Graphic Operation Terminal GOT-F900
HPP Mode 10
10-19
10.7
BFM MONITOR
The contents of buffer memories relating to special blocks connected to the FX
2N
/FX
2NC
PLC,
can be read / written to.
The model of the connected special blocks are automatically recognized and the contents of
the buffer memories are displayed together with the name and the unit. Accordingly, operations
can be checked without performing any manual procedure.
•
Applicable special blocks
Analog input: FX
2N
-4AD, FX
2N
-4DA, FX
2N
-4AD-PT and FX
2N
-4AD-TC
High-speed counter: FX
2N
-1HC
Pulse output: FX
2N
-1PG
u
u
u
u
Basic operation
•
Serial block Nos. are assigned to special blocks connected to the FX
2N
/FX
2NC
Series basic
unit. "0" is assigned to the special block nearest to the basic unit. Up to eight special blocks
can be monitored and set.
For each available special block, its model name is displayed.
For each unavailable special unit (such as the FX-10GM and the FX-20GM), "UNKNOWN"
is displayed.
When no special blocks are connected, "NONE" is displayed.
•
When a special block to be monitored is selected, the buffer memory list is displayed as
shown below.
•
The set value can be entered using the touch keys
on the screen.
To enter a numeric, use the ten-key pad displayed
at the bottom of the screen.
•
The DETAIL key is provided for the FX
2N
-1PG, etc.
so that the contents of the buffer memories can be
monitored in detail.
n
n
n
n
Important point
•
Setting of the buffer memories
The contents of the buffer memories set using this function are treated as follows when the
power of the special block is turned off.
-
FX
2N
-4AD, FX
2N
-4DA, FX
2N
-4AD-PT and FX
2N
-4AD-TC
The setting contents are saved in the built-in EEPROM, and kept stored even if the power
is turned off.
-
FX
2N
-1HC and FX
2N
-1PG
The setting contents are saved in the built-in RAM, therefore deleted when the power is
turned off.
When the buffer memories have been set using a sequence program (TO instruction), the
sequence program priority.
Use the buffer memory monitor function to perform initial setting of special blocks and monitor
buffer memories.
5
(BLOCK 1)
[ 4DA ]
END
6
0
1
7
8
2
3
9
4
CLR
ENT
OUTPUT MODE
OUTPUT DATA
DATA HOLDING
OFFSET DATA
GAIN DATA
G/O ADJUST
ERR STATUS UNDEFINED
(0mA to 20mA)
[ 0. 000](mA)
[ 0. 000](mA)
[ 20. 000](mA)
HOLD
FORBID
CH1
CH2
CH3
CH4
INIT
Summary of Contents for F930GOT-BWD
Page 1: ...OPERATION MANUAL GOT F900 ...
Page 4: ...Graphic Operation Terminal GOT F900 ii ...
Page 6: ...Graphic Operation Terminal GOT F900 iv ...
Page 14: ...Graphic Operation Terminal GOT F900 Contents xii ...
Page 16: ...Graphic Operation Terminal GOT F900 Manual configuration and various data 2 MEMO ...
Page 30: ...Graphic Operation Terminal GOT F900 Introduction 1 1 14 MEMO ...
Page 34: ...Graphic Operation Terminal GOT F900 Outside dimensions 3 3 2 MEMO ...
Page 38: ...Graphic Operation Terminal GOT F900 Part names 4 4 4 MEMO ...
Page 42: ...Graphic Operation Terminal GOT F900 Installation 5 5 4 MEMO ...
Page 90: ...Graphic Operation Terminal GOT F900 Creation of Display Screens 8 8 32 MEMO ...
Page 154: ...Graphic Operation Terminal GOT F900 Alarm Mode 12 12 14 MEMO ...
Page 164: ...Graphic Operation Terminal GOT F900 Test Mode 13 13 10 MEMO ...
Page 174: ...Graphic Operation Terminal GOT F900 Connection to Bar Code Reader 15 15 2 MEMO ...
Page 180: ...Graphic Operation Terminal GOT F900 Screen Hard Copy Function 16 16 6 MEMO ...
Page 320: ...Graphic Operation Terminal GOT F900 Creation of Display Screen GT Designer 20 20 46 MEMO ...
Page 341: ......