that are specified in the general
specification. If the Products are used in any environment beyond the bounds of the general
specification, electric shock, fire, malfunction, or damage to or degradation of the Products will
result.

Do not directly touch any conductive parts of Conversion Adapter. Contact will cause
malfunction or failure in the system.

Fasten the Conversion Adapter and the Mounting Bracket securely with retaining screws, and
tighten the screws by applying torque within specified limits. Loose screws can lead to the
dropping of the Conversion Adapter or Mounting Bracket, possibly causing breakage thereof.
Excessive tightness of the screws can lead to breakage of the screws, Conversion Adapter,
Mounting Bracket, or MELSEC-L Series Module, possibly causing the dropping, shorting, and
malfunction thereof.

Always check for correct match between MELSEC-L Series and the Conversion Adapter.
Incorrect match can cause damage to the MELSEC-L Series Module.

When installing the Conversion Adapter, take care not to get your hand snagged on the
Mounting Bracket or the like. Injury may result.

When installing or removing the MELSEC-L Series Module complete with a Converter
Adapter, be sure to hold it with both hands. Dropping may lead to breakage.

[Wiring Precautions]

WARNING

Before attempting to install the Unit or carry out the necessary wiring, make certain that the
external power supply, used in the system, is shut off on all three phases. Failure to do so may
result in electric shock or damage to the product.

After installation and wiring, close the terminal block cover before turning on the module for
operation. Failure to do so may result in electric shock.

CAUTION

Carry out wiring for the Conversion Adapter correctly after checking the specification and
terminal arrangement for the module used. Connecting a power supply with a different voltage
rating or incorrect wiring may cause a fire or failure.

Tighten the MELSEC-AnS Series terminal installation screws and terminal screw securely by
applying torque within the specified limits. Loose screws will cause short circuit, fire or
malfunction. Excessive tightening will damage the screws or the Conversion Adapter which in
turn will cause dropping of parts, short circuit or malfunction.

Use care to prevent foreign materials including cuttings and wiring debris from entering the
Conversion Adapter or the MELSEC-L Series Module. These will be cause for fire, failure or
malfunction.

[Startup and Maintenance Precautions]

WARNING

Do not touch live terminals. There is a danger of electric shock or malfunction.

Shut off the external power supply for the system in all phases before cleaning or
retightening the terminal screws. Failure to do so may result in electric shock or cause the
MELSEC-Q Series module to fail or malfunction. Loose screws can lead to dropping,
shorting, and malfunction. Excessive tightness of the screws can lead to breakage of the
screws, Conversion Adapter, Mounting Bracket, or MELSEC-Q Series Module, possibly
causing the dropping, shorting, and malfunction thereof.

CAUTION

Do not modify the Conversion Adapter or take it apart. Doing so will cause failure,
malfunction, personal injury, or fire.

Do not drop the Conversion Adapter and Mounting Bracket or do not give a strong impact
to it. This will cause damage.

[Disposal Precautions]

CAUTION

When disposing of the product, treat it as industrial waste.

EMC AND LOW VOLTAGE DIRECTIVES

Compliance to the EMC Directive, which is one of the EU Directives, has been a legal obligation
for the products sold in European countries since 1996 as well as the Low Voltage Directive
since 1997.
Manufacturers who recognize their products are compliant to the EMC and Low Voltage
Directives are required to declare that print a "CE mark" on their products.

Authorized representative in Europe

Authorized representative in Europe is shown below.
Name: Mitsubishi Electric Europe BV
Address: Gothaer strasse 8, 40880 Ratingen, Germany

1

Overview

This manual describes specifications, handling and other information about the Conversion Adapter
“ERNT-ASLT62DA” available as Renewal Tools for the Mitsubishi General-Purpose Programmable
Controller.
The Conversion Adapter is a product for effecting conversion to transcend difference in pin
assignment between the MELSEC-AnS Series and the MELSEC-L Series.
Before attempting to make a switch from MELSEC-AnS Series to MELSEC-L Series in your
installation, consult the user's manual supplied with individual module under the latter series to learn
about how they differ in various aspects including performance and function.

