Main circuit terminal specifications
2.2 Main circuit terminal specifications
2.2.1
Specification of main circuit terminal
Terminal
Symbol
Terminal Name
Description
R/L1,
S/L2,
T/L3
AC power input
Connect to the commercial power supply.
U, V, W
Inverter output
Connect a three-phase squirrel-cage motor.
R1/L11,
S1/L21
Power supply for
control circuit
Connected to the AC power supply terminals R/L1 and S/L2. To retain the
fault display and fault output, remove the jumpers from terminals R/L1-R1/
L11 and S/L2-S1/L21 and apply external power to these terminals.
Do not turn off the power supply for control circuit (R1/L11, S1/L21) with the
main circuit power (R/L1, S/L2, T/L3) on. Doing so may damage the
inverter. The circuit should be configured so that the main circuit power (R/
L1, S/L2, T/L3) is also turned off when the power supply for control circuit
(R1/L11, S1/L21) is off.
Power supply capacity for the 15K or less is 90VA and for the 18.5K or
more is 100VA.
P/+, N/-
DC terminal
Do not connect any options.
Earth (Ground)
For earthing (grounding) the inverter chassis. Must be earthed
(grounded).