14
WIRING
(2) Loosen the terminal screw and insert the cable into the terminal.
Tighten each cable with fixing screws to the recommended tightening torque.
Screw Size
Tightening Torque
Cable Size
Screwdriver
M2
0.22N•m to 0.25N•m
0.3mm
2
to 0.75mm
2
Small
flat-blade screwdriver
(Tip thickness: 0.4mm /tip width: 2.5mm)
CAUTION
• Undertightening can cause cable disconnection or malfunction. Overtightening can cause a short circuit or
malfunction due to damage to the screw or unit.
D+ D-
V-
<Cable connection example>
To next inverter
To master
D+ D-
V-
D+ D-
V-
<Connection example of multiple inverters>