Once you have opened the packaging, verify that it contains the following products.

Product

Shape

Quantity

Conversion Adapter

1

Mounting bracket

1

Mounting bracket fixing screws

(M3.5 x 6)

1

Terminal block cover

1

This manual

1

2

General Specifications

Item

Specifications

Operating ambient
temperature

0 to 55

Storage ambient
temperature

-25 to 75

Operating ambient
humidity

5 to 95%RH

non-condensing

Storage ambient
humidity

Vibration
resistance

Compliant with

JIS B 3502

and

IEC 61131-2

Frequency

Constant

acceleration

Half

amplitude

Sweep count

Under

intermittent

vibration

5 to 8.4Hz

3.5mm

10 times each in

X, Y, Z directions

8.4 to 150Hz

9.8m/s

2

Under

continuous

vibration

5 to 8.4Hz

1.75mm

8.4 to 150Hz

4.9m/s

2

Shock resistance

Compliant with JIS B 3502 and IEC 61131-2

(147 m/s

2

, 3 times each in 3 directions X, Y, Z)

Operating atmosphere

No corrosive gases

Operating altitude *1

0 to 2000m

Installation location

Inside a control panel

Overvoltage category *2

II or less

Pollution degree *3

2

*1

Do not use or store under pressure higher than the atmospheric pressure of altitude 0m.

*2

This indicates the section of the power supply to which the equipment is assumed to be connected between
the public electrical power distribution network and the machinery within premises.
Category II applies to equipment for which electrical power is supplied from fixed facilities.

*3

This index indicates the degree to which conductive material is generated in terms of the environment in
which the equipment is used.
Pollution level 2 is when only non-conductive pollution occurs. A temporary conductivity caused by
condensing must be expected occasionally.

3

Product Specifications

For detail specifications which do not appear in the specification comparison charts contained herein, see the user's manual supplied with the MELSEC-L Series module you use. Those parts of the specification that
differ between the MELSEC-AnS Series and the MELSEC-L Series are where a switch from the first series to the second is subjected to specification-related restrictions. Check the specification of the devices to be
connected for more details.
Furthermore, it is recommended to refer to the “Transition from MELSEC-AnS/QnAS (Small Type) Series to L Series Handbook (Intelligent Function Modules): L (NA)-08259ENG” issued by Mitsubishi Electric.

Conversion Adapter

Model

Before replacement

MELSEC-AnS Series

Module Model

No. of

channels

After replacement

MELSEC-L Series

Module Model

Conversion

Adapter

Weight (g)

No. of

modules

ERNT-ASLT62DA

A1S62DA

2

L60DA4

1

75

Internal circuit diagram of ERNT-ASLT62DA

A1S62DA

Terminal Block

L60DA4

Terminal Block

TB2
TB4
TB6
TB8

TB10
TB12
TB14
TB16
TB18
TB20

TB1
TB3
TB5
TB7
TB9

TB11
TB13
TB15
TB17
TB19

TB2
TB4
TB6
TB8

TB10
TB12
TB14
TB16
TB18

TB1
TB3
TB5
TB7
TB9

TB11
TB13
TB15
TB17

-

+

Terminal

No.

TB1

TB2

TB3

TB5

TB6

TB7

TB8

TB9

TB10

TB11

TB12

TB13

TB14

TB15

TB16

TB17

TB18

TB19

TB20

TB4

Signal
Name

24G

FG

V+

COM

I+

C
H
1

C
H
2

C
H
3

C
H
4

Terminal

No.

