63
1
S
PECIFI
C
A
T
IONS
SPECIFICATIONS
41
141
FB
Speed detection
Output when the actual motor speed (estimated actual
speed value) reaches the [
Pr. 42 (Pr. 50, Pr. 116)
] setting.
{
─
─
─
42
142
FB2
Second speed detection
{
─
─
─
43
143
FB3
Third speed detection
{
─
─
─
44
144
RUN2 Inverter running 2
• Output during forward rotation or the reverse rotation
signal is ON.
• Output at deceleration even during forward rotation
or the reverse rotation signal is OFF.
(Does not output during pre-excitation LX is ON.)
• Output during the orientation command signal (X22)
is ON.
• Switched ON when the servo is ON (LX-ON) under
position control.
(Switched OFF when the servo is OFF (LX-OFF).
{
─
─
─
45
145
RUN3
Inverter running and start
command is on
Output when the inverter running and start commands
are ON.
{
{
─
─
46
146
Y46
During deceleration due to
power failure stop function
Output when the power failure-time deceleration
function is executed(retained until release).
{
{
{
{
47
147
PID
During PID control
activated
Output during PID control.
{
{
{
{
64
164
Y64
During retry
Output during retry processing.
{
{
{
{
70
170
SLEEP PID output interruption
Output when the PID output interruption function is
executed.
{
{
─
{
80
180
SAFE
Safety monitor output
Output while safety stop function is activated.
─
─
─
{
84
184
RDY
Position control
preparation ready
Signal is output when the servo is ON (LX-ON) and
ready to operate.
*4
{
─
─
─
85
185
Y85
DC feeding
Output during power failure or under voltage of AC
power.
{
─
─
─
86
186
Y86
Control circuit capacitor
life
*5
Output when the control circuit capacitor life falls below
10% of ([
Pr. 257
]).
{
{
{
─
87
187
Y87
Main circuit capacitor life
*5
Output when the main circuit capacitor life falls below
85% of ([
Pr. 258
]).
{
{
{
─
88
188
Y88
Cooling fan life
*5
Output when the speed of the cooling fan falls below
50%.
{
{
{
─
89
189
Y89
Inrush current limit circuit
life
*5
Output when the inrush current limit circuit life falls
below 10% of ([
Pr. 256
]).
{
{
{
─
90
190
Y90
Life alarm
Output when any of the control circuit capacitor, main
circuit capacitor and inrush current limit circuit or the
cooling fan approaches the end of its service life.
{
{
{
{
91
191
Y91
Fault output 3 (power-off
signal)
Output when a fault occurs due to the internal circuit
failure of the inverter wiring mistake.
{
{
{
{
92
192
Y92
Energy saving average
value updated timing
Turned ON and OFF alternately every time the power
saving average value is updated when the power
saving monitor is used.
Cannot be set to a relay output terminal.
{
{
─
─
93
193
Y93
Current average value
monitor signal
Average current value and maintenance timer value
are output as pulses.
Cannot be set to a relay output terminal.
{
{
{
{
94
194
ALM2
Fault output 2
Output when the inverter protective function is
activated to stop the output (fault).
Continue outputting the signal during inverter reset and
stop outputting after reset is cancelled.
*3
{
{
─
─
95
195
Y95
Maintenance timer signal
Output when [
Pr. 503
] rises to or above the [
Pr. 504
]
setting.
{
{
{
{
96
196
REM
Remote output
Output to the terminal when a value is set to the
parameter.
{
{
{
{
97
197
ER
Alarm output 2
When [
Pr. 875
= "0"] (initial value), the signal is output
when the inverter protective function is activated to
stop the output (major fault).
When [
Pr. 875
= "1"], the signal is output when the
inverter protective function is activated at occurrence of
OHT/THM/PTC error and deceleration is started.
Output when other protective functions are activated to
stop output.
{
─
─
─
Setting
Signal
Name
Functions
Operation
Available Inverters
Positive
logic
Negative
logic
A700
F700
E700
D700
Summary of Contents for FR-A700 Series
Page 245: ...279 2 PARAMETER PARAMETER MEMO ...
Page 440: ...474 PARAMETER MEMO ...
Page 522: ...556 SELECTION MEMO ...