2.16.2 Power failure stop mode [Pr. 261, 262 to 266
*
, Pr. 294
*
]
(common)
When a power failure or undervoltage occurs, the inverter can be decelerated to a stop or can be decelerated and re-
accelerated to the set frequency.
common
(*[Pr. 294] is not available for
.)
(*[Pr. 262 to 266, 294] are not available for
.)
F700
E700
D700
[Pr. ]
Name
Initial
Value
Setting
Range
Description
Available Inverters
261
Power failure stop
selection
0
0
Coasts to stop
When undervoltage or power failure occurs, the
inverter output is shut off.
{
{
{
1
Without under
voltage
avoidance
When undervoltage or a power failure
occurs, the inverter can be
decelerated to a stop.
{
{
{
11
With under
voltage
avoidance
{
—
—
2
Without under
voltage
avoidance
When undervoltage or a power failure
occurs, the inverter can be
decelerated to a stop.
If power is restored during a power
failure, the inverter accelerates
again.
{
{
{
12
With under
voltage
avoidance
{
—
—
262
Subtracted frequency at
deceleration start
3Hz
0 to 20Hz
Normally operation can be performed with the initial
value unchanged. But adjust the frequency according
to the magnitude of the load specifications (moment of
inertia, torque).
{
{
—
263
Subtraction starting
frequency
60Hz
0 to
120Hz
When output frequency
≥
[
Pr. 263
]
Decelerate from the speed obtained from output
frequency minus [
Pr. 262
].
When output frequency < [
Pr. 263
]
Decelerate from output frequency
{
{
—
9999
Decelerate from the speed obtained from output frequency
minus [
Pr. 262
].
264
Power-failure deceleration
time 1
5s
0 to 3600/
360s
*
Set a deceleration slope down to the frequency set in
[
Pr. 266
].
{
{
—
265
Power-failure deceleration
time 2
9999
0 to 3600/
360s
*
Set a deceleration slope below the frequency set in
[
Pr. 266
].
{
{
—
9999
Same slope as in [
Pr. 264
]
266
Power failure deceleration
time switchover frequency
60Hz
0 to
400Hz
Set the frequency at which the deceleration slope is
switched from the [
Pr. 264
] setting to the [
Pr. 265
]
setting.
{
{
—
294
UV avoidance voltage gain 100% 0 to 200%
Adjusts the response level during undervoltage
avoidance operation. A larger setting will improve
responsiveness to the bus voltage change. Since the
regeneration amount is large when the inertia is large,
decrease the setting value.
{
—
—
A700
F700
E700
D700
* The setting range is 0 to 3600 and the setting increments is 0.1s when [
Pr. 21 Acceleration/deceleration time increments
= 0] (initial
value) and the setting range is 0 to 360s and the setting increments is 0.01s when [
Pr. 21
= 1].