24
SPECIFICATIONS
1.3 Standard connection diagram and terminal
specifications
1.3.1
Internal block diagram
(1) FR-A700
*1
A common mode choke is provided for the 55K or less.
*2
For the 75K or more, a jumper across terminal P1-P/
+
is not provided. Always connect a DC reactor provided.
When a DC reactor is connected to the 55K or less, remove the jumper across P1-P/
+
.
*3
A relay is used for the 200V class 11K and 30K to 90K and 400V class 11K, 15K and 110K to 500K.
*4
The 200V class 0.4K and 0.75K are not provided with the EMC filter ON/OFF connector.
*5
To supply power to the control circuit separately, remove the jumper across R/L1-R1/L11 and S/L2-S1/L21.
*6
Terminal function can be changed using [
Pr. 178 to Pr. 189 Input terminal selection
].
*7
Terminal input specifications can be changed by analog input specifications switchover ([
Pr. 73, Pr. 267
]). Note that the
current at terminal 2 and 4 is always 4 to 20mA when the voltage/current input switch is set to ON.
Terminal 2 : Initial value 0 to 5VDC (can be changed to 0 to 10VDC, 4 to 20mADC)
Terminal 4 : Initial value 4 to 20mADC (can be changed to 0 to 5VDC, 0 to 10VDC)
Terminal 1 : Initial value 0 to 10VDC (can be changed to 0 to 5VDC)
*8
It is recommended to use 2W1k
when the frequency setting signal is changed frequently.
*9
Remove the jumper across terminal PR-PX when connecting a brake resistor. (0.4K to 7.5K)
Terminal PR is provided for the 0.4K to 22K.
*10 The built-in brake resistor is provided for the 7.5K or less. A brake transistor is provided for the 22K or less.
*11 A CN8 connector is provided for the 75K or more.
*12 Terminal function can be changed using [
Pr. 190 to Pr. 196 Output terminal selection
].
*13 It is not necessary when calibrating the meter from the operation panel.
5.5V
RXD+
TXD+
SG
VCC
R/L1
S/L2
T/L3
IM
U
V
W
R
TR
*10
P1
P/+
+
C
N/-
PR
PX
R1/L11
S1/L21
SD
POWER
CHARGE
Jumper
*9
*10
Jumper
*2
Jumper
*5
CN8
*11
AM
5
RUN
SU
IPF
OL
FU
SE
(-)
(+)
5V
(Permissible load
current 100mA)
PC
SINK
SOURCE
STF
STR
STOP
RH
RM
RL
RT
MRS
RES
CS
SD
JOG
24V
MC
*3
R
Capacitive
filter
ON
C1
B1
A1
RA
C2
B2
A2
RA
[
Pr.291
= 10, 11,
20, 21, 100]
[
Pr.291
= 0, 1]
FM
+
-
5V
[
Pr.291
=
1, 11, 21, 100]
[
Pr.291
= 0, 10, 20]
AU
AU
PTC
AU/PTC
switch over
switch
2
3
1
(+)
(-)
(+)
10E
10V
10
5V
2
*7
5
4
*7
1
*7
(-)
Operation
panel
FR-DU07
TXD-
RXD-
OFF
MCCB
Three-phase AC
power supply
Earth
(Ground)
Forward rotation start
*6
Reverse rotation start
*6
Start self-holding selection
*6
Middle speed
*6
High speed
*6
Low speed
*6
Multi-speed
selection
Second function selection
*6
Output stop
*6
Reset
*6
Terminal 4 input selection
(PTC input)
*6
Jog mode
(Pulse train input)
*6
Selection of automatic restart
after instantaneous
power failure
*6
24VDC power supply
(Common for external power supply transistor)
Contact input common
Control
circuit
EMC filter
ON/OFF
connecter
*4
Option
connector 1
Option
connector 2
Option
connector 3
Frequency setting
potentiometer
1/2W1k
Ω
*8
USB
connector
PU
connector
Terminating
resistor
Auxiliary
input
Terminal 4 input
(Current input)
Voltage/
current
input switch
*7
Voltage/
current
input switch
*7
GND
Earth (Ground)
Data
reception
Data
transmission
RS-485
terminals
Open collector output common
Sink/source common
Frequency detection
*12
Running
*12
Up to frequency
*12
Instantaneous power failure
*12
Overload
*12
Relay output 2
*12
Relay output 1
(Fault output)
*12
Motor
(0 to 10VDC)
Analog signal output
Moving-coil type
1mA full-scale
(Frequency meter, etc.)
Indicator
Calibration
resistor
*13
Converter
Zero-phase
reactor
*1
Control
power
supply
Current
detection
Gate drive
circuit
Voltage
detection
Inverter
Summary of Contents for FR-A700 Series
Page 245: ...279 2 PARAMETER PARAMETER MEMO ...
Page 440: ...474 PARAMETER MEMO ...
Page 522: ...556 SELECTION MEMO ...