7 SPECIFICATIONS
7.1 Rating
7.1.1
Inverter rating
z
200V class
*1
The applicable motor capacity indicated is the maximum capacity applicable for use of the Mitsubishi 4-pole standard motor.
*2
The rated output capacity indicated assumes that the output voltage is 220V.
*3
The % value of the overload current rating indicated is the ratio of the overload current to the inverter's rated output current. For repeated duty,
allow time for the inverter and motor to return to or below the temperatures under 100% load.
*4
The maximum output voltage does not exceed the power supply voltage. The maximum output voltage can be changed within the setting range.
However, the pulse voltage value of the inverter output side voltage remains unchanged at about
that of the power supply.
*5
The power supply capacity varies with the value of the power supply side inverter impedance (including those of the input reactor and cables).
*6
FR-DU07:IP40 (except for the PU connector)
Type FR-A721-
K
5.5
7.5
11
15
18.5
22
30
37
45
55
Applicable motor capacity (kW)
*1
5.5
7.5
11
15
18.5
22
30
37
45
55
Output
Rated capacity (kVA)
*2
9.2
12.6
17.6
23.3
29
34
44
55
67
82
Rated current (A)
24
33
46
61
76
90
115
145
175
215
Overload current rating
*3
150% 60s, 200% 3s (inverse time characteristics)
surrounding air temperature 50°C
Voltage
*4
Three-phase 200 to 240V
Regenerative braking torque
100% continuous 150% 60s
Pow
er supply
Rated input
AC voltage/frequency
Three-phase 200 to 220V 50Hz, 200 to 240V 60Hz
Permissible AC voltage fluctuation
170 to 242V 50Hz,170 to 264V 60Hz
Permissible frequency fluctuation
±
5%
Power supply capacity (kVA)
*5
12
17
20
28
34
41
52
66
80
100
Protective structure (JEM 1030)
*6
Open type (IP00)
Cooling system
Forced air cooling
Approx. mass (kg)
20
22
33
35
50
52
69
87
90
120
2