INVERTER SETTING
4.1
Parameter list
The following parameters are used for the communication option (FR-A7NP).
Set the values according to need.
*1
Parameters which can be displayed when the plug-in option (FR-A7NP) is mounted.
*2
The setting is apllied after inverter reset or at the next power-ON.
Parameter
Number
Name
Setting Range
Minimum
Setting
Increments
Initial
Value
Refer to
page
79
Operation mode selection
0 to 4, 6, 7
1
0
338
Communication operation command
source
0, 1
1
0
339
Communication speed command
source
0, 1, 2
1
0
340
Communication startup mode selection
0, 1, 10
1
0
342
Communication EEPROM write
selection
0, 1
1
0
349
Communication reset selection
0, 1
1
0
500
Communication error execution waiting
time
0 to 999.8s
0.1s
0
501
Communication error occurrence count
display
0
1
0
502
Stop mode selection at communication
error
0, 1, 2, 3
1
0
550
NET mode operation command source
selection
0, 2, 9999
1
9999