TB1

TB2

TB3

TB5

TB6

TB7

TB8

TB9

TB10

TB11

TB12

TB13

TB14

TB15

TB16

TB17

TB18

TB4

SLD

V+

COM

I+

SLD

V+

COM

I+

SLD

V+

COM

I+

+24V

*

1

*

3

*

3

*

3

*

2

Signal
Name

TEST

TEST

Open(24G)

Open(FG)

V+

V-

I+

I-

C
H
1

C
H
2

V+

V-

I+

I-

Open(SLD)

Open(+24V)

Open(SLD)

Open

Open

Open

HLD/CLR

HLD/CLR

< Specification Comparison >

Model

Specifications

MELSEC-AnS Series

MELSEC-L Series

A1S62DA

L60DA4

Digital input

Voltage

1/4000

-4000 to 4000

1/8000

-8000 to 8000

1/12000

-12000 to 12000

-20480 to 20479

(When using the scaling function

-32768 to 32767)

Current

1/4000

0 to 4000

1/8000

0 to 8000

1/12000

0 to 12000

Analog output

Voltage

-10 to 0 to 10VDC (external load resistance

2kΩ

to

1MΩ

)

-10 to 10VDC (external load resistance

1kΩ

to

1MΩ

)

Current

0 to 20mADC (external load resistance

to

600Ω

)

0 to 20mADC (external load resistance

to

600Ω

)

I/O characteristics

Maximum resolution

Overall accuracy

±1.0% (Voltage output

±100mV, Current output

±200μA

)

Ambient temperature 25±5

℃:

Within ±0.1% (voltage

±10mV, current

±20μA

)

Ambient temperature 0 to 55

℃:

Within ±0.3% (voltage

±30mV, current

±60μA

)

Maximum conversion speed

Maximum 25ms/2 channels (same for 1 channel)

20μs

/channel

Absolute maximum output

Voltage

±12V

Current

:+

28mA

Analog output points

2 channels

4 channels

Insulation
method

Between output
terminals and
programmable
controller power
supply

Photocoupler insulation

Photocoupler insulation

Between terminals

No insulation

No insulation

Between external
power supply and
analog output

Transformer insulation

Number of occupied I/O points

32 points

16 points

Connected terminal block

20-point terminal block

18-point terminal block

External
power supply

Voltage

24VDC +20%

-15%

Current

0.18A

Current consumption

0.8A

0.16A

*1

When the offset value is set to 0V and the gain value is set to 10V.

*2

When the offset value is set to 4mA and the gain value is set to 20mA.

Make sure the

section of the above table meets the specification of the machines and equipment connected to the MELSEC-L Series module.

Precautions for programming

(1)

A1S62DA and L60DA4 differ from each other in the way input/output signals (X, Y) and buffer memory addresses are allocated. Therefore, you need make necessary changes to the sequence program that is

used.

(2)

CH3 and CH4 of L60DA4 cannot be used.

Precautions for wiring

L60DA4 is not provided with a terminal for Offset/Gain setting or Output Hold/Clear setting
purposes.

Make Output Hold/Clear setting by choosing an appropriate L60DA4 intelligent function
module switch setting.
For more details about the Offset/Gain setting and Output Hold/Clear setting, see the L60DA4
User’s Manual.

L60DA4 requires power supply. Therefore, use the opened terminals(TB18, TB19) of
A1S62DA to provide 24VDC power supply to L60DA4.

Connect the shield wires of each channel to the opened terminals (TB11 and TB17) of
A1S62DA, and make sure to ground the FG terminal (TB18) of L60DA4 by using the opened
terminal (TB20) of A1S62DA.

*

1

*

2

Resolution

1/4000

1/8000

1/12000

Analog output

Voltage

output

(*1)

Current

output

(*2)

Digital input value

4000

8000

12000

10V

20mA

2000

4000

6000

5V

12mA

0

0

0

0V

4mA

-2000

-4000

-6000

-5V

-

-4000

-8000

-12000

-10V

-

1/4000

1/8000

1/12000

Voltage output

2.5mV

1.25mV

0.83mV

Current output

5μA

2.5μA

1.7μA

Analog output range

Digital value

Resolution

Voltage

0 to 5V

0 to 20000

250μV

1 to 5V

200μV

-10 to 10V

-20000 to 20000

500μV

User range setting

333μV

Current

0 to 20mA

0 to 20000

1000

A

4 to 20mA

800

A

User range setting

-20000 to 20000

700

A

*

3