27
1
S
PECIFI
C
A
T
IONS
SPECIFICATIONS
(4) FR-D700
*1
Operation panel is not removable from the inverter.
*2
Terminal function can be changed using [
Pr. 178 to Pr. 182 Input terminal selection
].
*3
Take caution not to short across terminals PC and SD when using between those terminals as 24VDC power supply.
*4
It is recommended to use 2W1k
when the frequency setting signal is changed frequently.
*5
Can be changed by switching analog input specification ([
Pr.73
]) Terminal 10 and 2 can be used as PTC input terminals
([
Pr.561
]).
*6
Can be changed by switching analog input specification ([
Pr.267
])
To input voltage, set the voltage/current input switch to "V". To input current, set the voltage/current input switch to "I" (initial
setting).
*7
Terminal function can be changed using [
Pr. 190 and Pr. 192 Output terminal selection
].
*8
It is not necessary when calibrating the meter from the operation panel.
*9
Common terminal for terminal SO is terminal SC (Terminal SC is connected to terminal SD inside of the inverter.)
R/L1
S/L2
T/L3
P1
P/+
R
+
C
N/-
PR
TR
U
V
W
IM
24V
S1
S2
SC
STF
STR
RH
RM
RL
RA
A
B
C
FM
SD
RUN
SE
SO
+
-
SC
SOURCE
SINK
24V
5V
SD
PC
10
1
2
3
2 *5
5
4 *6
(+)
(-)
Jumper
Control
circuit
PU
connector
Voltage/
current
input switch
*6
Converter
Inverter
MC
MCCB
Three-phase AC
power supply
Earth (Ground)
Open collector output common
Sink/source common
Relay output
*7
(Fault output)
Motor
Moving-coil type
1mA full-scale
Indicator (Frequency meter, etc.)
Control
power
supply
Current
detection
Gate drive
circuit
Voltage
detection
Output shutoff (Line 1)
Shorting wire
Output shutoff (Line 2)
Output shutoff terminal common
Current detection
circuit
Operation
panel
Forward rotation start
*2
Reverse rotation start
*2
Middle speed
*2
High speed
*2
Low speed
*2
Multi-speed
selection
Contact input common
24VDC power supply
(Common for external power supply transistor)
Frequency setting
potentiometer
Terminal 4 input
(Current input)
*4
*3
Safety monitor output
*9
Running
*7
Three-phase 400V class