11
3
3
WIRING
3.1
Terminal block
Terminal block layout
Terminal
No.
Terminal Name
Definition
1-A
V+ (VP)
Voltage output (approx. 5V to V-)
1-B
D+ (RXD/TXD-P)
Sends and receives PROFIBUS (B-line)
2-A
D+ (RXD/TXD-P)
Sends and receives PROFIBUS (B-line)
2-B
D+ (RXD/TXD-N)
Sends and receives PROFIBUS signal- (A-line)
3-A
D+ (RXD/TXD-N)
Sends and receives PROFIBUS signal- (A-line)
3-B
GND of D+/D-
4-A
(To connect a terminating resistor)
4-B
(To connect a terminating resistor)
5-A
GND of D+/D-
5-B
CNTR
Control signal (sending request from the inverter)
6-A
FG
(Connected to the earth of the inverter unit)
6-B
FG
(Connected to the earth of the inverter unit)
*1
Use this when connecting a terminating resistor.
(Refer to page 15)
*2
It may not be necessary depending on the master used.
D+ D- V- D- CNTR FG
V+ D+ D- D+ V- FG
1
2
3
4
5
6
A
1
2
3
4
5
6
B